SiUS281117
Field Setting from Remote Controller
74
Field Setting
2.3
Setting Contents and Code No. for Indoor Units
: Factory setting
Note:
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
4. “
88
” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
5. Only for FTQ
6.
7. For FTQ: Factory setting is “02”.
Mode No.
First Code
No.
Description of Setting
Second Code No.
01
02
03
04
10
(20)
0
Filter cleaning sign time
Light
Heavy
—
—
0
5
Filter dirt
Light
Heavy
—
—
1
Filter type
Long life filter
Ultra long life
filter
—
—
1
5
Filter cleaning sign time (Light/Heavy)
2,500/1,250
10,000/5,000
—
—
2
Remote controller thermistor
Use
Not use
—
—
2
5
Remote sensor and remote controller thermistor
Both
Remote
thermistor
Remote
controller
thermistor
—
3
Filter sign display
ON
OFF
—
—
7
4-step thermostat processing
11
(21)
3
5
Electric heater setting
Heat Pump
lockout mode
—
Auxiliary
electric heater
+ Heat Pump
lockout mode
—
5
5
Electric heater step setting
With heater
—
Without
heater
—
12
(22)
0
Optional accessories output selection (Field
selection of output for adaptor for wiring)
Indoor Unit
turned ON by
thermostat
—
Operation
output
Error output
1
ON/OFF Input from outside (Set when ON/OFF is
to be controlled from outside.)
Forced Off
ON/OFF
control
External
protection
device input
—
2
Thermostat differential changeover (Set when
remote sensor is to be used.)
2 °F
1 °F
7
—
—
3
Set fan speed when thermostat OFF
LL
Set fan speed
—
—
5
Power failure automatic reset (Auto restart)
No equipped
Equipped
—
—
13
(23)
0
Airflow adjustment ceiling height
N
H
S
—
1
Airflow direction
F
(4 directions)
T
(3 directions)
W
(2 directions)
—
4
Field setting airflow position setting
Draft
prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure selection
Standard
High static
pressure
—
—
14
(24)
4
5
Setting of humidifier / air purifier fan tap
Remote
controller
setting
H tap
—
—
5
5
Humidifier residual operation time
30 sec.
60 sec.
120 sec.
—
Symbol
6
01
02
03
04
05
06
Ttson
-7.2°F
-6.3°F
-5.4°F
-4.5°F
-3.6°F
-2.7°F
Ttsoff
-3.6°F
-2.7°F
-1.8°F
-0.9°F
0°F
-0.9°F
Set temperature
<Ttsoff>
<Ttsoff>
Thermostat
ON
Thermostat
OFF