Unit installation
Installer and user reference guide
63
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
▪
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note: If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
▪
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
▪
Where the voltage fluctuates a lot
▪
In vehicles or vessels
▪
Where acidic or alkaline vapour is present
16.1.2 Installation site requirements of the heat exchanger unit
The heat exchanger unit has the same installation site requirements as the
compressor unit, and a few additional ones:
▪
Heat exchanger fins are sharp and injury is possible. Choose an installation
location where there is no risk for injury (especially in areas where children play).
▪
Service space.
Mind the following requirements:
≥10
≥50
a
b
≥100
≥500
≥100
(mm)
a
Air suction side
b
Air discharge side
▪
Protective guards.
Make sure to install protective guards on the suction and
discharge side to prevent somebody from touching the fan blades or heat
exchanger.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated properly.