Sound data
10 - 1 Sound Power Spectrum
VAM650FB
4D082466
Power level data (in case of Total Heat Exchange mode)
(dB) (dBA)
Unit model
name
Hz
Fan speed
63
125
250
500
1000 2000 4000 8000 Total
VAM650FB
U-H
62.0
58.0
52.5
48.5
45.5
41.5
34.0
26.0
51
H
61.0
56.5
51.0
47.0
44.5
39.0
30.0
26.0
50
L
53.5
50.5
46.0
42.0
37.5
32.0
24.0
25.5
44
NOTES
1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m
2
3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound.
VAM800FB
4D082467
Power level data (in case of Total Heat Exchange mode)
(dB) (dBA)
Unit model
name
Hz
Fan speed
63
125
250
500
1000 2000 4000 8000 Total
VAM800FB
U-H
58.0
58.0
52.5
49.5
48.5
41.5
33.5
26.0
53
H
58.5
57.0
51.5
49.5
47.0
40.5
31.0
27.5
52
L
54.5
54.5
47.5
44.5
43.0
35.5
24.5
23.5
47
NOTES
1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m
2
3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound.
VAM1000FB
4D082468
Power level data (in case of Total Heat Exchange mode)
(dB) (dBA)
Unit model
name
Hz
Fan speed
63
125
250
500
1000 2000 4000 8000 Total
VAM1000FB
U-H
62.0
58.5
54.0
50.5
49.0
42.0
36.5
28.0
53
H
61.0
57.0
52.0
50.0
48.0
38.5
31.0
25.5
52
L
58.0
55.0
49.0
45.5
43.5
36.5
27.5
24.0
48
NOTES
1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m
2
3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound.
VAM1500FB
4D082469
Power level data (in case of Total Heat Exchange mode)
(dB) (dBA)
Unit model
name
Hz
Fan speed
63
125
250
500
1000 2000 4000 8000 Total
VAM1500FB
U-H
60.5
61.0
55.5
52.5
50.5
46.0
39.5
29.5
55
H
60.5
60.0
53.5
51.5
49.5
44.5
37.0
31.0
54
L
58.5
58.0
51.0
49.0
47.0
39.5
30.5
31.0
51
NOTES
1. dBA = A-weighted sound power level (A-scale according to IEC).
2. Reference acoustic intensity 0dB = 10E-6μW/m
2
3. Measured according to ISO 3744.
4. The operating sound level may become higher than this value depending on the operating
FRQGLWLRQVUHÀHFWHGVRXQGDQGSHULSKHUDOQRLVH
5. The power IeveIs have been caIcuIated in the assumption that the measuring point is
immediately under the source of operating sound.