Daikin VRV III REMQ8P8Y1B Скачать руководство пользователя страница 30

Installation manual

25

REMQ8~16P8Y1B

VRVIII System air conditioner

4PW40598-1A

12.4. Test operation

In case the unit is operated with the leak detection function
available:

the outdoor temperature must be 0°C DB~43°C DB

the indoor temperature must be 20°C DB~32°C DB

In case the unit is operated out of the temperature range as
instructed above, the display of the remote controller shows 

U3

and the unit operates without the availability of the leak detection
function.

In the test operation, the following checks and judgement will be
performed:

Check of the stop valve opening

Check for wrong wiring

Check of refrigerant overcharge

Initial refrigerant detection

In case the leak detection function is available, the check
operation will last 2 hours, otherwise it takes between 40 and
60 minutes to complete the check operation.

Make sure to carry out the test operation after the first
installation. Otherwise, the malfunction code 

U3

 will be displayed

on the remote controller and normal operation can not be
carried out.

In case of a multi system, check the settings and results on the
master unit.

Abnormalities on indoor units can not be checked for each unit
individual. After the test operation is finished, check the indoor
units one by one by performing a normal operation using the
remote controller.

Test operation procedure

1

Close all front panels except the front panel of the electric box.

2

Turn ON the power to all outdoor units and the connected indoor
units.

Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.

3

Make the field setting as described in the paragraph 

"12.3. Field

setting" on page 23

.

4

Press the 

 button once, and set to the SETTING

MODE (H1P LED = OFF).

5

In case the leak detection function is required,
press and hold the 

 button down for 5 seconds or

more. The unit will start the test operation.

In case the leak detection function is not required,
go into setting mode 2 by pressing the 

 button for 5

seconds. The H1P LED is on 

w

. Perform following steps.

1.

Press the 

 button 3 times.

2.

Press the 

 button once to confirm.

3.

Press the 

 button in order to change the LED

display to the following display.

4.

Press the 

 button once to confirm.

5.

Press the 

 button a second time to start the

test operation. The unit will start the test operation.

The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.

It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.

During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the LED display may change, but these are not mal-
functions.

During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the 

 button. The unit will stop after

±30 seconds.

6

Close the front panel in order to let it not be the cause of
misjudgement.

7

Check the test operation results by the LED display on the
outdoor unit.

8

When the test operation is fully completed, normal operation will
be possible after 5 minutes. 

Otherwise, refer to 

"Correcting after abnormal completion of the

test operation" on page 25

  to take actions for correcting the

abnormality.

Correcting after abnormal completion of the test operation

The test operation is only completed if there is no malfunction code
displayed on the remote controller. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:

Confirm the malfunction code on the remote controller

Do not insert fingers, rods or other objects into the air
inlet or outlet. When the fan is rotating at high speed, it
will cause injury.

Do not perform the test operation while working on the
indoor units.

When performing the test operation, not only the outdoor
unit, but the connected indoor unit will operate as well.
Working on a indoor unit while performing a test operation
is dangerous.

NOTE

A test operation can not be carried out when the
outdoor temperature is less than –5°C.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x w w

BS1  MODE

BS4  TEST

BS1  MODE

BS2  SET

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x

x c

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x

x

x c x

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Normal completion

x

x w x

x

x

x

Abnormal completion

x w w x

x

x

x

Installation error

Error code

Remedial action

The stop valve of an 
outdoor unit is left 
closed.

E3

E4

F3

F6

UF

Open the stop valve.

The phases of the 
power to the outdoor 
units are reversed.

U1

Exchange two of the three phases 
(L1, L2, L3) to make a positive 
phase connection.

No power is supplied 
to an outdoor or 
indoor unit (including 
phase interruption).

LC

U1

U4

Check if the power wiring for the 
outdoor units are connected 
correctly.

Incorrect 
interconnections 
between units

UF

Check if the refrigerant line piping 
and the unit wiring are consistent 
with each other.

Refrigerant 
overcharge

E3

F6

UF

Recalculate the required amount of 
refrigerant from the piping length 
and correct the refrigerant charge 
level by recovering any excessive 
refrigerant with a refrigerant 
recovery machine.

Insufficient refrigerant

E4

F3

Check if the additional refrigerant 
charge has been finished correctly.
Recalculate the required amount of 
refrigerant from the piping length 
and add an adequate amount of 
refrigerant.

BS3  RETURN

BS2  SET

BS3  RETURN

BS3  RETURN

BS3  RETURN

Содержание VRV III REMQ8P8Y1B

Страница 1: ...INSTALLATION MANUAL REMQ8P8Y1B REMQ10P8Y1B REMQ12P8Y1B REMQ14P8Y1B REMQ16P8Y1B System air conditioner ...

Страница 2: ...m b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 10...

Страница 3: ...20 mm 500 mm 1 1 1 A B 2 2 2 4 5 3 8 F1 F2 F1 F2 Q1 Q2 F1 F1 F2 F2 Q1Q2 7 TOIN DUNIT TOOUT DUNIT TOMULTIUNIT A1P Q1 Q2 A1P Q1 Q2 A1P 1 2 2 3 4 5 6 8 10 10 9 9 REMQ8 12 REMQ14 16 1 2 3 4 1 5 6 7 8 F1 F2F1F2 F1 F2F1F2 TO IN D UNIT TO OUT D UNIT TO IN D UNIT TO OUT D UNIT F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 11 10 10 9 9 12 13 14 15 16 17 18 20 19 21 ...

Страница 4: ...ään ohjeidemme mukaisesti 14 za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům 15 u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják 17 spe...

Страница 5: ...štelę 23 Maksimālais pieļaujamais spiediens PS K bar Minimālā maksimālā pieļaujamā temperatūra TS TSmin Minimālā temperatūra zemā spiediena pusē L C TSmax Piesātinātā temperatūra saskaņā ar maksimālo pieļaujamo spiedienu PS M C Dzesinātājs N Spiediena drošības ierīces iestatīšana P bar Izgatavošanas numurs un izgatavošanas gads skat modeļa izgatavotājuzņēmuma plāksnītie 24 Maximálny povolený tlak ...

Страница 6: ...pes will cause malfunctions when combined with the REYQ P system The REMQ P units can be combined with Daikin VRV indoor units for air conditioning purposes suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the REMQ P units Installation of the indoor units is not described in this manual Always refer to the installation manual suppl...

Страница 7: ...350 910 REYQ30 REMQ14 REMQ16 375 975 REYQ32 REMQ16 REMQ16 400 1040 REYQ34 REMQ8 REMQ10 REMQ16 425 1105 REYQ36 REMQ8 REMQ12 REMQ16 450 1170 REYQ38 REMQ10 REMQ12 REMQ16 475 1235 REYQ40 REMQ12 REMQ12 REMQ16 500 1300 REYQ42 REMQ10 REMQ16 REMQ16 525 1365 REYQ44 REMQ12 REMQ16 REMQ16 550 1430 REYQ46 REMQ14 REMQ16 REMQ16 575 1495 REYQ48 REMQ16 REMQ16 REMQ16 600 1560 NOTE When installing a multi outdoor sy...

Страница 8: ...oncentration from exceeding allowable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke ...

Страница 9: ...height of the foundation must at least be 150 mm from the floor The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete and make sure the base under the unit is larger than the grey marked area as indicated in figure 3 Fasten the unit in place using four foundation bolts M12 It is best to screw in the foundation bolts until their length remains 20 mm above the fou...

Страница 10: ... be installed by a licensed refrigeration technician and must comply with relevant local and national regulations Caution to be taken when brazing refrigerant piping Do not use flux when brazing copper to copper refrigerant piping Particularly for the HFC refrigerant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has extremely harmful influence ...

Страница 11: ... around the edges using repair paint to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage 1 Large knockout hole 2 Small knockout hole 3 Drill 4 Points for drilling Any gas remaining inside the stop valve may blow off the pinched piping causing damage or injury 1 Pinched piping 2 Do not dissolve this brazing 3 Auxiliary ...

Страница 12: ...ohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping between outdoor units as shown in the 4 correct possibilities of the figure below Prohibited patterns change to pattern 1 or 2 Change to configuration as in figures below Correct configuration If the piping length between the outdoor units exceeds 2...

Страница 13: ... installation may lead to malfunction of the outdoor unit 5 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level difference and allowable length after branching as indicated in 6 6 Example of connection on page 9 6 5 Protection against contamination when installing pipes Take measures to prevent foreign materi...

Страница 14: ...Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the capacity of the outdoor unit example refnet joint A How to select the refnet header Choose from the following table in accordance with the total capacity of...

Страница 15: ...it can be extended up to 90 m if all the following conditions are fulfilled Required conditions Example drawings It is necessary to increase the pipe size of the liquid and suction gas pipe if the pipe length between the first and the final branch kit is over 40 m reducers must be procured on site Increasing the HP LP gas pipe size is not allowed If the increased liquid pipe size is larger than th...

Страница 16: ... Liquid line stop valve 11 Refrigerant charge port 12 Valve A 13 Valve B 14 Valve C 15 To BS unit or indoor unit 16 Stop valve 17 Service port 18 Field piping 19 Gas flow NOTE Make sure to perform airtightness test and vacuum drying using the service ports of the stop valves of the equalizer pipe HP LP gas pipe suction gas pipe and liquid pipe For the service port location refer to the Caution lab...

Страница 17: ...quid H E liquid suction liquid R10 Resistor current sensor A4P A8P R31T R33T Thermistor discharge M1C M3C R50 R59 Resistor R90 Resistor current sensor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Diode bridge A3P V1R Power module A4P A8P V2R Power module A3P X1A X4A Connecto...

Страница 18: ...e to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding Be sure to install an earth leakage breaker One that can handle...

Страница 19: ...ing wires to the terminal block on the PC board too much heat or tightening could damage the PC board Attach with care See the table below for the tightening torque of the transmission wiring terminals 1 Field power supply 6 Remote controller 2 Main switch 7 BS unit 3 Earth 8 Cool heat selector 4 Outdoor unit 9 Earth leakage breaker 5 Indoor unit 10 Fuse Power supply wiring sheathed cable 380 415 ...

Страница 20: ... wiring between outdoor units 1 Liquid pipe 2 HP LP gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3 N 50 Hz 2 Earth leakage breaker 3 Fuse 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using a f...

Страница 21: ...n page 5 The electrical work 1 Make sure there is no faulty power wiring or loose nuts See 8 Field wiring on page 11 2 Make sure there is no faulty transmission wiring or loose nuts See 8 Field wiring on page 11 3 Make sure the insulation resistance of the main power circuit is not deteriorated Measure the insulation resistance and check if the value is in accordance with relevant local and nation...

Страница 22: ...ve Refrigerant cannot be charged until all field wiring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means that in case the calculated refrigerant charge is equal to or more than 95 kg you must divide your multiple outdoor system into smaller independent sy...

Страница 23: ... 1 H1P x OFF BS1 MODE BS1 MODE BS2 SET BS2 SET BS3 RETURN BS1 MODE Adding refrigerant using the automatic refrigerant charging function is recommended When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the refrigerant charging procedure is done or when pausing close the valve of the...

Страница 24: ...trument 2 Refrigerant tank R410A siphon system 3 Charge hose 4 Equalizer pipe stop valve 5 High pressure low pressure gas pipe stop valve 6 Suction gas pipe stop valve 7 Liquid pipe stop valve 8 Refrigerant charge port 9 Valve A 10 Valve B 11 Valve C 12 To BS unit indoor unit 13 Stop valve 14 Service port 15 Field piping 16 Refrigerant flow when pre charging through the liquid stop valve service p...

Страница 25: ...system reaches the stable state It may disturb a correct decision and may cause overcharging 7 Ready Press the button once within 5 minutes If the button is not pushed within 5 minutes P2 will be displayed on the remote controller Refer to 3 Remote controller malfunction code display on page 21 8 Operation When the following LED display is shown open valve A and close the front panel If the front ...

Страница 26: ...nt charging operation If the refrigerant tank is left with the valve open the amount of refrigerant which is properly charged may be off the point H1P H2P H3P H4P H5P H6P H7P w c c w w w w LED display Default status before delivery Micro computer operation monitor Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H...

Страница 27: ...x 15 70 x 75 w x x w w w w 16 75 x 80 w x w x x x x 17 80 x 85 w x w x x x w 18 85 x 90 w x w x x w x 19 90 x 95 w x w x x w w 20 95 x 100 w x w x w x x 21 100 x w x w x w x w NOTE If you get confused in the middle of the input process press the button to return to setting mode 1 initial state The H1P LED is off x Resume the input procedure from step 2 onwards BS2 SET BS3 RETURN BS2 SET BS3 RETURN...

Страница 28: ... is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor unit and the indoor unit Be sure to turn the power on at least 6 hours before operation in order to have power running to the crankcase heater 2 Make sure that transmission is normal by checking the LED display...

Страница 29: ...normal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limitation setting x standard operation factory setting w operation NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P LED is off Possible functions...

Страница 30: ...ing the test operation the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not mal functions During the test operation it is not possible to stop the unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the...

Страница 31: ...g 4 When the unit is not operating push the button until the additional refrigerant charging operation function A in setting mode 2 can be defined refer to Setting the mode on page 24 the H1P LED is on w 5 The operation starts automatically The H2P LED will start flashing c and the messages Test operation and Under centralized control will display on the remote controller 6 After charging the spec...

Страница 32: ... as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration...

Страница 33: ...0 3 2 6 6 6 6 23 18 9 8 1 2 4 3 5 13 14 15 10 7 12 19 2 1 24 6 11 16 17 15 6 5 10 11 12 7 4 9 16 17 18 3 8 13 14 2 2 1 1 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 4 4 6 6 6 6 6 6 22 23 24 ...

Страница 34: ...4PW40598 1A Copyright Daikin ...

Отзывы: