UATYQ*Y1

Packaged Rooftop

4P522681-1B

 

 the mask displays the working hours of compressors 3 and 4.

2.10 Alarms

When an alarm is triggered, the red "Alarm" key is on and the alarm digital output is activated.
By pressing the "Alarm" key, the last alarm is displayed; the other active alarms can be scrolled with arrow keys.

This is an example of an alarm mask:

Each alarm is identified by a code “ALxx” and the alarm cause is described in the mask. To reset an active alarm, 

press and hold for at least 2 seconds the "Alarm" key; if the alarm has been successfully reset, the alarm mask 

disappears and, if no other alarms are active, the red "Alarm" key is switched OFF. An alarm can be reset only if the 

condition that has activated the alarm is not present anymore.

The manual reset of an alarm must be done only after checking the alarm cause and solving the 

problem that has activated the alarm.
The improper reset of an alarm can cause serious damages to the unit or to its components.

On alarm history menu, last 150 alarms are stored. When the memory is full and another alarm is activated, the oldest 

alarm is overwritten.
In the following, the full alarm list is reported with the main possible causes, some troubleshooting hints, the reset 

mode, the action on the unit and on its components.

The alarm reset mode is reported on the “RESET” column:

• 

A = automatic: when the alarm condition disappears, the alarm is automatically reset;

• 

AC = automatic controlled: the alarm is automatically reset for a limited number of attempts in a certain time, after 

that the reset becomes manual;

• 

M = manual reset from display or from supervisor: the alarm must be manually reset by display as described 

above or by the supervisor reset variable; for each alarm with manual reset, the reset day and time are stored on 

the alarm history.

In the “OFF UNIT” column, it is reported if the alarm stops the whole unit or not:

• 

Yes = the alarm stops the unit;

• 

No = the alarm does not stop the unit, but only the concerned devices

CODE

DESCRIPTION

MAIN CAUSES

CHECKS AND TROUBLESHOOTING RESET UNIT 

OFF

ITEMS OFF

AL01

Overload 

Compressor 1

Intervention of the thermal 

protection compressor 1

Check working conditions.

M

No

Compressor 1

Check cabling, terminals and circuit 

breaker of the motor.

Check adsorbed current.

Check compressor discharge 

temperature.

AL02

Overload 

Compressor 2

Intervention of the thermal 

protection compressor 2

Check working conditions.

M

No

Compressor 2

Check cabling, terminals and circuit 

breaker of the motor.

Check adsorbed current.

Check compressor discharge 

temperature.

Содержание UATYQ-ABAY1

Страница 1: ...1 UATYQ115ABAY1 UATYQ20AFC2Y1 UATYQ25AFC2Y1 UATYQ30AFC2Y1 UATYQ45AFC2Y1 UATYQ50AFC2Y1 UATYQ55AFC2Y1 UATYQ65AFC2Y1 UATYQ75AFC2Y1 UATYQ90AFC2Y1 UATYQ110AFC2Y1 UATYQ115AFC2Y1 UATYQ20AFC3Y1 UATYQ25AFC3Y1...

Страница 2: ......

Страница 3: ...Main mask and menu 6 2 3 Switching ON OFF he unit from keyboard 7 2 4 Temperature and air flow setpoint adjust 7 2 5 Clock menu and time slots setting 8 2 5 1 Time slots programming examples 9 2 6 Sto...

Страница 4: ...e menu and to set the parameters The key functions are described in the following This key called up arrow allows to scroll up the masks and to modify the value of each mask field increasing it This k...

Страница 5: ...password protected or completely password protected Pressing the key from any mask the following menu loop is displayed With arrow keys it is possible to scroll the menu the selected one is highlight...

Страница 6: ...ht to display the unit working mode the time slots activation the dehumidification activation not available the setpoint compensation activation where enabled to display if the unit is in defrost in f...

Страница 7: ...starting up systems does not give its consent the unit will not start running 2 4 Temperature and air flow setpoint adjust select Setpoint menu Enter From S0 mask the indoor temperature setpoint in s...

Страница 8: ...date can be set from this mask while the day is automatically updated to enable and set time slots input the Clock menu password and press the key the factory Clock menu password is 0001 from this mas...

Страница 9: ...ng examples To better explain the time slots programming two examples are reported in the following Example n 1 The unit has to operate every day from 07 00 to 20 00 with summer setpoint 26 0 C and wi...

Страница 10: ...F from 19 30 to 07 30 and the unit has to be completely switched OFF on Saturday and Sunday Masks K2 to K7 have to be set as follows In case the Unit OFF by time slot function is enabled in mask K2 th...

Страница 11: ...air temperature rises above the summer setpoint while the changeover from summer mode to winter mode is done automatically when the indoor air temperature falls below the winter setpoint In any case t...

Страница 12: ...emperatures internal and external the mask displays the supply air temperature the mask displays circuit 1 and 2 refrigerant pressures The mask displays the CO2 or VOC concentration read by the air qu...

Страница 13: ...opening percentage of the recirculation damper if present the mask displays the running percentage of external fans of circuit 1 and 2 the mask displays the running percentage of delivery and return f...

Страница 14: ...this mask the control language can be changed choosing from those available Press Enter change the language the mask displays the following unit data serial number factory testing date and factory te...

Страница 15: ...e following the full alarm list is reported with the main possible causes some troubleshooting hints the reset mode the action on the unit and on its components The alarm reset mode is reported on the...

Страница 16: ...reshold exceeded Indoor temperature is lower than the min value set Check working conditions A 2 No None AL08 Low pressure Circuit 1 in summer Low pressure alarm circuit 1 from the low pressure switch...

Страница 17: ...t point is lower than winter set point or winter set point is higher than summer set point and automatic changeover is enabled Check for the correct temperature set point cooling and heating modes A Y...

Страница 18: ...terminals Check correct functioning of the analogic input of the main board AL27 B8 probe broken or disconnected The reading of the probe B8 Outdoor air temperature exceeds the range Check working co...

Страница 19: ...ntion value cooling mode Evaporation pressure circuit 2 is lower than prevention value heating mode Check working conditions A 2 No One compressor of circuit 2 Check condensing pressure Check condensi...

Страница 20: ...of cooling circuit 2 in cooling summer mode from pressure transducer The attempt x of the maximum number y of attempts is displayed when the maximum number of attempts is reached the alarm reset beco...

Страница 21: ...eating winter mode is lower than the low pressure prevention value Check working conditions A 2 No A compressor of circuit 2 Check evaporating pressure Check evaporating fans and coil Check evaporatin...

Страница 22: ......

Страница 23: ......

Страница 24: ...Copyright 2019 Daikin 4P522681 1B 2019 05 CM_DKN_0001_Rooftop_EN_06 05 2019_rev02...

Отзывы: