SiBE05-722EE
Field Settings
Trial Operation and Field Settings
121
3.3
Jumper and Switch Settings
Indoor Unit
For the location of the jumper and the switch, refer to page 19.
Outdoor Unit
For the location of the jumper, refer to page
,
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Function
Jumper
When connected
(factory setting)
When cut
Fan speed setting when
compressor stops for
thermostat OFF. (effective only
in cooling operation)
JB
Fan speed setting ;
Remote controller
setting
The fan stops.
Power failure recovery function
JC
Auto-restart
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
Function
Switch
FLOOR
(factory setting)
CEILING
Installation style changeover
SW2
When installed as
the floor mounted
type
When installed as the ceiling
suspended type
Function
Jumper
Jumper: connected
(factory setting)
Jumper: cut
Improvement
of defrost
performance
RK(X)S25/35E2V1B
→
J5
RK(X)S25/35G2V1B
→
J5
RK(X)S25/35G2V1B9
→
J5
RXS25/35J2V1B
→
J5
RXS25K3V1B
→
J5
RXS35K2V1B
→
J5
RXS25/35L2V1B
→
J5
Standard control
Reinforced control (Ex:
The frequency increases,
the duration time of
defrost lengthens.)