Installation manual
21
RXYQ8~1 RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
2
Adding refrigerant without using leak detection function
■
Charge with the outdoor unit at standstill
1.
Calculate how much refrigerant to be added using the formula
explained in the chapter
"How to calculate the additional
refrigerant to be charged" on page 9
.
2.
Open valve C (valves A and B and the stop valves must be left
closed) and charge the required amount of refrigerant through
the liquid side stop valve service port.
■
When the required amount of refrigerant is fully charged,
close valve C. Record the amount of refrigerant that was
added on the "Request for indication of additional refrigerant
charging and leak detection amount" label provided with the
unit and attach it on the back side of the front panel. Perform
the test procedure as described in
added without using the leak detection function (pre-
charging, charging in heating mode)" on page 27
■
When the additional charging is not complete, perform the
procedure explained in the chapter
■
Charge with operating outdoor unit
Charge the refrigerant through valve A.
1.
Start of charging refrigerant manually
-
Open the liquid and gas side stop valves and the service port
stop valve. (Valves A, B and C must be closed.)
-
Close all frontpanels except the electric box frontpanel and
turn the power ON.
-
Make sure all indoor units are connected, refer to
to check how many units are connected" on page 17
-
If the H2P LED is not flashing (in 12 minutes time after
turning on the power), make sure it is displayed as shown
below.
If the H2P LED is flashing, check the malfunction code on the
remote controller
"4 Remote controller malfunction code
2.
Press the
button once if the LEDs combination is not
as in the figure below.
3.
Press the
button once.
4.
Hold the
button down for 5 seconds or more.
5.
Charging mode judgement
If the indoor temperature is 10°C DB or lower, charging in
cooling mode is not possible in some cases. The unit will
automatically select the cooling mode or heating mode for
charging.
Continue with the manually charging in cooling
mode OR in heating mode.
■
Charging in heating mode
6.
Start up
Wait while the unit is preparing for charging in heating mode.
7.
Ready
Press the
button once within 5 minutes.
If the
button is not pushed within 5 minutes,
P2
will be
displayed on the remote controller. Refer to
malfunction code display" on page 22
8.
Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.
*
= The state of this LED is not important.
9.
Complete
If the calculated amount of refrigerant minus 10 kg is reached,
close valve A and press the
button once.
10. Press the
button once and the charging is complete.
Record the amount that was added on the additional refrigerant
charge label provided with the unit and attach it on the back side
of the front panel.
Perform the test procedure as described in
H1P
H2P
H3P
H4P
H5P
H6P
H7P
x
x w x
x
x
x
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w w w w w w w
When charging in cooling mode, the unit will stop
operating when the required amount of refrigerant is
charged.
During charging in heating mode, a person must
manually close valve A when complete charging is
finished. Calculate how much refrigerant to be added
using the formula explained in the chapter
calculate the additional refrigerant to be charged" on
page 9
BS1 MODE
BS4 TEST
BS4 TEST
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Pressure control
(for the first minute)
x c x
x
x
x w
Start up control
(for the next 2 minutes)
c c x
x
x w x
Waiting for stable
heating conditions
(for the next ±15
minutes (according to
the system))
c c x
x
x w w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
c c x
x w x w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w c
*
*
*
*
*
When a malfunction occurs, check the display of the
remote controller and refer to
malfunction code display" on page 22
.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
c c c w w w w
BS4 TEST
BS4 TEST
BS3 RETURN
BS1 MODE