background image

English

8

NOTE

• Do not remove the air filter except when cleaning.

Breakdown may occur.

4-2

OPTIMUM OPERATION

Observe the following precautions to ensure the system oper-
ates.

• When the display shows “

 ”, ask a qualified service 

person to clean the filters (Refer to MAINTENANCE).

• Do not operate the HRV unit in Bypass mode when the 

room air is under heating in winter or when the outside 
temperature is 30°C or higher.

This may cause condensation to form on the main unit or on 
discharge grill, or around air supply opening.

• Keep the indoor unit and the remote controller at least 

1 m away from televisions, radios, stereos, and other 
similar equipments.

This may cause distorted picture or noise.

• Turn off the main power supply switch when it is not 

used for long periods of time. When the main power 
switch is turned on, some watts of electricity is being 
used even if the system is not operating.

• Do not install the remote controller where the indoor 

temperature and humidity, respectively, are out of the 
range of 0-35°C and RH 40-80%.

This may cause malfunction.

• Do not install the remote controller where direct sun-

light may fall on it.

This may cause discoloration or deformation.

NOTE

• When the fan motor fails, the remote controller does not dis-

play any error code.
Usage under that status will lead to insufficient ventilation.
The air supply and exhaust fans should be checked once 
every one or two months.
You can make a simple check such as below way.
To check the wind flow, hold a bar of which the end has a 
string or other similar lightweight item over the supply grille 
and exhaust grille.

4-3

HOW TO CLEAN THE HEAT EXCHANGE 
ELEMENT

CLEANING FREQUENCY

AT LEAST ONCE EVERY TWO YEARS
(FOR GENERAL OFFICE USE)
(CLEAN THE ELEMENT MORE FREQUENTLY IF NECES-
SARY.)

WARNING

• Please exchange the heat exchange element if you find 

that the knob of the heat exchange element is damaged 
or is deteriorated when cleaning it.

There is falling danger.

1. Detach the maintenance cover.

Refer to the section (4-1, 1).

2. Detach the air filter.

Refer to the section (4-1, 2).

3. Take out the heat exchange elements.

Pull out the air filter and then pull out the two heat 
exchanger elements. 

(Refer to figure 7)

4. Use a vacuum cleaner to remove dust and foreign objects 

on the surface of the heat exchange element.

(Refer to figure 10)

• Use the vacuum cleaner equipped with a brush on the 

tip of the suction nozzle.

• Lightly contact the brush on the surface of the heat 

exchange element when cleaning.
(Do not crush the heat exchange element while clean-
ing.)

CAUTION (During Operation)

• Do not clean touching strongly with a vacuum cleaner. This 

may crush the mesh of the heat exchange elements.

• Never wash the heat exchange element with water.
• Have your dealer professionally clean the filter if it is very dirty.

5. Put the heat exchange element on the rail and insert it 

securely in place.

6. Install the air filter securely in place.

(Refer to the section (4-1, 4))

7. Install the maintenance cover securely in place.

(Refer to the section (4-1, 5))

CAUTION

• Always use the air filter.

If the air filter is not used, heat exchange elements will be 
clogged, possibly causing poor performance and subse-
quent failure.

4-4

INSPECTION OF THE FAN MOTER

NOTE

• When the fan motor fails, the remote controller does not dis-

play any error code.
Usage under that status will lead to insufficient ventilation.
The air supply and exhaust fans should be checked once 
every one or two months.
You can make a simple check such as below way.
To check the wind flow, hold a bar of which the end has a 
string or other similar lightweight item over the supply grille 
and exhaust grille.

5.

TROUBLE SHOOTING

5-1

THE FOLLOWING SITUATIONS ARE NOT 
MALFUNCTIONS

• Operation does not start.

<Symptom>

The icon “

” (under centralized control) is dis-

played on the remote controller and pressing the on/off but-
ton causes the display to blink for a few seconds.

<Cause>

This indicates that the central device is controlling the unit.
The blinking display indicates that the remote controller can-
not be used.

<Symptom>

The fans rotates after 1 minutes when pressing on on/off 
button.

<Cause>

This indicates that the operation is in preparation.
Wait for about 1 minute.

• Operation stops sometimes.

<Symptom>

“U5” is displayed on the remote controller and the operation 
stops but then restarts after a few minutes.

<Cause>

This indicates that the remote controller is intercepting noise 
from electrical appliances other than the HRV unit, and this 
prevents communication between the units, causing them to 
stop.
Operation automatically restarts when the noise goes away.

3P034927-5_En.fm  Page 8  Sunday, October 30, 2005  3:24 PM

Содержание VAM 150GJVE

Страница 1: ...otal Heat Exchanger HRV Heat Reclaim Ventilation MODELS Ceiling mounted duct type VAM 150GJVE VAM 250GJVE VAM 350GJVE VAM 500GJVE VAM 650GJVE VAM 800GJVE VAM 1000GJVE VAM 1500GJVE VAM 2000GJVE 00_CV_3P034927 5J fm Page 1 Saturday November 19 2005 4 42 PM ...

Страница 2: ...aso tenha algum problema ou se existe alguma falha no funcionamento consulte este manual Guarde este manual para futuras consultas sem pre que não souber como utilizar ou se existir algum problema com a unidade durante a oper ação HRV Вентиляция с реãенерацией тепла До начала работы с DAIKIN HRV внимательно изóчите данное рóêоводство по эêсплóатации При возниêновении любых нарóшений работы или про...

Страница 3: ... 1 MODELS VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE 1 00_CV_3P034927 5J_Illust fm Page 1 Thursday November 24 2005 3 46 PM ...

Страница 4: ...to the same condition as indoors and then brings it indoors Sometimes when first using the unit the smell of the heat exchanging element may be noticeable but it is not harmful The smell will gradually go away as the unit is used Important 17 SA Supply air Supply air to room 15 Maintenance space for the air filters the heat exchange elements and control box 14 OA Outdoor air Fresh air from outdoor...

Страница 5: ...RV unit Combined operation system with VRV systems and Sky air series Remote controller for indoor unit Indoor unit HRV unit Remote controller for HRV unit BRC301B61 Remote controller for indoor unit Remote controller for VRV BRC1A61 62 25 NOT AVAILABLE 27 Remote controller for HRV BRC301B61 NOT AVAILABLE Remote controller for VRV BRC1C61 3 2 00_CV_3P034927 5J_Illust fm Page 3 Thursday November 24...

Страница 6: ...te controller for HRV BRC301B61 2 3 1 4 Remote controller for VRV BRC1C61 1 4 2 3 Remote controller for VRV BRC1A61 62 1 4 Remote controller for HRV BRC301B61 2 3 1 Remote controller for VRV BRC1C61 1 3 2 1 3 2 Remote controller for VRV BRC1A61 62 4 5 6 7 00_CV_3P034927 5J_Illust fm Page 4 Thursday November 24 2005 3 46 PM ...

Страница 7: ... 5 8 9 10 00_CV_3P034927 5J_Illust fm Page 5 Thursday November 24 2005 3 46 PM ...

Страница 8: ...dren animals and plants may result Neither place a flammable spray bottle near the HRV unit or indoor intake and outlet grills nor perform spraying Doing so may result in a fire Turn off the power when the unit is not to be used for long periods of time Otherwise the unit may get hot or catch on fire due to dust accumulation Do not block the intake or outlet grills If the fan does not blow air thr...

Страница 9: ...d the humidity of the installation location is within the usage range not exceed the limit Do not install in cold storage or other locations with low tem peratures or near heated pools This may cause fires or short circuits Install the two outdoor ducts with down slope to pre vent rainwater from entering the unit If this is not done completely water may enter the building damaging furniture and ca...

Страница 10: ...tart It may be displayed when the combined air conditioner is in heating mode 14 Timer mode start stop button Refer to the chapter Operation procedure Programming start and stop of the system with timer 3 2 15 Timer on off button Refer to the chapter Operation procedure Programming start and stop of the system with timer 3 2 16 Inspection test operation button Pressed during inspection or test run...

Страница 11: ... be started and stopped using the Cetralized controller or the indoor and the HRV remote controllers During the indication of centralized control appears on the display the ON OFF and timer operation may not be possible with the HRV remote controllers Other operations can be performed using the HRV remote con trollers Refer to the section 3 2 3 3 3 OPERATION PROCEDURE 3 1 INDEPENDENT COMBINED OPER...

Страница 12: ... connection system Independent duct system The HRV unit cannot be operated independently when the air conditioner is connected to the HRV unit via a duct When using the HRV unit set the air conditioner to fan mode on weak fan strength Each time you press the operation selection button the operation mode display will change as shown in the figure below Example 1 In case of the remote controller BRC...

Страница 13: ...he remaining time For cancelling the timer operation push the timer on off button once again The indication disappears NOTE When setting the timer off and on at the same time repeat the above procedure from to once again DETAIL EXPLANATION When you want to stop operation after a desired time Example Set the time to 8 will display Stops operation 8 hours after the reservation is complete The progra...

Страница 14: ...t gloves may cause injury Watch your step Use caution as this requires working in high places Do not use benzene or thinner to clean the outside surfaces of the air conditioner This may cause cracks discoloration or machine trouble 4 1 HOW TO CLEAN THE AIR FILTER Clean the air filter when the display shows TIME TO CLEAN AIR FILTER It will display that it will operate for a set amount of time CLEAN...

Страница 15: ...move dust and foreign objects on the surface of the heat exchange element Refer to figure 10 Use the vacuum cleaner equipped with a brush on the tip of the suction nozzle Lightly contact the brush on the surface of the heat exchange element when cleaning Do not crush the heat exchange element while clean ing CAUTION During Operation Do not clean touching strongly with a vacuum cleaner This may cru...

Страница 16: ...ion has occurred with a combined air conditioner or outdoor unit See the operation manuals included with the air conditioners or outdoor units for details 5 3 IF THE SYSTEM DOES NOT PROPERLY OPERATE EXCEPT FOR THE ABOVE MENTIONED CASE AND NONE OF THE ABOVE MENTIONED MALFUNCTIONS IS EVIDENT INVESTIGATE THE SYSTEM ACCORDING TO THE FOLLOWING PROCEDURES 1 The unit does not operate at all Check if ther...

Страница 17: ...ur dealer Do not remove or reinstall the unit by yourself Incomplete installation may cause a water leakage electric shock and fire Contact your dealer When asking your dealer to repair inform related staff of the details as follows Shipping date and installation date Malfunction Inform the staff of the defective details Malfunction code being displayed on the remote controller Name address teleph...

Страница 18: ...EM03A029 0511 3P034927 5J FS HT 00_CV_3P034927 5J fm Page 4 Saturday November 19 2005 4 42 PM ...

Отзывы: