Setting Up
8 - 1 Precautions for Setup
The intelligent Manager Monitor System PC and printer are used in the same way as general OA equipment.
iPUs are set up within the system.
However, avoid setting up in the following locations.
•
Locations that are exposed to direct sunlight, or that are subject to radiation from heat generating equipment such as a boiler.
•
Locations with high humidity or where there could be contact with water.
•
Locations that are corrosive or where inflammable gas is generated.
Ambient temperature and humidity conditions of location of setup
10 - 35°C 20 - 80% RH (intelligent Manager Monitor System PC, Printer, Display, UPS)
0 - 50°C - 95%RH (iPU)
Separate our air conditioning power (electrical) lines and the communications lines for control a minimum of 50 mm. In other cases, separate from the
power lines to meet the following conditions.
8 - 2 Summary of Attachment
•
Always attach inside a locked electrical equipment box (or somewhere that cannot be opened without the use of a special tool) so that indoor
equipment cannot be easily tampered. The location should not allow the equipment to be subjected to the influence of electromagnetic waves or
to be exposed to dust.
Minimum depth dimension necessary for setup is 100 mm.
•
The figure at right shows the minimum spacing between equipment when setting up consecutively and the wall.
•
Attach as shown in the following figure.
Always attach in the vertical direction. Attaching horizontally will cause failures so do not attach in that direction.
Power Line Electrical Capacity
Distance of Separation of Power Lines and Communication Lines for Control
Daikin Air Conditioners
Other Equipment
Max. 220 V
Max. 10A
Min. 50 mm
Min. 300 mm
Max. 50A
Min. 500 mm
Max. 109A
Min. 1000 mm
Exceeding 100A
Min. 1500 mm