7. DRAIN PIPING WORK

CAUTION

The connection opening on the drain piping may vary
depending on the model, so check the model name and use
the right method for that model.

Make sure all water is out before making the duct connection.

(1) Install the drain piping.

Make sure the drain works properly.

The diameter of the drain piping should be greater than or
equal to the diameter of the connecting pipe (vinyl tube; pipe
size: 20 mm; outer dimension: 26 mm).
(not including the riser)

Keep the drain piping short and sloping downwards at a
gradient of at least 1/100 to prevent air pockets from forming.

(Refer to Fig. 10)

CAUTION

Water accumulating in the drain piping can cause the 
drain to clog.

To keep the drain piping from sagging, space hanging
bracket every 1 to 1.5 m.

Use the drain hose (2) and the metal clamp (1). Insert the
drain hose (2) fully into the drain socket and firmly tighten the
metal clamp (1) with the upper part of the tape on the hose
end. Tighten the metal clamp (1) until the screw head is less
than 4 mm from the hose. 

(Refer to Fig. 11, 12)

The two areas below should be insulated because
condensation may form there causing water to leak.

Drain piping passing indoors

Drain socket

Referring the figure below, insulate the metal clamp (1) and 
drain hose (2) using the included large sealing pad (5).

(Refer to Fig. 12)

In case of PDVE, NDVE type (with drain pump)

Drain socket

Refrigerant pipes

Service drain hole 
(with rubber cap)

600mm or less

Central drain piping 

(with a slope of at least 1/100)

Fig. 10

CAUTION

Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 

condensation or burns if touched.

When brazing the refrigerant piping, perform nitrogen
replacement first, or perform the brazing (CAUTION 2) while
feeding nitrogen into the refrigerant piping (CAUTION 1), and
finally connect the indoor unit using the flare connections.

(Refer to Fig. 9)

CAUTION

1. When brazing a pipe while feeding nitrogen inside the

pipe, make sure to set the nitrogen pressure to 0.02 MPa
(0.2 kg/cm

2

) using the pressure reducing valve.  (This

pressure is such that breeze is blown to your cheek.)

2. Do not use a flux when brazing the refrigerant pipe joints.

Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) which does not require flux.
(Using a flux containing chlorine may cause the piping to
corrode.  Using a welding flux containing fluorine may
cause the refrigerant lubricant to deteriorate, and affect
adversely the refrigerant piping system.)

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the 
unit without a torque wrench, you may follow the installation 
method mentioned below.

After the work is finished, make sure to check that there is 
no gas leak.

When you keep on tightening the flare nut with a spanner, there 
is a point where the tightening torque  suddenly increases. From 
that position, further tighten the flare nut the angle shown below:
Table 2

Pipe size

Further tightening angle

Recommended arm 

length of tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150 mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200 mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250 mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300 mm

Refrigerant piping

Part to be brazed

Taping

Pressure-reducing valve

hands 

valve

Nitrogen

Nitrogen

Fig. 9

Содержание VRV FXDQ-PDVE

Страница 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz...

Страница 2: ......

Страница 3: ...eristics 19 7 Safety Devices Setting 20 8 Capacity Tables 21 8 1 Cooling Capacity for Te Auto 21 8 2 Cooling Capacity for Te 6 C 21 8 3 Cooling Capacity for Te 9 C 22 8 4 Heating Capacity 22 9 Fan Per...

Страница 4: ...S 63NDV2S 40NDVTS 50NDVTS 63NDVTS FXDQ for Indonesia 20PDVE4 25PDVE4 32PDVE4 20PDVT4 25PDVT4 32PDVT4 40NDVE4 50NDVE4 63NDVE4 40NDVT4 50NDVT4 63NDVT4 Note FXDQ has following 2 series as shown below FXD...

Страница 5: ...A 28 26 23 28 26 23 Sound power level HH H L dB A 56 54 51 56 54 51 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion va...

Страница 6: ...mal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp...

Страница 7: ...26 23 Sound power level HH H L dB A 56 54 51 56 54 51 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic...

Страница 8: ...ermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Cla...

Страница 9: ...28 26 33 30 27 Sound power level HH H L dB A 58 56 54 61 58 55 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve...

Страница 10: ...hermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Cl...

Страница 11: ...33 30 27 Sound power level HH H L dB A 58 56 54 61 58 55 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electr...

Страница 12: ...Thermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting...

Страница 13: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 11 3 Dimensions 3 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE with a drain pump 3D049799D Unit mm...

Страница 14: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 12 FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET without a drain pump 3D050732C Unit mm...

Страница 15: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 13 3 2 FXDQ NDVE T FXDQ40NDVE FXDQ50NDVE with a drain pump 3D045494E Unit mm...

Страница 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm...

Страница 17: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 15 FXDQ40NDVET FXDQ50NDVET without a drain pump 3D049701D Unit mm...

Страница 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm...

Страница 19: ...DQ63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50N...

Страница 20: ...DQ PDVE T FXDQ NDVE T EDFMT391749 18 5 Wiring Diagrams FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET 3D10333...

Страница 21: ...DVE T FXDQ NDVE T EDFMT391749 19 6 Electric Characteristics FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET 3D...

Страница 22: ...5 A 250 V 5 A Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Drain pump thermal fuse C Model FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE Printed circuit board fuse 250 V...

Страница 23: ...ing length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air te...

Страница 24: ...otes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature a...

Страница 25: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 23 9 Fan Performances 9 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ20PDVET FXDQ25PDVET 3D052156E...

Страница 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E...

Страница 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G...

Страница 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G...

Страница 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G...

Страница 30: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 28 10 Sound Levels 10 1 FXDQ PDVE T FXDQ20PDVE FXDQ20PDVET FXDQ25PDVE FXDQ25PDVET 4D112287 4D112290...

Страница 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291...

Страница 32: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 30 10 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET FXDQ50NDVE FXDQ50NDVET 4D112292 4D112294...

Страница 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295...

Страница 34: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 32 11 Centre of Gravity 11 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET 4D049300M Unit mm...

Страница 35: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 33 11 2 FXDQ NDVE T FXDQ40NDVE FXDQ50NDVE FXDQ40NDVET FXDQ50NDVET 4D043886R Unit mm...

Страница 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm...

Страница 37: ...BRC1C62 Note 4 Navigation remote controller Wired remote controller BRC1E62 Note 4 Simplified remote controller BRC2C51 Remote controller for hotel use BRC3A61 Adaptor for wiring KRP1B56 Wiring adapto...

Страница 38: ...stall the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of in...

Страница 39: ...eted Do not discard them 1 Decide upon a line of transport 2 Leave the unit inside its packaging while moving until reaching the installation site Where unpacking is unavoidable use a sling of soft ma...

Страница 40: ...your customer Did you hand the operation manual and warranty over to your customer Did you explain about the way of maintaining and cleaning local procurements air filter grille both air outlet and su...

Страница 41: ...e glass wool or polyethylene foam as insulation so that it is no thicker than 10 mm and fits inside the ceiling opening 1 Select an installation site where the following conditions are fulfilled and t...

Страница 42: ...Open the installation hole Pre set ceilings Once the installation hole is opened in the ceiling where the unit is to be installed pass refrigerant piping drain piping transmission wiring and remote co...

Страница 43: ...the flare nut connection Main unit 4 Tighten the upper nut 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out in...

Страница 44: ...ate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched When brazing the refrigerant piping perform nitrogen replacement...

Страница 45: ...nspection window Portable pump Inspection lid Refrigerant pipes Bucket Service drain hole Drain outlet with rubber cap Indoor PC board ASSY Terminal block Terminal block Remote controller terminal con...

Страница 46: ...mething similar to prevent air escaping Class 20 25 32 40 50 63 Number of positions 16 22 26 Portable pump Refrigerant pipes Bucket Air outlet Drain outlet Connection screw 7 accessory Field supply Fi...

Страница 47: ...to insulate the duct to prevent condensation from forming Material glass wool or polyethylene foam 25 mm thick Use electric insulation between the duct and the wall when using metal ducts to pass meta...

Страница 48: ...0 as shown in the Fig 17 to prevent outside pres sure being exerted on the wiring connections and clamp firmly Be sure to attach power supply wiring and earth wire to the control box with the clamp Wh...

Страница 49: ...ls with insulation sleeve or insulate the wirings properly Connect the terminal as shown in Fig 20 Do not carry out soldering finish when stranded wires are used Otherwise the loosening of wires may r...

Страница 50: ...unit 2 Max No of indoor units Crossover wire P1 P2 Remote controller 1 MAIN Remote controller 2 SUB Input A 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING No 3 system When includ...

Страница 51: ...sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of the con ne...

Страница 52: ...wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote controller to stop operation 4 After finishing the test run make sure to check...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...arts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation o...

Отзывы: