Si71-502
Troubleshooting
Troubleshooting
49
1.14
Main Unit PCB Assembly
Error Detection
Method
Check microcomputer operation monitor.
Error Generating
Conditions
When main unit PCB assembly does not operate.
When communication circuit errors.
Possible Causes
Fuse (excess current)
Power transformer
Noise
Main unit PCB
Troubleshooting
Main unit PCB
NO
NO
NO
YES
Does equipment
reset properly.
Is it flashing?
After checking
other possible
causes, replace
PCB assembly.
Is monitor indicator
Off?
YES
YES
Monitor indicator remains
On.
With remote controller
disconnected, check
microcomputer operation
monitor.
Turn off power, then
restart.
Noise may be causing erroneous
operation. If power reset does not
solve the problem, replace main unit
PCB.
There may be a malfunction in main
unit PCB fuse, main unit PCB or power
transformer.
Check fuse and transformer. If they are
normal, replace PCB.
Replace main unit PCB.
(HF013)
Exhaust
air fan
Supply
air fan
CN3
CN4
CN2
CN1
CN7
FuL
10A
CN13
CN8
CN12
CN5
CN6
CN9
KRP
50-2
CN11
CN10
L
N
P2
P1
F1
F2
J1
J2
JC
LED A
(HL031)
(Microcomputor Operation Monitor)
Содержание VAM 150GJVE
Страница 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance ...
Страница 8: ...Si71 502 Introduction vii ...
Страница 13: ...General Constructions Si71 502 4 General Constructions ...
Страница 29: ...Maintenance Si71 502 20 Maintenance ...
Страница 43: ...Circuit Operations Si71 502 34 Circuit Operations ...
Страница 103: ...After sales Service Si71 502 94 Operation Manual ...
Страница 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE ...
Страница 107: ...Appendix Si71 502 98 Appendix ...