Outdoor unit multi connection piping kit and

Refrigerant branch kit selection

Pipe size selection

 Refrigerant branch kits can only be used with R410A.

 When multi outdoor system are installed, be sure to use the 

special separately sold Outdoor unit multi connection piping 

kit. (BHFP26P90 · 136).

(For how to select the proper kit, follow the table at right.)

 Never use BHFP26M90 · 135, BHFP22M90 · 135P for M 

type of this series or T joint (field supplyed).

How to select the REFNET joint

Piping between outdoor unit (*2) and refrigerant branch kit (part A)

How to select the REFNET header

When using REFNET joint at the first branch counted from the outdoor unit side,

choose from the following table in accordance with the outdoor unit capacity type.

(Example : REFNET joint A)

Choose from the following table in accordance with the outdoor unit system capacity type.

Piping between outdoor unit multi connection piping kit and outdoor unit (part C)

Temper grade and wall thickness for pipes

(Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)

Choose from the following table in accordance with the capacity type of

the outdoor unit connected.

Piping between outdoor unit multi connection piping kits (part B)

Choose from the following table in accordance with the total capacity of all

the outdoor units connected upstream.

Choose from the following table in accordance with the total capacity index of all

the indoor units connected below the REFNET header.

250 type indoor unit can not be connected below the REFNET header.

How to select the outdoor unit multi connection piping kit

(This is required when the system is multi outdoor unit system.)

Choose from the following table in accordance with the number of outdoor units.

Choose the REFNET joints other than the first branch from the following table in accordance

with the total capacity index of all the indoor units connected below the REFNET joint.

Outdoor unit capacity type

8,10HP type

12~22HP type

24HP type ~

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

640 

 x

Refrigerant branch kit name

KHRP25A33T

KHRKHRP25M72TP

KHRKHRP25M73TP

3 pipes

KHRP25A22T

KHRP25A33T

KHRKHRP25M72TP

KHRKHRP25M73TP

2 pipes

KHRP26A22T

KHRP26A33T

KHRP26A72T

Refrigerant branch kit name

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

640 

 x

Number of outdoor unit

2 units

3 units

Connecting piping kit name

BHFP26P90

BHFP26P136

3 pipes

KHRP25M33H

KHRKHRP25M72HP

KHRKHRP25M73HP

2 pipes

KHRP26M22H or KHRP26M33H

KHRP26M33H

KHRP26M72H

KHRKHRP26M73HP

Refrigerant branch kit name

Example for indoor units

connected downstream

Example REFNET joint C : Indoor units  5  +  6  +  7  +  8

Example REFNET joint B : Indoor units  7  +  8

Example REFNET header : Indoor units  1  +  2  +  3  +  4  +  5  +  6

Example REFNET header :

Indoor units  1  +  2  +  3  +  4  +  5  +  6  +  7  +  8

The thickness of the pipes in the table shows 

the requirements of Japanease High Pressure 

Gas Controll low. (As of Jan. 2003)

The thickness and material shall be selected in 

accordance with local code.

<In case of single outdoor unit system>

<In case of multi outdoor unit system>

Equalizer pipe

(part D)

Piping between outdoor unit

multi connection piping kit

and outdoor unit (part C)

Piping between outdoor unit multi 

connection piping kits (part B)

Piping between outdoor unit and 

refrigerant branch kit (part A)

Piping between outdoor unit and 

refrigerant branch kit (part A)

Outdoor unit

Independent

unit 1

Independent

unit 2

Independent

unit 3

Outdoor unit

capacity type

8HP type

10HP type

12HP type

14,16HP type

18HP type

20,22HP type

24HP type

26~34HP type

36HP type

38~48HP type

Piping size (O. D.)

Piping size (O. D.)

Suction gas pipe

φ

19.1

φ

22.2

φ

28.6

φ

34.9

φ

41.3

HP/LP gas pipe

φ

15.9

φ

19.1

φ

22.2

φ

28.6

φ

34.9

Liquid pipe

φ

9.5

φ

12.7

φ

15.9

φ

19.1

Outdoor unit

capacity type

8,10HP type

12HP type

14,16HP type

Copper tube O. D.

Temper grade

Wall thickness

(Min. requirement)

Suction gas pipe

φ

22.2

φ

28.6

HP/LP gas pipe

φ

19.1

φ

22.2

Liquid pipe

φ

9.5 

×

 0.8

φ

12.7

φ

6.4

0.80

φ

9.5

0.80

φ

12.7

0.80

φ

15.9

0.99

φ

19.1

0.80

φ

22.2

0.80

φ

25.4

0.88

φ

28.6

0.99

φ

31.8

1.10

φ

34.9

1.21

φ

38.1

1.32

φ

41.3

1.43

Piping between refrigerant branch kits

Piping between refrigerant branch kit and BS unit

Piping between BS unit and refrigerant branch kit

Choose from the following table in accordance with the total capacity type of all the

indoor units connected downstream.

Piping between refrigerant branch kit, BS unit and indoor unit

Equalizer pipe (part D) (multi outdoor unit system only)

Match to the size of the connection piping on the indoor unit.

*1 Connection piping must not exceed the refrigerant Piping size between outdoor

     unit and refrigerant branch kit (part A).

*2 When selecting 2 pipes line (gas pipe and liquid pipe), use Suction gas pipe

     column for gas pipe and Liquid pipe column for liquid pipe.

Indoor capacity index

x < 150

150 

 x < 200

200 

 x < 290

290 

 x < 420

420 

 x < 640

640 

 x < 920

920 

 x

Suction gas pipe

φ

15.9

φ

19.1

φ

22.2

φ

28.6

φ

34.9

φ

41.3

HP/LP gas pipe

φ

12.7

φ

15.9

φ

19.1

φ

28.6

Liquid pipe

φ

9.5

φ

12.7

φ

15.9

φ

19.1

Indoor unit capacity type

20 · 25 · 32 · 40 · 50 type

63 · 80 · 100 · 125 type

200 type

250 type

gas pipe

φ

12.7

φ

15.9

φ

19.1

φ

22.2

Liquid pipe

φ

6.4

φ

9.5

Piping size (O. D.)

φ

19.1

 (unit : mm)

 (unit : mm)

Piping size (O. D.)

 (unit : mm)

Piping size (O. D.)

 (unit : mm)

 (unit : mm)

1/2H type

O type

01_EN_3P201178-4B.fm  Page 7  Friday, May 18, 2007  7:58 PM

Содержание VRV III REYQ8PY1B

Страница 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Страница 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Страница 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Страница 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Страница 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Страница 6: ...3P201178 4B EM07A013 0705 HT...

Страница 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Страница 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Страница 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Страница 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Страница 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Страница 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Страница 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Страница 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Страница 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Страница 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Страница 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Страница 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Страница 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Страница 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Страница 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Страница 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Страница 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Страница 24: ...English 18 NOTES...

Отзывы: