background image

16 Configuration

Installation and operation manual

34

RXYQQ8~20U7Y1B

VRV IV Q+ series heat pump

4P546221-1B – 2020.10

16.1

Making field settings

16.1.1

About making field settings

To continue the configuration of the VRV IV replacement heat pump
system, it is required to give some input to the PCB of the unit. This
chapter will describe how manual input is possible by operating the
push  buttons/DIP  switches  on  the  PCB  and  reading  the  feedback
from the 7‑segment displays.

Making settings is done via the master outdoor unit.

Next to making field settings it is also possible to confirm the current
operation parameters of the unit.

Push buttons and DIP switches

Item

Description

Push buttons

By operating the push buttons it is possible to:

▪ Perform 

special 

actions 

(automatic

refrigerant charge, testrun, etc).

▪ Perform  field  settings  (demand  operation,

low noise, etc).

DIP switches

By operating the DIP switches it is possible to:

▪ DS1  (1):  COOL/HEAT  selector  (refer  to  the

manual  of  the  cool/heat  selector  switch).
OFF=not installed=factory setting

▪ DS1  (2~4):  NOT  USED.  DO  NOT  CHANGE

THE FACTORY SETTING.

▪ DS2  (1~4):  NOT  USED.  DO  NOT  CHANGE

THE FACTORY SETTING.

See also:

"Field setting components"

 [

4

 34]

"To access the field setting components"

 [

4

 34]

PC configurator

For  VRV  IV  replacement  heat  pump  system  it  is  alternatively
possible  to  make  several  commissioning  field  settings  through  a
personal computer interface (for this, option EKPCCAB* is required).
The  installer  can  prepare  the  configuration  (off-site)  on  PC  and
afterwards upload the configuration to the system.

See  also: 

"To  connect  the  PC  configurator  to  the  outdoor

unit"

 [

4

 36].

Mode 1 and 2

Mode

Description

Mode 1

(monitoring
settings)

Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.

Mode 2

(field settings)

Mode 2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.

In general, normal operation can be resumed
without special intervention after changing field
settings.

Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.

See also:

"To access mode 1 or 2"

 [

4

 35]

"To use mode 1"

 [

4

 35]

"To use mode 2"

 [

4

 35]

"Mode 1: Monitoring settings"

 [

4

 35]

"Mode 2: Field settings"

 [

4

 36]

16.1.2

Field setting components

Location of the 7‑segment displays, buttons and DIP switches:

a

b

BS1 BS2

DS1 DS2

BS3

X27A

BS1

MODE: For changing the set mode

BS2

SET: For field setting

BS3

RETURN: For field setting

DS1, DS2

DIP switches

a

7‑segment displays

b

Push buttons

16.1.3

To access the field setting components

It is not required to open the complete electronic component box to
access  the  push  buttons  on  the  PCB  and  read  out  the  7‑segment
display(s).

To  access  you  can  remove  the  front  inspection  cover  of  the  front
plate  (see  figure).  Now  you  can  open  the  inspection  cover  of  the
electrical  component  box  front  plate  (see  figure).  You  can  see  the
three  push  buttons  and  the  three  7‑segment  displays  and  DIP
switches.

a

b

c

a

Front plate

b

Main PCB with 3 7‑segment displays and 3 push buttons

c

Electrical component box service cover

Operate the switches and push buttons with an insulated stick (such
as a closed ball-point pen) to avoid touching of live parts.

Make  sure  to  re-attach  the  inspection  cover  into  the  electronic
component box cover and to close the front plate's inspection cover
after the job is finished. During operation of the unit the front plate of
the  unit  should  be  attached.  Settings  are  still  possible  to  be  made
through the inspection opening.

NOTICE

Make  sure  that  all  outside  panels,  except  for  the  service
cover  on  the  electrical  component  box,  are  closed  while
working.

Close the lid of the electrical component box firmly before
turning on the power.

Содержание VRV IV Q+ Series

Страница 1: ...ion and operation manual VRV IV Q series heat pump English Installation and operation manual VRV IV Q series heat pump RXYQQ8U7Y1B RXYQQ10U7Y1B RXYQQ12U7Y1B RXYQQ14U7Y1B RXYQQ16U7Y1B RXYQQ18U7Y1B RXYQ...

Страница 2: ...iejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin ju...

Страница 3: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Страница 4: ...8 2 15 Symptom The display shows 88 14 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 14 8 2 17 Symptom The inside of an outdoor unit is warm even whe...

Страница 5: ...tion manual Installation and operation instructions Format Paper in the box of the outdoor unit Installer and user reference guide Preparation of the installation reference data Detailed step by step...

Страница 6: ...NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because t...

Страница 7: ...of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and recovery By ensurin...

Страница 8: ...e WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental...

Страница 9: ...range is only valid in case direct expansion indoor units are connected to the VRV IV system 6 2 Operating the system 6 2 1 About operating the system Operation procedure varies according to the combi...

Страница 10: ...al of the user interface 6 3 Using the dry program 6 3 1 About the dry program The function of this program is to decrease the humidity in your room with minimal temperature decrease minimal room cool...

Страница 11: ...operating in the horizontal direction It may cause dew or dust to settle on the ceiling or flap 6 5 Setting the master user interface 6 5 1 About setting the master user interface c c b b a a VRV rep...

Страница 12: ...from fan heaters gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation 8 Troubleshooting If one...

Страница 13: ...anger gas temperature sensor malfunction outdoor Suction temperature sensor malfunction outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE malfunction o...

Страница 14: ...s because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication between the units causing them to stop Operation automatical...

Страница 15: ...ESULT OF LEAK CHECK OPERATION REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT BE SURE TO FILL OUT THE BLANKS WHICH ARE NEEDED FOR AFTER SALE SERVICES...

Страница 16: ...15 C a e c d d c b a VRV IV replacement heat pump outdoor unit b Refrigerant piping c VRV direct expansion DX indoor unit d User interface dedicated depending on indoor unit type e Cool Heat changeov...

Страница 17: ...a b c d e a Electrical component box cover b Front side c Power supply terminal block d Sealing material e Moisture and dirt could enter NOT allowed Allowed 13 3 Mounting the outdoor unit 13 3 1 To p...

Страница 18: ...and thickness and if the pipes and branch piping are not corroded If the existing field piping does not comply with the above conditions replace the existing field piping with field piping that meets...

Страница 19: ...34 9 1 0 38 1 41 3 1 1 a If annealed temper grade is 1 The refrigerant pipes and branches must meet the condition of design pressure 33 bar 3 3 MPa If it is NOT possible to confirm this use the refrig...

Страница 20: ...If the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line within a length of 2 m from the kit If Then 2 m a b 2 m 2 m a 2 m 2 m 200 mm 200 mm b 2 m 2 m...

Страница 21: ...allowed Allowed Make sure that the total length of the piping connected to the joint is absolute straight for more than 500 mm Only if a straight field piping of more than 120 mm is connected more tha...

Страница 22: ...lve size mm Tightening torque N m when opening or closing Valve body Hexagonal wrench Service port 9 5 5 7 4 mm 10 7 14 7 12 7 8 10 15 9 14 16 6 mm 19 1 19 21 8 mm 25 4 14 2 7 To remove the spun pipes...

Страница 23: ...ant piping involves Checking for any leakages in the refrigerant piping Performing vacuum drying to remove all moisture air or nitrogen in the refrigerant piping If there is a possibility of moisture...

Страница 24: ...our 3 Should you fail to reach the target vacuum within 2 hours or maintain the vacuum for 1 hour the system may contain too much moisture In that case break the vacuum by pressurising with nitrogen g...

Страница 25: ...or manual charging This step is included in below procedure see To charge refrigerant 428 It can be skipped but charging will take longer then A flow chart is available which gives an overview of the...

Страница 26: ...kg 12 HP N 6 C2 0 kg C C1 C2 0 5 kg Metric piping When using metric piping replace the weight factors in the formula by the ones from the following table Inch piping Metric piping Piping Weight facto...

Страница 27: ...t on the additional refrigerant charge label Go to test run Step 4b Close valve B R Q R Q R Q Step 5 Connect valve A to refrigerant charge port Open all outdoor unit stop valves Proceed with automatic...

Страница 28: ...al refrigerant charge label Go to test run Following codes appear e 2 indoor temperature out of range and e 3 outdoor temperature out of range Push BS1 to leave program Charging is finished Fill in th...

Страница 29: ...6 Step 6a To automatically charge refrigerant INFORMATION The automatic refrigerant charging has limits as described below Out of these limits the system cannot operate the automatic refrigerant charg...

Страница 30: ...tial NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in...

Страница 31: ...nd select the next higher recommended fuse capacity Example Combining the RXYQQ30 by using the RXYQQ18 and RXYQQ12 Minimum circuit ampacity of the RXYQQ18 35 0 A Minimum circuit ampacity of the RXYQQ1...

Страница 32: ...or unit e Outdoor unit In case of multi outdoor unit installation F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P d d e f b a c Q1 Q2 a Unit A master outdoor unit b Unit B slave outdoor unit c Unit C slave outdoor unit d...

Страница 33: ...Power supply terminal block f Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N g Earth wire GRN YLW h Tie wrap i Cup washer j When connecting the earth wire it is recommended to perf...

Страница 34: ...he current field setting value and changing the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field...

Страница 35: ...nit What How Changing and accessing the setting in mode 1 Once mode 1 is selected push BS1 one time you can select the wanted setting It is done by pushing BS2 Accessing the selected setting s value i...

Страница 36: ...et C 0 default Auto 2 6 3 7 4 8 5 9 6 10 7 11 2 9 Tc target temperature during heating operation 2 9 Tc target C 0 default Auto 1 41 3 43 6 46 2 20 Manual additional refrigerant charge 2 20 Descriptio...

Страница 37: ...ce of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and earth NEVER use the megatester for the transmission wiring Fuses circuit breakers or protection devices Chec...

Страница 38: ...egment display idle Abnormal completion Indication of malfunction code on the 7 segment display Refer to 17 5 Correcting after abnormal completion of the test run 438 to take actions for correcting th...

Страница 39: ...rface s display or transmission wiring between the outdoor unit and the indoor unit Electronic expansion valve malfunction main Y1E A1P X21A Check connection on PCB or actuator Electronic expansion va...

Страница 40: ...tuator De icing temperature sensor malfunction R7T A1P X30A Check connection on PCB or actuator Liquid temperature sensor after subcool HE malfunction R5T A1P X30A Check connection on PCB or actuator...

Страница 41: ...alfunction Check if other indoor units have malfunction and confirm indoor unit mix is allowed Connection malfunction over indoor units or type mismatch R410A R407C RA Hydrobox etc Check if other indo...

Страница 42: ...d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm Layout A B C D A B Possibility 1 Possibility 2 5 a 10 mm b 500 mm c 10 mm d 500 mm e 20 mm f 900 mm a 50 mm b 500 mm c 50 mm d 500 mm e 100...

Страница 43: ...ed are listed below INFORMATION The wiring diagram on the outdoor unit is only for the outdoor unit For the indoor unit or optional electrical components refer to the wiring diagram of the indoor unit...

Страница 44: ...ion valve liquid cooling Y1S Solenoid valve main Y2S Solenoid valve accumulator oil return Y3S Solenoid valve oil 1 Z C Noise filter ferrite core Z F A2P A5P Noise filter with surge absorber Connector...

Страница 45: ...expansion valve main Y2E Electronic expansion valve sub cool Y3E Electronic expansion valve liquid cooling Y1S Solenoid valve main Y2S Solenoid valve accumulator oil return Y3S Solenoid valve oil 1 Y4...

Страница 46: ......

Страница 47: ......

Страница 48: ...4P546221 1B 2020 10 Copyright 2018 Daikin 4P546221 1 B 0000000Y Verantwortung f r Energie und Umwelt...

Отзывы: