background image

15

English

[Remote controller displays malfunction code]

Note

If any malfunction codes other than the above are displayed, check 
the service manual for how to respond. 

12. ONSITE SETTINGS

Use the push button switches (BS1 through BS5) on the outdoor unit 
PC-board (A1P) to make the necessary onsite settings.
See the “Service Precautions” label (upper) on the EL. CONPO. BOX 
(1) lid for details on the positions and operating method of the push 
button switches and on the onsite setting. (see figure 32)
Make sure to record the setting on the accessory “REQUEST FOR 
THE INDICATION” label.

Warning

Electric Shock Warning

Use an insulated rod to operate the push buttons via the inspection 
door of EL. COMPO. BOX (1) lid. 
There is a risk of electric shock if you touch any live parts, since 
this operation must be performed with the power on.

13. TEST RUN

13-1 Before test run

Make sure the following works are completed in accordance with 
the installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Additional refrigerant charge

„

Check operation

Check that all work for the BS, indoor unit are finished and there 
are no danger to operate.

13-2 Test Run

After all works are completed, operate the unit normally and check 
the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corre-

sponding outdoor unit is also operating.

(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote control-

ler to see if they operate properly.

Note

Heating is not possible if the outdoor temperature is 24°C or 
higher. Refer to the Operation manual.

If a knocking sound can be heard in the liquid compression of the 
compressor, stop the unit immediately and then energize the 
crank case heater for a sufficient length of time before restarting 
the operation.

Once stopping, the compressor will not restart in about 5 minutes 
even if the On/Off button of the remote controller is pushed.

When the system operation is stopped by the remote controller, 
the outdoor units may continue operating for further 5 minutes at 
maximum.

The outdoor unit fan may rotate at low speeds if the Night-time low 
noise setting or the External low noise level setting is made, but 
this is not a malfunction.

If the check operation was not performed at first istallation, the 
malfunction code “U3” will be displayed in the remote controller. 
Perform the check operation following 

“11-2-2 Procedure of 

Check Operation”

.

13-3 Checks After Test Run

Perform the following checks after the test run is complete.

Record the contents of field setting.

Record them on the accessory “REQUEST FOR THE INDI-
CATION” label.
And attach the label on the back side of the front panel.

Record the installation date.

Record the installation date on the accessory “REQUEST 
FOR THE INDICATION” label in accordance with the 
IEC60335-2-40.
And attach the label on the back side of the front panel.

Note

After the test run, when handing the unit over to the customer, make 
sure the EL.COMPO.BOX lid, the inspection door, and the unit casing 
are all attached.

14. CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combusti-
ble refrigerant. Nevertheless care must be taken to ensure that air 
conditioning facilities are installed in a room which is sufficiently large. 
This assures that the maximum concentration level of refrigerant gas 
is not exceeded, in the unlikely event of major leak in the system and 
this in accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maxi-
mum concentration of refrigerant is directly related to the humanly 
occupied space in to which it could leak.

The unit of measurement of the concentration is kg/m

3

 ( the weight in 

kg of the refrigerant gas in 1m

3

 volume of the occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.
In Australia the maximum allowed concentration level of refrigerant to 

a humanly space is limited to 0.35kg/m

3

 for R407C and 0.44kg/m

3

 for 

R410A.

1.

direction of the refrigerant flow

2.

room where refrigerant leak has occurred (outflow of all 
the refrigerant from the system)

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.

Malfunc-

tion code

Installation error

Remedial action

E3, E4

F3, F6
UF

The shutoff valve of the out-
door unit is left closed.

Open the shutoff valve.

U1

The phases of the power to the 
outdoor unit is reversed.

Exchange two of the three phases (L1, 
L2, L3) to make a proper connection.

U1
U4
LC

No power is supplied to an out-
door, BS or indoor unit (includ-
ing phase interruption).

Make sure the power source wire is prop-
erly connected to the outdoor, BS or 
indoor unit and revise if necessary.

UF

There is conflict on the con-
nection of transmission wiring 
in the system.

Check if the refrigerant piping line and the 
transmission wiring are consistent with 
each other.

E3
F6

UF

Refrigerant overcharge.

Recalculate the additional amount refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

E4
F3

Insufficient refrigerant.

• Check if the additional refrigerant 

charge has been finished correctly.

• Recalculate the additional amount 

refrigerant from the piping length and 
add the adequate amount.

U7, U4
UF, UH

Field wiring is connected to 
“TO MULTI UNIT (Q1,Q2)” ter-
minal on the outdoor unit PC-
board (A1P) when the system 
is one outdoor system.

Remove the line from the “TO MULTI 
UNIT (Q1, Q2)” terminal.

UA

The internal transmission wir-
ing to “TO MULTI UNIT 
(Q1,Q2)” for the single outdoor 
unit system are disconnected.

Connect the internal transmission wiring 
to “TO MULTI UNIT (Q1,Q2)”. (See the 
wiring diagram.)

2

1

01_EN_3P201178-3B.fm  Page 15  Friday, May 18, 2007  5:21 PM

Содержание VRV III REYQ10PY1

Страница 1: ...System air conditioner INSTALLATION MANUAL REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 00_CV_3P201178 3B fm Page 1 Friday May 18 2007 3 25 PM ...

Страница 2: ...YQ32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30PY1 REYQ32PY1 REYQ34PY1 REYQ36PY1 REYQ38PY1 REYQ40PY1 REYQ42PY1 REYQ44PY1 REYQ46PY1 REYQ48PY1 REYQ8PY1B REYQ10PY1B REYQ12PY1B REYQ14PY1B REYQ16...

Страница 3: ...ttern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 figure 8 4 2 5 1 3 3 6 1 2 3 4 5 6 figure 9 1 2 3 1 2 3 5 6 6 17 7 4 14 16 15 18 15 5 6 10 11 12 9 7 13 8 8 8 8 8 8 5 5 100 100 100 100 100 100 1 2 3 4 figure 5 1 2 3 5 4 6 figure 10 figure 11 figure 12 figure 13 00_CV_3P201178 3...

Страница 4: ... 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figure 20 1 2 3 4 5 4 4 6 7 6 5 8 9 10 4 11 11 L1 L2 L3 N 1 2 3 4 figure 21 figure 23 figure 14 A 3 4 1 5 2 B 1 2 figure 15 00_CV_3P201178 3B fm Page 3 Friday May 18 2007 3 25 PM ...

Страница 5: ...16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 1 2 3 11 12 10 4 5 6 7 9 8 13 14 15 16 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 00_CV_3P201178 3B fm Page 4 Friday May 18 2007 3 25 PM ...

Страница 6: ... closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Failure to use the specified parts may result in water leakage electric shocks fire or the unit falling Install the air conditioner on a foundation strong enough to with stand the weight of the unit A foundation of insufficient stren...

Страница 7: ...em into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with in...

Страница 8: ... units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space of front side 4 Service space of suction side For Patterns 1 and 2 in figure 2 Wall height for front side no higher than 1500 mm Wall height on the suction side no higher than 500 mm Wall height for sides no limit If the height is ex...

Страница 9: ...in water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off the anti corrosion effect may decrease 6 REFRIGERANT PIPING Note All field piping must be installed by a licensed refrigeration techni cian and must comply with relevant local and national regulations After piping work is complete d...

Страница 10: ...g Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay piping 3 Pinch piping 4 Procedure 1 Confirm the shutoff valve is closed 5 Procedure 2 Connect a charge hose to the service port of shutoff valve and remove the gas in the pinch piping 6 Procedure 3 After removing the gas in the p...

Страница 11: ...r unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to be 6m for calculation purposes Total piping length from outdoor unit 2 to all indoor unit 1000m Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit 10m Equivalent pipe length from first outdoor...

Страница 12: ...P26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example REFNET joint B Indoor units 7 8 Example REFNET header Indoor units 1 2 3 4 5 6 Example REFNET header Indoor units 1 2 3 4 5 6 7 8 The thickness of the pipes in the table shows the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 Th...

Страница 13: ...1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3 6kg 1 0kg 1 5kg 2 0kg 2 5kg 3 0kg 3 5kg 4 0kg 4 5kg REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACITY OF INDOOR UNIT INDOOR CONNECTION CAPACITY MORE THAN 100 120 OR LESS MORE THAN 120 130 OR LESS MODEL NAME REYQ8 32PY1 REYQ34 ...

Страница 14: ...of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running the product in reversed phase may break the compres sor and other parts 7 1 Power circuit safety device and cable requirements A power circuit see the following table must be provided for con nection of the unit This circuit must be...

Страница 15: ... wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outside force from being applied to the terminal area Refer to figure 23 1 Power supply 3N 380 415V 50Hz 2 Earth leakage circuit breaker 3 Branch switch Overcurrent breaker 4 Ground wire 5 EL COMPO BOX 1 6 EL COMPO BOX 2 7 Do not op...

Страница 16: ...iping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter the pipes during work etc 1 After performing the vacuum drying for two hours pressurize to 0 05 MPa i e vacuum breakdown with nitrogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If...

Страница 17: ...radation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use the charge hose After tightening the cap make sure no refrigerant gas is leaking Tightening torque The sizes of the shutoff valves on each model and the tightening torque for each size are listed in the table below Size of Shutoff Valv...

Страница 18: ...he refrigerant make sure to close the lid of the refrigerant charging port The tightening torque for the lid is 11 5 to 13 9 Nm See Shutoff valve operation procedure in chapter 11 1 for details on how to handle shutoff valves When done or when pausing the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric exp...

Страница 19: ...y units are con nected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation Table Display of normal system 3 Charge the remained refrigerant by additional refrigerant charg ing operation of service mode About the method of additional refrigerant charging operation refer to the Service Precaution labe lower attached on the EL COMPO BOX lid of t...

Страница 20: ...OMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The installer and system specialist shall secure safety against leakage according to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air condi...

Страница 21: ...e floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum con centration level then make similar calculations for the second then third smallest room and so until the result falls short of the maxi mum concentration 4 Dealing with the situations where the result exceeds the maxi mum co...

Страница 22: ...3P201178 3B EM07A014 0705 HT 00_CV_3P201178 3B fm Page 5 Friday May 18 2007 3 25 PM ...

Отзывы: