Supplementary Explanation
SiE71-202
54
Supplementary Explanation
1. Supplementary Explanation
1.1
Field Setting, Service Mode Operation
1.1.1
Field Setting
Initial setting (mode
Nos. 17, 27, 18, 28)
Step 1
With equipment in normal mode, press the
button for more than 4 seconds to enter field
setting mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select desired mode No.
Step 3
To setting heat recovery ventilation units by group, press
button and select desired
unit No.
Step 4
Press
button to select desired setting switch No.
Step 5
Press
button to select desired setting position No.
Step 6
Press
button to enter settings.
Step 7
Press
button to return to normal mode.
4
3
6
1, 7
5
2
Unit No.
Mode No.
Setting position No.
Field setting mode
Setting switch No.
(HL039)
Содержание VAM 1000FAVE
Страница 5: ...SiE71 202 iv Table of Contents ...
Страница 10: ...SiE71 202 General Constructions 1 Part 1 General Constructions 1 General Constructions 2 1 1 Explanation 2 ...
Страница 13: ...General Constructions SiE71 202 4 General Constructions ...
Страница 14: ...SiE71 202 Product Specification 5 Part 2 Product Specification 1 Product Specification 6 1 1 Specification 6 ...
Страница 37: ...Control Functions SiE71 202 28 Control Functions ...
Страница 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Страница 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Страница 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Страница 77: ...Appendix SiE71 202 68 Appendix ...
Страница 81: ...SiE71 202 iv Index ...