2
|
Components
Service manual
66
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
Is the DC fan motor shaft friction
normal?
Action
No
Replace the DC fan motor assembly, see
To perform an electrical check of the DC fan motor assembly
1
First perform a mechanical check of the DC fan motor assembly, see
2
Measure the resistance between the pins 1-2, 1-3, and 2-3 of the DC fan
motor connector. All measurements MUST be 15~20 Ω.
DC fan motor resistance measurements
are correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the DC fan motor, see
2.5.2 Repair procedures
To remove the DC fan motor assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Pull the clip and remove the heat exchanger thermistor from its holder.
2
Remove the screws to disconnect the grounding wires from the heat
exchanger.
a a
b
c
d
e
a
Grouding wire screw
b
Heat exchanger thermistor
c
Indoor unit PCB
d
Switch box screw
e
Switch box
3
Disconnect the connectors of the indoor unit fan motor, the swing flap motor
and the swing raster motor (if equipped) from the indoor unit PCB.
4
Remove the screw and remove the switch box from the indoor unit.
Содержание Split Comfora R32