19
|
Configuration
Installer and user reference guide
118
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Setting
Value / Description
[1‑41]
Shows the current
heating comfort
setting.
For more information, see setting [2‑82].
19.2.8 Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The display and the settings differ depending on
the model.
Model
Display
Setting/value
5 HP
7‑LEDs display
The seven LEDs give a binary representation of the setting/
value number.
8 HP
7‑segments display
The three 7‑segments show the setting/value number.
For more information and advice about the impact of the following settings, see
"19.3 Energy saving and optimum
•
In case of 5 HP: settings [2‑8], [2‑9], [2‑41] and [2‑42]
•
In case of 8 HP: settings [2‑8], [2‑9], [2‑81] and [2‑82]
Setting
Value
(8 HP)
(5 HP)
Description
[2‑8]
T
e
target temperature during cooling
operation.
0
(default
)
(default)
Auto
2
6°C
3
7°C
4
8°C
5
9°C
6
10°C
7
11°C
[2‑9]
T
c
target temperature during heating
operation.
0
(default
)
(default)
Auto
1
41°C
3
43°C
6
46°C
Содержание VRV IV RKXYQ5T8Y1B Series