[How to Check How Many Units are Connected]

It is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the PC-board (A1P) of out-
door unit (In case of multi system master unit).
Follow the procedure below to check how many indoor or outdoor units are turned on.

Note

Press the “MODE button” (BS1) if you get confused while operating.
This returns to 

Setting Mode 1

 (default).

• Refer to “

„

 Function of push-button” on page 24.

1.

Check of power supply

• Make sure to turn on both indoor, BS and outdoor units.

If check operated when any of the indoor units is not turned on, 
check of refrigerant amount is not completed properly.

• Make sure to turn on all the connected indoor units.

Please see 

[How to Check How Many Units are Connected]

 

(Descriptions on above) for checking numbers of connected 
indoor units from an outdoor unit.

11-2 Procedure of check operation

WARNING

ELECTRIC SHOCK WARNING

• Make sure to close the EL. COMPO. BOX lid before turning on 

the power when performing the refrigerant charging operation.

• Perform the setting on the PC-board (A1P) of the outdoor unit and 

check the LED display after the power is on via the inspection 
door which is in the EL. COMPO. BOX lid.

• Use an insulated rod to operate the push buttons via the EL. 

COMPO. BOX’s inspection door.
There is a risk of electric shock if you touch any live parts, since 
this operation must be performed with the power on.

(Refer to figure 32)

1.

EL.COMPO.BOX lid

2.

DIP switch (DS1-1~4)

3.

Inspection door

4.

Label “Service Precaution”

5.

LED (H1~8P)

6.

Push button (BS1-5)

7.

Lift the protruding part to open the cover

CAUTION

• Make sure to use the protect tool (protective groves and gog-

gles) when charging the refrigerant.

• Due to a danger of liquid hammer, the refrigerant must not be 

charged over the allowable maximum amount when charging the 
refrigerant.

• Do not perform the refrigerant charging operation under working 

for BS and indoor unit. (BS unit is used only RQCEQ series.)

• When opening the front panel, make sure to take caution to the fan 

rotation during the working.
After the outdoor unit stops operating, the fan may keep rotation 
for a while.

Note

• If operation is performed within 12 minutes after the indoor and 

outdoor units are turned on, H2P will be lit on and the compressor 
will not operate.

• In order to ensure uniform refrigerant distribution, it may take up to 

around 10 minutes for the compressor to start up after the unit 
starting operating. This is not a malfunction.

<About refrigerant charging>

• The refrigerant charge port is connected to the piping inside the 

unit.
When the unit is shipped from the factory, the unit’s internal piping 
is already charged with refrigerant, so be careful when connecting 
the charge hose.

• After adding the refrigerant, make sure to close the lid of the 

refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.

• See [Shutoff valve operation procedure] in chapter 11-1 for details 

on how to handle shutoff valves.

• When done or when pausing the refrigerant charging operation, 

close the valve of the refrigerant tank immediately. If the tank is 
left with the valve open, the amount of refrigerant which is prop-
erly charged may be off the point. More refrigerant may be 
charged by any remaining pressure after the machine is stopped.

<About check operation>

Make sure to perform the check operation after installation. 
Otherwise, the malfunction code “U3” will be displayed and 
normal operation cannot be performed.

And the failure of “Check of miswiring” may also cause abnormal 
operation. Performance may drop due to the failure of “Judgment 
of piping length”.

• Check operation must be performed for each refrigerant piping 

system.
Checking is impossible if multiple systems are being done at 
once.

(LED display: 

h

 ...OFF  

k

 ...ON  

l

 ...Blinking  

 ...Uncertain)

LED display

H1P H2P H3P H4P

H5P

H6P

H7P

(1) Press the MODE button (BS1) once, and set the MONITOR MODE (H1P: Blinking).

l

h

h

h

h

h

h

(2) Press the SET button (BS2) the number of times until the 

LED display matches that at right.

For checking the number 
of outdoor units: eight 
times

l

h

h

k

h

h

h

For checking the number 
of indoor units: five times

l

h

h

h

k

h

k

(3) Press the RETURN button (BS3) and read the number of units from the display of 

H2P through H7P.
[Reading Method]
The display of H2P through H7P should be read as a binary number, with 

l

 standing 

for “1” and 

h

 standing for “0”.

l

l

h

l

h

l

l

h

(4) Press the “MODE button” (BS1) once. This returns to 

Setting Mode 1

 (default).

h

h

k

h

h

h

h

Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”, 
which would mean 22 units are connected.

Note: “000000” indicates 64 units.

32 × 

0

 + 16 × 

1

 + 8 × 

0

 + 4 × 

1

 + 2 × 

1

 + 1 × 

0

 = 22 units

01_EN_3P226891-14T.fm  Page 20  Tuesday, September 30, 2014  7:48 PM

Содержание VRV III-Q RQYQ140PY1

Страница 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Страница 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Страница 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Страница 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Страница 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Страница 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Страница 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Страница 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Страница 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Страница 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Страница 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Страница 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Страница 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Страница 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Страница 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Страница 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Страница 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Страница 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Страница 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Страница 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Страница 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Страница 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Страница 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Страница 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Страница 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Страница 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Страница 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Страница 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Страница 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Страница 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Страница 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Страница 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Страница 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Отзывы: