17 Configuration
Installation and operation manual
34
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1A – 2020.01
Ambient
temperature
Humidity
Minimum thickness
≤30°C
75% to 80% RH
15 mm
>30°C
≥80% RH
20 mm
Between outdoor and indoor unit
1
Insulate and fix the refrigerant piping and cables as follows:
g
b
a
f
e
c
d
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Field wiring (if applicable)
e
Liquid pipe
f
Liquid pipe insulation
g
Finishing tape
2
Install the service cover.
Inside the outdoor unit
To insulate the refrigerant piping, proceed as follows:
b
a
c
d
f
e
a
Liquid piping
b
Gas piping
c
Vinyl tape around curves
d
Sealant
e
Vinyl tape against sharp edges
f
Stop valves
3
Insulate the liquid piping (a, see above) and the gas piping (b,
see above).
4
Wind heat insulation around the curves, and then cover it with
vinyl tape (c, see above).
5
Make sure the field piping does not touch any compressor
components.
6
Seal the insulation ends (sealant etc.) (d, see above).
7
Wrap the field piping with vinyl tape (e, see above) to protect it
against sharp edges
8
If the outdoor unit is installed above the indoor unit, cover the
stop valves (f, see above) with sealing material to prevent
condensed water on the stop valves from moving to the indoor
unit.
NOTICE
Any exposed piping might cause condensation.
9
Reattach the service cover and the piping intake plate.
10
Seal all gaps to prevent snow and small animals from entering
the system.
a
a
Seal
NOTICE
Do not block the air vents. This could affect air circulation
inside the unit.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
17
Configuration
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
17.1
Making field settings
17.1.1
About making field settings
To configure the heat pump system, you must give input to the
outdoor unit's main PCB (A1P). This involves the following field
setting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
▪ DIP switches (only change the factory settings if you install a cool/
heat selector switch).
See also:
▪
"17.1.3 Field setting components"
▪