10. WIRING EXAMPLE

10-1 HOW TO CONNECT WIRINGS 

Wire only after removing the control box lid as shown in 

Fig. 17, refering to view A.

CAUTION

Be sure to attach power supply wiring and earth wire to the 

control box with the clamp.

When doing the wiring, make sure the wiring is neat and 

does not cause the control box lid to stick up, then close the 

cover firmly. When attaching the control box lid, make sure 

you do not pinch any wires.

Outside the air conditioners, separate the weak wiring 
(remote controller and transmission wiring) and strong wiring 
(earth wire and power supply wiring) by at least 50 mm so 
that they do not pass through the same place together. Prox-
imity may cause electrical interference, malfunctions, and 
breakage.

A main switch or other means for disconnection, having a 

contact separation in all poles, must be incorporated in the 

fixed wiring in accordance with relevant local and national 

legislation.

Note that the operation will restart automatically if the main 

power supply is turned off and then turned back on again.

[ PRECAUTIONS ] 

Refer to the “REMOTE CONTROLLER INSTALLATION 

MANUAL” on how to install and lay the wiring for the remote 

controller.

See also the “Wiring Diagram plate” attached to the control 

box lid when laying electrical wiring.

Connect the remote controller and transmission wiring to 

their respective terminal blocks.

CAUTION

• Do not, under any circumstances, connect the power sup-

ply wiring to the remote controller or transmission wiring 

terminal block. Doing so can destroy the entire system.

[ Connecting electrical wiring, remote controller wiring, 
and transmission wiring ] (Refer to Fig. 18)

• Power supply and Earth wiring

Remove the control box lid.

Next, pull the wires into the unit through the Wiring through 

hole and connect to the terminal block (3P).

Be sure to put the part of the sheathed vinyl into the control 

box.

(Rear)

Wiring Diagram

Control box lid

Power supply wiring
Earth wire

Penetration area

• Make sure to let a wire go through a wire penetration area.
• After wiring, seal the wire and wire penetration area to prevent 

moisture and small creatures from the outside.

• Wrap the strong and weak electric lines with the sealing 

material (12) as shown in the figure below.

  (Otherwise, moisture or small creatures such as insects from 

the outside may cause short-circuit inside the control box.) 
Attach securely so that there are no gaps.

Sealing 
material (12)

(accessory)

Wire

[How to adhere to it]

Outside 
unit

Inside 
unit

Fig. 17

view A

Power supply wiring
Earth wire

Indoor PCboard 

(ASSY)

Clamps
(for preventing slippage)

*Transmission wiring
*Remote controller wiring

* Do not connect power 

supply wiring here.
That may cause 
malfunction

Control box

Control box

Power supply wiring/Earth wire

Fig. 18

Remote controller wiring
Transmission wiring

Power supply wiring
Earth wire

Wiring through hole

Wiring through hole

Terminal block (6P)

Terminal block (3P)

Indoor PCboard (ASSY)

Clamps

P1 P2 F1 F2 T1 T2

TRANSMISSION

    WIRING

FORCED
  OFF

REMOTE
 CNTRL

4PEN365593-1A.book  Page 10  Tuesday, June 9, 2015  2:44 PM

Содержание VRV FXDQ15P2VE

Страница 1: ...INSTALLATION MANUAL FXDQ15P2VE FXDQ20P2VE FXDQ25P2VE FXDQ32P2VE FXDQ40P2VE FXDQ50P2VE FXDQ63P2VE System Inverter Air Conditioners 4PEN365593 1A book Page 1 Tuesday June 9 2015 2 44 PM...

Страница 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acor...

Страница 3: ...phoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that a...

Страница 4: ...to the unit When moving the unit at or after opening hold the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A...

Страница 5: ...talled as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk...

Страница 6: ...to prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken a...

Страница 7: ...ation may form on the surface of the insulation if the temperature above the ceiling reaches 30 C or the humidity RH80 CAUTION Follow the points below Use a pipe cutter and flare suitable for the type...

Страница 8: ...se phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluori...

Страница 9: ...efer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the dra...

Страница 10: ...ection area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side U...

Страница 11: ...ls Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case...

Страница 12: ...power sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wirin...

Страница 13: ...em For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18...

Страница 14: ...WORK 3 Remove the control box lid 4 Add remote controller 2 SUB to the terminal block for remote controller P1 P2 in the control box There is no polarity L N F F1 2 F F1 2 F F1 2 F F1 2 IN D IN D OUT...

Страница 15: ...should be selected by selecting the SECOND CODE NO as shown in the table below The SECOND CODE NO is set to 01 when shipped Input A of forced off and ON OFF operation work as shown in the table below...

Страница 16: ...f the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote controller to stop operation 4...

Страница 17: ...24A CONNECTOR WIRELESS REMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWI...

Страница 18: ...4P365593 1A 2015 06 Copyright 2013 Daikin 4PEN365593 1A book Page 1 Tuesday June 9 2015 2 44 PM...

Отзывы: