17
REYQ-TATJA / TAYDA
EDUS371704C-D
8. Capacity Range
8.1 Connection Ratio
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Type
Min.
connection
ratio
Max. connection ratio
Types of connected indoor units
Type of connected air treatment equipment
When using only
FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54T
When using at least
one FXFQ07/09,
FXZQ05T,
FXSQ05T
Other indoor unit
models
FXMQ-MF
When FXMQ-MF is
only connected
When FXMQ-MF
and indoor units are
connected
Single outdoor units
50%
200% *1
130%
200% *1
100%
100% *2*3
Double outdoor units
160% *1
Triple outdoor units
130%
Note:
*
1. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units. Field setting now exists to
configure this situation. For cooling and heating mode – see below.
*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air
processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
*
3. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further
details.
*4. For indoor units used for cooling only (do not connect to Branch Selector unit when using for heat recovery), total capacity index must be 50%
or less than the capacity index of the outdoor units.
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
Default value = 0
Value
Indoor unit fan tap setting
0
Fan speed is limited to L tap when indoor units capacity ≥ 130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity ≥ 130%.
2
Fan speed follows a setting of the remote controller (not limited by indoor units connection capacity).
3
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C) and indoor air
temperature is in condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over
90.5 °F (32.5°C) or indoor air temperature is in condition B (**).
4
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C) and indoor air
temperature is in condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over
79.7°F (26.5°C) or indoor air temperature is in condition B (**).
5
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C) and indoor air
temperature is in condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over
72.1°F (22.3°C) or indoor air temperature is in condition B (**).
6
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C). It returns to remote
controller setting when outdoor air temperature goes up to over 90.5°F (32.5°C).
7
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C). It returns to remote
controller setting when outdoor air temperature goes up to over 79.7°F (26.5°C).
8
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C). It returns to remote
controller setting when outdoor air temperature goes up to over 72.1°F (22.3°C).
* Indoor condition A: Temperature difference (indoor air temperature - set temperature) is more than -2.7°F (-1.5°C) and less than 5.4°F (3°C).
** Indoor condition B: Temperature difference (indoor air temperature - set temperature) is -2.7°F (-1.5°C) or less, or 5.4°F (3°C) or more.
Содержание VRV IV REYQ120TATJA
Страница 2: ......
Страница 34: ...32 REYQ TATJA TAYDA EDUS371704C D 10 Dimensions REYQ72TATJA TAYDA 3D090838C ...
Страница 41: ...39 REYQ TATJA TAYDA EDUS371704C D 12 Center of Gravity REYQ72TATJA 4D090825A ...
Страница 42: ...40 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA 4D090826A ...
Страница 43: ...41 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA 4D090827A ...
Страница 44: ...42 REYQ TATJA TAYDA EDUS371704C D REYQ72TAYDA 4D090828A ...
Страница 45: ...43 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TAYDA 4D090829A ...
Страница 46: ...44 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TAYDA 4D090830A ...
Страница 48: ...46 REYQ TATJA TAYDA EDUS371704C D 14 Piping Diagrams REYQ72TATJA TAYDA 3D091128B ...
Страница 49: ...47 REYQ TATJA TAYDA EDUS371704C D REYQ96 168TATJA TAYDA 3D091127B ...
Страница 67: ...65 REYQ TATJA TAYDA EDUS371704C D 18 Operation Limits REYQ72 456TATJA TAYDA 3D091329A ...
Страница 69: ...67 REYQ TATJA TAYDA EDUS371704C D 20 Sound Levels Reference Data REYQ72TATJA TAYDA C 4D093380A ...
Страница 70: ...68 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA TAYDA C 4D093379A ...
Страница 71: ...69 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA TAYDA C 4D093378A ...
Страница 79: ...77 REYQ TATJA TAYDA EDUS371704C D 23 Caution Label 23 1 REYQ72TATJA TAYDA Operation Name Plate 2P385982 1A ...
Страница 80: ...78 REYQ TATJA TAYDA EDUS371704C D 2P385982 1A ...
Страница 81: ...79 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385986 1A ...
Страница 82: ...80 REYQ TATJA TAYDA EDUS371704C D 3P385986 1A ...
Страница 83: ...81 REYQ TATJA TAYDA EDUS371704C D 23 2 REYQ96 168TATJA TAYDA Operation Name Plate 3P385983 1B ...
Страница 84: ...82 REYQ TATJA TAYDA EDUS371704C D 3P385983 1B ...
Страница 85: ...83 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 86: ...84 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 87: ...85 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 88: ...86 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 89: ...87 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 90: ...88 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A ...
Страница 91: ...89 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385987 1A ...
Страница 92: ...90 REYQ TATJA TAYDA EDUS371704C D 3P385987 1A ...
Страница 103: ......