Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
158
1.4.15 Optional Accessories Output Selection
Using this setting,
operation output signal
and
abnormal output signal
can be provided. Output
signal is output between terminals X1 and X2 of adaptor for wiring, an optional accessory.
: Factory setting
1.4.16 External ON/OFF Input
This input is used for ON/OFF operation and protection device input from the outside. The input is
performed from the T1-T2 terminal of the operation terminal block in the electrical component box.
: Factory setting
1.4.17 Thermostat Differential Changeover
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with ON/OFF of remote controller is provided.
04
In case of Error Display appears on the remote controller, output is
provided.
05
—
06
—
07
Only for FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB
Economizer (field supply) ON/OFF signal is provided.
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Permission of operation
ON
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The other
indoor units indicate
U9
.
04
—
05
Only for FXSQ-TA, FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
06
—
07
Only for FXSQ-TB, FXMQ-TB
ON: Economizer (field supply) is connected.
OFF: Not connected
F2 T1 T2
Forced stop
Input A
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Model
Second Code No.
Contents
FXFQ-T, FXFQ-P, FXZQ-TA, FXZQ-M, FXUQ-P, FXEQ-P,
FXSQ-TA, FXHQ-M, FXTQ-TA, FXTQ-TB
01
1°C (1.8°F)
FXFQ-AA, FXZQ-TB, FXUQ-PA, FXDQ-M, FXSQ-TB,
FXMQ-PB, FXMQ-TB, FXMQ-TA, FXMQ-M, FXAQ-P,
FXLQ-M, FXNQ-M, FXMQ-MF, CTXQ-TA
02
0.5°C (0.9°F)
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...