• Outdoor Units • VRV
®
Heat Pump • RXYSQ4-6PAY
• VRV
®
Systems • Outdoor Units
26
8
Installation
8 - 1
Service space
(a) One row of stand-alone installation.
(b) Rows of series installation
(2 or more).
1
Series installation.
The relations between H, A and L are
as follows.
L
A
L
≤
H
0 < L
≤
1/2 H
250
1/2 H < L
≤
H
300
H < L
Set the stand as : L <= H
4. Double-decker installation
(a) Obstacle on the discharge side.
Close the gap A (the gap between the upper
and lower outdoor units) to prevent the
discharged air from being bypassed.
Do not stack more than two unit..
The relations between H, A and L are as follows.
L
A
L
≤
H
0 < L
≤
1/2 H
250
1/2 H < L
≤
H
300
H < L
Cannot be installed
(b) Obstacle on the suction side only.
Close the gap A (the gap between the upper
and lower outdoor units) to prevent the
discharged air from being bypassed.
Do not stack more than one unit..
5. Multiple rows of series installation
(on the rooftop, etc.).
RXYSQ-PY1
(b) Obstacle above, too
Close the bottom of the installation frame to
prevent the discharged air from being bypassed.
Only two units can be installed for this series.
1
Stand-alone installation.
2
Series installation (2 or more).
The relations between H, A and L are as follows.
L
A
L
≤
H
0 < L
≤
1/2 H
750
1/2 H < L
≤
H
1000
H < L
Set the stand as : L <= H
The relations between H, A and L are as follows.
L
A
L
≤
H
0 < L
≤
1/2 H
1000
1/2 H < L
≤
H
1250
H < L
Set the stand as : L <= H
Pattern 2
Where the obstacle on the discharge side is
lower than the unit.
(There is no height limit for obstructions on the
intake side.)
(a) No obstacle above.
1
Stand-alone installation.
2
Series installation (2 or more).
The relations between H, A and L are as follows.
L
A
0 < L
≤
1/2 H
250
1/2 H < L
≤
H
300
(b) Obstacle above, too.
1
Stand-alone installation.
The relations between H, A and L are as follows.
L
A
L
≤
H
0 < L
≤
1/2 H
100
1/2 H < L
≤
H
200
H < L
Set the stand as : L <= H
Close the bottom of the installation frame to
prevent the discharged air from being
bypassed.
Close the bottom of the installation frame to
prevent the discharged air from being bypassed.
Close the bottom of the installation frame to prevent
the discharged air from being bypassed.
Only two units can be installed for this series.
500 or less
250 or more
500 or less
300 or more
100 or more
500 or more
1500 or more
1000 or more
500 or less
500 or less
1500 or more
Drain
piping
construction
dimension
1000 or more
300 or more
1000 or more
200 or more
2000 or more
100 or more
3000 or more
600 or more
1500 or more
1000
or
more
100
or
more
1000
or
more
1000
or
more
3D045696C
Drain
piping
construction
dimension