background image

 

FXMQ50-125P7VEB9
VRV System air conditioners
3P468515-4 – 12.2016

Installation and operation manual

10

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring

-

Connect input from outside to terminals T1 and T2 of the 
terminal board (remote controller to transmission wiring).

2

Actuation

-

The following table explains "forced off" and "on/off 
operations" in response to input A.

3

How to select forced off and on/off operation

-

Turn the power on and then use the remote controller to 
select operation.

-

Set the remote controller to the field set mode. For details, 
refer to the chapter "How to set in the field", in the remote 
controller manual.

-

When in the field set mode, select mode No. 12, then set the 
first code No. to "1". Then set second code (position) No. to 
"01" for forced off and to "02" for on/off operation. (forced off 
at factory set.) 

(See figure 20)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel.

T

EST

 

OPERATION

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an error
occurs. Check the error code on the liquid crystal display to identify
the trouble. 

If any of the items in following table are displayed on the remote
controller, there may be a problem with the wiring or power, so check
the wiring again.

M

AINTENANCE

How to clean the air filter

Clean the air filter when the display shows "

" (TIME TO CLEAN

AIR FILTER).

Increase the frequency of cleaning if the unit is installed in a room
where the air is extremely contaminated.

If the dirt becomes impossible to clean, change the air filter. (Air filter
for exchange is optional.)

1

Open the suction grille. (Only for bottom suction.)

Slide both knobs simultaneously as shown and then pull them
downward.

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

Forced off

on/off operation

Input "on" stops 
operation 

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control 

input on 

 off: turns off the unit by 

remote controller

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

F2

T1

T2

FORCED
OFF

Input A

Error code

Meaning

A8

Error in power supply to indoor unit

C1

Transmission error between fan driver PCB and controller 
PCB of the indoor unit

C6

Improper combination of fan driver PCB of the indoor unit or 
setting failure in control PCB type

U3

Test operation of the indoor unit has not been finished

Error code

Meaning

There is a short circuit at the forced off terminals (T1, T2)

U4

 or 

UH

- The power on the outdoor unit is off
- The outdoor unit has not been wired for power supply
- Incorrect transmission of forced off wiring

no display

- The power on the indoor unit is off
- The indoor unit has not been wired for power supply
- Incorrect transmission wiring, forced off wiring or remote 

controller wiring

Caution

Only a qualified service person is allowed to perform
maintenance.

Before obtaining access to terminal devices, all power
supply circuits must be interrupted.

Do not use water or air of 50°C or higher for cleaning
air filters and outside panels.

When cleaning the heat exchanger, be sure to remove
the switchbox, fan motor, auxiliary electric heater and
drain pump. Water or detergent may deteriorate the
insulation of electronic components and result in burn-
out of these components.

If the main power supply is turned off during
operation, operation will restart automatically after the
power turns back on again.

Содержание VRV FXMQ100P7VEB9

Страница 1: ...INSTALLATION AND OPERATION MANUAL FXMQ50P7VEB9 FXMQ63P7VEB9 FXMQ80P7VEB9 FXMQ100P7VEB9 FXMQ125P7VEB9 System air conditioners ...

Страница 2: ... 680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5 6 2 1 5 4 1 3 2 6 4 4 A A 1 2 3 4 5 6a 6b 6c 7a 7b 7c 8 9 10 11 ...

Страница 3: ...tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Se...

Страница 4: ...re machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire This appliance is not intended for ...

Страница 5: ...al appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept When installing the wireless remote controller kit the distance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fl...

Страница 6: ...ng surface 2 Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation with duct but no duct service opening modify the position of the air filters 1 Remove the air filter s at the outside of the unit 2 Remove the interchangeable plate 3 Install the air filter s fro...

Страница 7: ...the specified refrigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque Overtightening may damage the flare and cause leaks Table 1 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand ...

Страница 8: ... the drain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than 625 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit To prevent air bubbles install the drain hose level or slightly tilted up 75 mm T...

Страница 9: ...legislation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal block wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and an indoor unit are mismatched the system m...

Страница 10: ...or units less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 Ø1 6 The branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding terminal Looseness in the...

Страница 11: ... indications Ultra long life filter Light 10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of ...

Страница 12: ...on the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 10 and the operation manual of the outdoor unit Check the defective point Using the remote controller Check on an indoor unit if the second code of mode No 21 is set to 01 factory setting Change the second code according to the external static pressure of the duct to be con...

Страница 13: ...r is extremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable l...

Страница 14: ...t the air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch at least 6 hours before operation What to do when stopping the sys...

Страница 15: ...X1M TERMINAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR ADAPTOR X38A CONNECTOR FOR WIRING WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB FIELD WIRING BLK BLACK ORG ORANGE CONNECTOR ...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ... N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4 7 8 9 SETTING 2 1 3 4 S M S S M 2 3 1 1 2 3 4 5 L N L N L N L N L N L N L N L N L N 4 18 19 16 17 12 14 15 13 20 12 13 14 15 16 17 19 18 20 ...

Страница 20: ...3P468515 4 12 2016 Copyright 2016 Daikin ...

Отзывы: