16 Electrical installation
Installation and operation manual
31
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02
Model
Minimum S
sc
value
RXYSA4_V
122.95 kVA
RXYSA5_V
154.07 kVA
RXYSA6_V
173.05 kVA
16.2
Specifications of standard wiring
components
NOTICE
We recommend using solid (single-core) wires. If stranded
wires are used, slightly twist the strands to consolidate the
end of the conductor for either direct use in the terminal
clamp or insertion in a round crimp-style terminal. Details
are described in "Guidelines when connecting the electrical
wiring" in the installer reference guide.
Component
RXYSA*_V
RXYSA*_Y
Power supply
cable
MCA
(a)
27.0 A
13.6 A
Voltage
220-240 V
380-415 V
Phase
1~
3N~
Frequency
50 Hz
Wire size
MUST comply with national wiring
regulation.
3-core cable
5-core cable
Wire size based on the current, but
not less than:
4.0 mm
2
2.5 mm
2
Interconnection
cable (indoor ↔
outdoor)
Voltage
220-240 V
Wire size
Only use harmonised wire providing
double insulation and suitable for
applicable voltage.
2-core cable
0.75-1.5 mm²
Recommended field fuse
32 A, C curve
16 A, C curve
Earth leakage circuit
breaker / residual current
device
30 mA – MUST comply with national
wiring regulation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
16.3
To connect the electrical wiring to
the outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover. See
2
Connect the interconnection cable as follows:
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
a
a
b
b
V
Y
X4M
TO IN/D
X2M
TO OUT/D
TO IN/D
a
a
a
a
a
a
a
a
Interconnection cable (see
31] for wiring
requirements)
b
Terminal board (field supply)
c
Shielded cable
NOTICE
▪ Use shielded wire for the interconnection cable.
▪ Y1 only: connect the earth (a) to the support frame of
the terminal X2M.
a
3
Connect the power supply as follows:
1~ 50 Hz
220-240 V
L
L
N
V
Y
X1M
3N~ 50 Hz
380-415 V
L1 L2 L3
L1 L2 L3
N
X1M
a
b
c
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable (see
"16.2 Specifications of standard
31] for wiring requirements)
4
Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration below.
Содержание VRV 5-S RXYSA4A7V1B
Страница 46: ......
Страница 47: ......
Страница 48: ...4P600329 1E 2023 02 Copyright 2020 Daikin 4P600329 1 E 0000000 Verantwortung f r Energie und Umwelt...