EDUS39-802A-R1_a
Field Wiring
RXYQ-P Heat Pump (208-230V)
13
6. Field Wiring
RXYQ72, 96, 120, 144PTJU
3D058621
L3
(TRANSMISSION LINE)
L2
L3
SWITCH
POWER SUPPLY
POWER SUPPLY
L1
FUSE
L1
L1
L1
MAIN SWITCH
SWITCH
FUSE
L2
6) Unit shall be grounded in compliance with the applicable
local and national codes.
7) Wiring shown are general points-of-connection guides
only and are not intended for or to include all details for
a specific installation.
8) Be sure to install the switch and the fuse to the power
line of each equipment.
9) Install the main switch that can interrupt all the power
souces in an integrated manner because this system
consists of the equipment utilizing the multiple
power sources.
10) If there exists the possibility of reversed phase, lose
phase, momentary blackout or the power goes on and
off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the
compressor and other parts.
L2
FUSE
L1
(TRANSMISSION LINE)
SWITCH
L2
L1
L2
(TRANSMISSION LINE)
L2
(TRANSMISSION LINE)
Notes 1) All wiring, components and materials to be procured
on the site must comply with the applicable local and
national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install ground fault circuit interrupter for safety.
5) All field wiring and components must be provided by
licensed electrician.
FUSE
FUSE
MAIN
SWITCH
SWITCH
L2
L1
SWITCH
(POWER LINE)
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
INDOOR UNITS
OUTDOOR UNITS
2 WIRES CABLE
(POWER LINE)
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
Содержание VRV III RXYQ_PTJU
Страница 1: ...EDUS 39 802A R1_a AMERICAS AMERICAS AMERICAS RXYQ_PTJU 3 phase 208 230V 60Hz...
Страница 10: ...EDUS39 802A R1_a Piping Diagrams RXYQ P Heat Pump 208 230V 9 4 Piping Diagrams RXYQ72 96 120PTJU 3D058636A...
Страница 11: ...Piping Diagrams EDUS39 802A R1_a 10 RXYQ P Heat Pump 208 230V RXYQ144PTJU 3D058640...
Страница 16: ...EDUS39 802A R1_a Electric Characteristics RXYQ P Heat Pump 208 230V 15 7 Electric Characteristics 3D060211...
Страница 17: ...Electric Characteristics EDUS39 802A R1_a 16 RXYQ P Heat Pump 208 230V 3D060213...