English
13
• Do not remove or reinstall the unit by yourself.
Incorrect installation may cause electrical shock or
fire.
Contact your dealer.
•
When asking your dealer to repair, inform
related staff of the details as follows:
• Product No. of air conditioner:
Refer to the warranty card.
• Shipping date and installation date:
Refer to the warranty card.
• Malfunction:
Inform the staff of the defective details.
(Malfunction code being displayed on
the remote controller.)
• Name, address, telephone number
•
Repair where the warranty term is expired
Contact your dealer. If necessary to repair, pay
service is available.
•
Minimum storage period of important parts
Even after a certain type of air conditioner is dis-
continued, we have the related important parts in
stock for 9 years at least.
The important parts indicate parts essential to
operate the air conditioner.
•
Recommendations for maintenance and
inspection
Since dust collects after using the unit for several
years, the performance will be deteriorated to
some extent.
Taking apart and cleaning inside require technical
expertise, so we recommend entering a mainte-
nance and inspection contract (at a cost) separate
from normal maintenance.
•
Recommended inspection and maintenance
cycles
[Note: The maintenance cycle is not the same
as the warranty period.]
Table 1 assumes the following usage conditions.
1. Normal use without frequent starting and stop-
ping of the machine.
(Although it varies with the model, we recom-
mend not starting and stopping the machine
more than 6 times/hour for normal use.)
2. Operation of the product is assumed to be
10 hours/day, 2500 hours/year.
• Table 1 “Inspection Cycle” and “Maintenance
Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for
details.
Note 2
This maintenance cycle indicates recommended
lengths of time until the need arises for maintenance
work, in order to ensure the product is operational
as long as possible.
Use for appropriate maintenance design (budgeting
maintenance and inspection fees, etc.)
Depending on the content of the maintenance and
inspection contract, the inspection and maintenance
cycles may in reality be shorter than those listed
here.
Note 3
It is necessary to shorten the maintenance cycle
and replacement cycle under tough operating condi-
tions (e.g., the air conditioner is operated for long
hours or started and stopped highly frequently) or
under tough environmental conditions (e.g., the air
conditioner is operated at high ambient tempera-
tures in a highly humid place).
■
Recommended replacement cycle of wear-out
parts
[The cycle is not the same as the warranty period.]
• Table 2 “Replacement Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Name of Main Part
Inspection
Cycle
Maintenance Cycle
[replacements and/or
repairs]
Compressor
1 year
20,000 hours
Electric motor (fan,
damper, etc.)
20,000 hours
PC boards
25,000 hours
Heat exchanger
5 years
Sensor (thermistor, etc.)
5 years
Remote controller and
switches
25,000 hours
Drain pan
8 years
Expansion valve
20,000 hours
Electromagnetic valve
20,000 hours
FAN
Outdoor: 10 years
Indoor: 13 years
Name of Main Part
Inspection
Cycle
Replacement Cycle
Air filter
1 year
5 years
High efficiency filter
(Optional accessory)
1 year
Fuse
10 years
Crankcase heater
8 years
01_EN_3P201178-2B.fm Page 13 Wednesday, April 25, 2007 3:51 PM