ESIE15-11A
|
Part 2. Troubleshooting
1. How to retrieve error code and data?
Page 16
23/09/16
VRV4 indoor units
Below items can be consulted in the Service Menu:
Service Menu
Item 2
Remarks
1. Model Name Display
1. Unit No.
Select the Unit No. you want to check.
2. Indoor unit
3. Outdoor unit
2. Operating Hours Display
1. Unit No.
Select the Unit No. you want to check.
2. Indoor unit operating time
All of these are displayed in hours.
3. Indoor unit fan operation
4. Indoor unit energized time
5. Outdoor operating time
6. Outdoor unit fan 1 operation
7. Outdoor unit fan 2 operation
8. Outdoor comp. 1 operation
9. Outdoor comp. 2 operation
3. Indoor Status Display 1/2
1. Unit No.
Select the Unit No. you want to check.
2. FAN
Tap, speed (rpm)
3. FLAP
Swing, fixed
4. Speed
Fan speed (rpm)
5. EV
Degree that electronic expansion valve is open (pls)
6. MP
Drain pump ON/OFF
7. 52H
Electric heater ON/OFF
8. Hu
Humidifier ON/OFF
9. Anti-freezing
Anti-freezing control ON/OFF
3. Indoor Status Display 2/2
1. Unit No.
Select the Unit No. you want to check.
VRV
2. Th1
Suction air thermistor
3. Th2
Heat exchanger liquid pipe thermistor
4. Th3
Heat exchanger gas pipe thermistor
5. Th4
Discharge air thermistor
6. Th5
—
7. Th6
—
4. Outdoor Status Display
1. Unit No.
Select the Unit No. you want to check.
2. FAN Tap 1
Fan tap
3. COMP
Compressor power supply frequency (Hz)
4. EV1
Degree that electronic expansion valve is open (pls)
5. SV1
Solenoid valve ON/OFF
VRV
6. Th1
—
7. Th2
—
8. Th3
—
5. Error Display Selection
1. Warning display ON
Displays a warning on the screen if an error occurs.
2. Warning display OFF
No warning is displayed.
3. Error display ON
Displays the error on the screen.
4. Error display OFF
Displays neither errors nor warnings.
6. Unit No. Transfer
1. Current Unit No.
A unit No. can be transferred to another.
2. Transfer Unit No.
7. Sensor Address Display
Unit No.: 0 - 15
Select the Unit No. you want to check.
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/heating batch address No.
Demand/low-noise address No.
Data
The corresponding data will be displayed, based on the
Unit No. and Code selected.