SiEN18-622
Field Setting
Test Operation
153
Caution
DIP switch Setting after changing the main PCB(A1P) to spare parts PCB
When you change the main PCB(A1P) to spare parts PCB, please carry out the following setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adapter
1
2
3
C
a
p
a
city Cl
ass
4 (112)
5 (140)
6 (160)
CAPACITY
S
ETTING ADAPTER (for 100/J112)
CAPACITY
S
ETTING ADAPTER (for 125/J140)
CAPACITY
S
ETTING ADAPTER (for 140/J160)
Po
s
ition of Att
a
ching the C
a
p
a
city
S
etting Ad
a
pter
Note
X51A
Po
s
ition of Att
a
ching the
C
a
p
a
city
S
etting Ad
a
pter
Содержание Super Multi Plus E-Series
Страница 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump...
Страница 30: ...SiEN18 622 Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Cooling Only 18 1 2 Heat Pump 34...
Страница 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit...
Страница 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function...
Страница 204: ...Instruction SiEN18 622 192 System Configuration FTK X S 50 60 71 F Indoor Unit 1 2 4 3 10 11 9 7 8 15 12 13 14 16 6 5...
Страница 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300...
Страница 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting...
Страница 446: ...Wiring Diagrams SiEN18 622 434 Appendix...
Страница 452: ...SiEN18 622 vi Index...