Table 5: Performance Data of LRMIFS0600AXY1 (R448A/ R449A) 

MODEL 

SPEED, rps 

  Te          

Ta 

  

-20 

-15 

-10 

-5 

LRMIFS0600AXY1 

30 

27 

CC 

2937 

4130 

5324 

6517 

7710 

8903 

  

30 

27 

PC 

1706 

1749 

1793 

1836 

1880 

1924 

  

30 

27 

COP 

1.72 

2.36 

2.97 

3.55 

4.10 

4.63 

  

30 

32 

CC 

2827 

3897 

4966 

6036 

7105 

8175 

  

30 

32 

PC 

1770 

1860 

1950 

2040 

2130 

2220 

  

30 

32 

COP 

1.60 

2.09 

2.55 

2.96 

3.34 

3.68 

  

30 

35 

CC 

2761 

3756 

4752 

5747 

6742 

7737 

  

30 

35 

PC 

1810 

1928 

2045 

2163 

2280 

2397 

  

30 

35 

COP 

1.53 

1.95 

2.32 

2.66 

2.96 

3.23 

  

30 

38 

CC 

2695 

3616 

4537 

5458 

6379 

7300 

  

30 

38 

PC 

1850 

1995 

2140 

2285 

2430 

2575 

  

30 

38 

COP 

1.46 

1.81 

2.12 

2.39 

2.63 

2.83 

  

30 

43 

CC 

2585 

3382 

4180 

4977 

5774 

6571 

  

30 

43 

PC 

1915 

2106 

2297 

2489 

2680 

2871 

  

30 

43 

COP 

1.35 

1.61 

1.82 

2.00 

2.15 

2.29 

  

60 

27 

CC 

5004 

7134 

9263 

11393 

13523 

15653 

  

60 

27 

PC 

3103 

3347 

3592 

3836 

4080 

4324 

  

60 

27 

COP 

1.61 

2.13 

2.58 

2.97 

3.31 

3.62 

  

60 

32 

CC 

4787 

6694 

8600 

10507 

12413 

14320 

  

60 

32 

PC 

3270 

3560 

3850 

4140 

4430 

4720 

  

60 

32 

COP 

1.46 

1.88 

2.23 

2.54 

2.80 

3.03 

  

60 

35 

CC 

4805 

6540 

8276 

10011 

11747 

13483 

  

60 

35 

PC 

3463 

3758 

4052 

4346 

4640 

4934 

  

60 

35 

COP 

1.39 

1.74 

2.04 

2.30 

2.53 

2.73 

  

60 

38 

CC 

4781 

6356 

7931 

9506 

11081 

12679 

  

60 

38 

PC 

3630 

3935 

4240 

4545 

4850 

5155 

  

60 

38 

COP 

1.32 

1.62 

1.87 

2.09 

2.28 

2.46 

  

60 

43 

CC 

4606 

5947 

7289 

8630 

  

  

  

60 

43 

PC 

3824 

4168 

4512 

4856 

  

  

  

60 

43 

COP 

1.20 

1.43 

1.62 

1.78 

  

  

  

80 

27 

CC 

8479 

10114 

11749 

13383 

15018 

16653 

  

80 

27 

PC 

4402 

4779 

5156 

5533 

5910 

6287 

  

80 

27 

COP 

1.93 

2.12 

2.28 

2.42 

2.54 

2.65 

  

80 

32 

CC 

7723 

9386 

11049 

12712 

14375 

16038 

  

80 

32 

PC 

4540 

4995 

5450 

5905 

6360 

6815 

  

80 

32 

COP 

1.70 

1.88 

2.03 

2.15 

2.26 

2.35 

  

80 

35 

CC 

7153 

8862 

10571 

12280 

13989 

15698 

  

80 

35 

PC 

4690 

5175 

5660 

6145 

6630 

7115 

  

80 

35 

COP 

1.53 

1.71 

1.87 

2.00 

2.11 

2.21 

  

80 

38 

CC 

6615 

8362 

10109 

11856 

13603 

  

  

80 

38 

PC 

4820 

5340 

5860 

6380 

6900 

  

  

80 

38 

COP 

1.37 

1.57 

1.73 

1.86 

1.97 

  

  

80 

43 

CC 

5826 

7609 

9393 

11176 

  

  

  

80 

43 

PC 

4977 

5570 

6163 

6757 

  

  

  

80 

43 

COP 

1.17 

1.37 

1.52 

1.65 

  

  

  

100 

27 

CC 

9980 

11765 

13549 

15334 

  

  

  

100 

27 

PC 

5932 

6342 

6753 

7164 

  

  

  

100 

27 

COP 

1.68 

1.85 

2.01 

2.14 

  

  

  

100 

32 

CC 

9037 

11117 

13196 

15276 

  

  

  

100 

32 

PC 

6190 

6710 

7230 

7750 

  

  

  

100 

32 

COP 

1.46 

1.66 

1.83 

1.97 

  

  

  

100 

35 

CC 

8471 

10728 

12984 

15241 

  

  

  

100 

35 

PC 

6345 

6904 

7462 

8021 

  

  

  

100 

35 

COP 

1.33 

1.55 

1.74 

1.90 

  

  

  

100 

38 

CC 

7905 

10339 

12773 

15207 

  

  

  

100 

38 

PC 

6500 

7105 

7710 

8315 

  

  

  

100 

38 

COP 

1.22 

1.46 

1.66 

1.83 

  

  

  

100 

43 

CC 

6961 

9690 

  

  

  

  

  

100 

43 

PC 

6758 

7465 

  

  

  

  

  

100 

43 

COP 

1.03 

1.30 

  

  

  

  

Содержание V3

Страница 1: ...ure Variable Capacity Scan below QR code to download latest manual from Website https drm daikinmalaysia com download V3 INVERTER SCROLL AIR COOLED SPLIT COMMERCIAL CONDENSING UNIT TECHNICAL MANUAL NO...

Страница 2: ...to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced...

Страница 3: ...D Display Button Functions 15 CONTROLLER HOME SCREEN 15 PASSWORD FOR ACCESSIBILITY LEVEL 15 CHANGING SET POINT 16 REFRIGERANT SELECTION 16 SWITCH UNIT ON OFF BY CONTROLLER 16 COMPRESSOR MODEL SELECTIO...

Страница 4: ...sensors Low pressure switch adjustable default auto reset High pressure safety switch manual reset cartridge type Mains switch for isolation of incoming power supply Manual motor starter for isolatio...

Страница 5: ...I 29 CABLE PRESSURE TRANSDUCER 30 SENSOR TEMPERATURE SUCTION VI 31 SENSOR TEMPERATURE DISCHARGE T 32 SENSOR TEMPERATURE AMBIENT 33 FUSE 34 VALVE SERVICE 35 VALVE DISCHARGE LINE 36 VALVE NON RETURN 37...

Страница 6: ...T CU19 JAN24 1 Page 4 Figure 3 Exploded View of LRMIFS0900AXY1...

Страница 7: ...and Weight Model SEPR 10K SH SPL 10m dB A Overall Dimensions mm Mounting Dimensions mm Dry Weight Gross Weight R448A R449A Width Depth Height Width Depth kgs kgs LRMIFS0300AXY1 3 03 3 03 31 3 1334 54...

Страница 8: ...450 2620 60 38 COP 1 6 1 75 1 92 2 1 2 29 2 48 60 43 CC 2620 3170 3796 4504 5301 6191 60 43 PC 1787 2023 2260 2497 2733 2970 60 43 COP 1 47 1 57 1 68 1 8 1 94 2 08 80 27 CC 4116 4906 5795 6788 7891 91...

Страница 9: ...35 COP 1 39 1 74 2 04 2 30 2 53 2 73 60 38 CC 4781 6356 7931 9506 11081 12679 60 38 PC 3630 3935 4240 4545 4850 5155 60 38 COP 1 32 1 62 1 87 2 09 2 28 2 46 60 43 CC 4606 5947 7289 8630 60 43 PC 3824...

Страница 10: ...6100 6150 6200 6250 60 38 COP 1 03 1 26 1 48 1 87 2 26 2 64 60 43 CC 5817 6741 7664 9925 12186 14446 60 43 PC 6700 6688 6675 6663 6650 6638 60 43 COP 0 87 1 01 1 15 1 49 1 83 2 18 80 27 CC 9718 12601...

Страница 11: ...Table 8 Operating Limit Operating Limits Recommendation Discharge gas temperature 1100C maximum Evaporator outlet superheat Above 6K to avoid liquid flood back Suction gas superheat at compressor inle...

Страница 12: ...units regardless of short term or long term operation The units are not designed to withstand loads or stress from other equipment or personnel Such extraneous loads or stress may cause failure leak i...

Страница 13: ...rap system is fitted Additional oil may be required if piping length exceeds 20m or multiple oil traps are fitted Check the oil level closely during commissioning and add oil as necessary Add oil in s...

Страница 14: ...sting has been completed satisfactorily release the pressure from the system gradually and safely to external atmosphere Evacuation and Charging Moisture prevents proper functioning of the compressor...

Страница 15: ...ital input Safe Torque Off STO on the drive When the STO contact is open the drive stops operating bypassing the software control Phase Sequence for Correct Compression BLDC scroll compressor requires...

Страница 16: ...r R448A Type of refrigerant available for selection R448A R449A R404A Low Pressure Switch Cut In 3barg Differential 2barg Auto Reset To cut off compressor when suction pressure drops below 1barg Softw...

Страница 17: ...to the setting fields in the setting fields confirms the set value and moves to the next parameter PRG Accesses the menu for selecting the group of parameters to be displayed modified access to the pa...

Страница 18: ...type of refrigerant Press ENTER for execution and press DOWN button to move to the next screen 2 Cag02 Select the compressor model Refer compressor nameplate on the unit to ensure correct model is se...

Страница 19: ...atible will be shown Compressor Operation Envelope management The compressor working zone in the software is defined based on the following measurements o Condensing pressure o Evaporation pressure o...

Страница 20: ...ial during start up The BLDC compressor cannot start if the pressure differential is greater than 9 0barg This limit depends on the maximum current delivered by the inverter As soon as the pressure di...

Страница 21: ...communication with the evaporators Serial communication allows information to be exchanged in real time between the controller and the MPXPRO devices AC Fan Speed Modulation One of the AC fans is cont...

Страница 22: ...by holding down on the button ALARM until active alarm is clear is required on the 5th times of this alarm occur in an hour Low pressure setting had been configured in such a way that it is the first...

Страница 23: ...o all evaporators Refrigerant charge by judging the liquid sight glass does not guarantee as 100 correct way To avoid system overcharging which can cause higher energy consumption and low compressor s...

Страница 24: ...27 20 20 20 20 20 20 80 64 52 40 30 22 20 20 20 20 20 70 72 59 46 34 25 20 20 20 20 20 60 82 67 53 40 29 20 20 20 20 20 50 97 78 63 47 34 24 20 20 20 20 40 118 95 76 59 43 29 20 20 20 20 30 97 75 56...

Страница 25: ...quest in case of regulat Probes fault 50 Cag43 BLDC settings Crankcase heater COMP OFF Cag43 BLDC settings Crankcase current 24 Cag43 BLDC settings STO alarm management MAN RESET Cag44 Crankcase heate...

Страница 26: ...A24 Suction pressure probe broken or disconnected Automatic 60 s R1 Related functions disabled ALA25 Suction temperature probe broken or disconnected Automatic 60 s R2 Related functions disabled ALA46...

Страница 27: ...drive Check the power supply voltage 5 Drive overtemperature The temperature inside the drive has exceeded the maximum level allowed Check that the quantity and flow of cooling air are regular Check t...

Страница 28: ...compressed air inert gas or a low pressure sprayer utilizing clean water A suitable chemical coil cleaner may be used as required Accumulations of dirt on the condenser face can be removed with a soft...

Страница 29: ...tor using the cable supplied with the power supply coming from the controller Figure 20 pCO Smart Key Appendix Table 20 Tightening Torque Model Tightening Torque Nm Compressor Mounting Main Cap Servic...

Страница 30: ...T CU19 JAN24 1 Page 28 Figure 21 Outline Drawing LRMIFS0300AXY1 LRMIFS0600AXY1 Figure 22 Outline Drawing LRMIFS0900AXY1...

Страница 31: ...T CU19 JAN24 1 Page 29 Figure 23 Wiring Diagram LRMIFS0300AXY1...

Страница 32: ...T CU19 JAN24 1 Page 30 Figure 24 Wiring Diagram LRMIFS0600AXY1...

Страница 33: ...PRESSURE SWITCH 3 15A A1P MAIN CONTROLLER N L N L IN OUT BRN GRN GRY GRY GRN YLW BLU BRN BLK M BLU BRN C2 BRN 380 415V 3N 50Hz L1L2L3PEU V WPE 1 2 3 4 5 6 7 8 910 POWER GRN YLW BRN GRY BLK BRN GRY BL...

Страница 34: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Отзывы: