Method of Field Set (Reset after Maintenance Inspection/Repair)
Si-71A
22
Explanation of Field Set
1.4
Local Setting Mode No.
Example
To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table
Notes:
1. Setting is made in all units in a group. To set for individual indoor units or to check the setting, use the
mode Nos. (with “2” in upper digit) in parentheses ( ).
2. The setting position No. is set to “01” at the factory, except for the following cases in which “02” is set.
„
Setting of air flow direction adjustment range
„
Automatic restart after power outage.
„
Remote control thermostat
„
Filter sign indication (only for ceiling-mounted duct type)
3. When installing Sky Air simultaneous operation multi-unit, set to either “twin” or “triple.”
Only when the factory setting is changed, it is necessary to make a setting using a remote controller.
4. For further details, see the installation instruction.
5. Since drafts may result, carefully select the installation location.
6. When power returns, units resume the settings made before the power outage.
Mode
No.
Note 1
Setting
Switch
No.
Setting Description
Setting Position No. *Note 2
01
02
03
10(20)
0
Filter contamination - heavy / light
(Setting of operating hours for filter
sign indication) (Change setting
when reducing filter sign indication
time to half due to quick soiling of
filter)
Urtra-Long-
Life Type
Light
Approx.
10,000
hours
Heavy
Approx.
5,000
hours
—
Long-Life
Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard
Type
Approx.
200 hours
Approx.
100 hours
1
Long-life filter type (Setting of filter sign indication
time)
(Change setting when Urtra-long-life filter is
installed)
Long-Life Filter
Urtra-Long-Life Filter
(1)
Setting Description
Urtra-Long-Life Filter
(2)
3
Estimation of filter operating hour
(Change setting when filter sign indication is not
used)
ON
OFF
—
11(21)
0
No. of Sky Air indoor units connected for
simultaneous ON-OFF multi system
(Change setting when simultaneous operation
multi system is used) *Note 3
Pair
Twin
Triple
1
Simultaneous operation multi-unit individual
setting
Unified
Individual
—
2
Indoor unit fan OFF when cooling/heating is OFF
—
Fan OFF
—
12(22)
3
Change to set fan speed when heater thermostat
is OFF *Note 5
Fan Speed LL
Set Fan Speed
—
5
Automatic restart after power outage reset
*Note 6
OFF
ON
—
13(23)
0
High
Ceiling
Ceiling-mounted built-in multi-flow
cassette type, Ceiling suspended
cassette type
N
H
S
Ceiling-suspended type, wall-mounted
typ
2.7 m or Lower
2.7~3.5 m
—
Fan speed increase (wall-mounted type)
Standard
Slight Increase
Normal Increase
1
Air flow direction selection (Change setting when
blocking kit is installed) *Note 4
F
T
W
3
Air flow direction adjustment (Change setting
when decorative air outlet panel is installed)
Installed
Not Installed
—
4
Setting of air flow direction adjustment range
Upward
Standard
Downward
5
On-site fan speed change by air outlet (When
using phase control)
Standard
Option 1
Option 2
6
External static pressure setting (To be set
according to connected duct resistance) (High
ceiling setting in the case of FHYK)
Standard (Standard)
High Static Pressure
(High Ceiling Setting)
Low Static Pressure
Содержание Skyair FHC35K
Страница 7: ...Si 71A vi Table of Contents...
Страница 19: ...Present Model s Functions Si 71A 8 Improved Points and Functions...
Страница 22: ...Si 71A Wired Remote Controller Remote Controller Operation 11...
Страница 24: ...Si 71A Wireless Remote Controller Remote Controller Operation 13...
Страница 26: ...Si 71A Wireless Remote Controller Remote Controller Operation 15...
Страница 27: ...Wireless Remote Controller Si 71A 16 Remote Controller Operation...
Страница 42: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 31 FHYC35 FHYC125KVE V1C...
Страница 43: ...Settings Concerning Maintenance Si 71A 32 Explanation of Field Set FHB35 FHB60FJV1 FV1...
Страница 44: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 33 FHYB35 FHYB71F...
Страница 45: ...Settings Concerning Maintenance Si 71A 34 Explanation of Field Set FHK35 FHK60FJV1 FV1...
Страница 46: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 35 FHYK35 FHYK71FJV1 FV1...
Страница 47: ...Settings Concerning Maintenance Si 71A 36 Explanation of Field Set FAY71 FAY100FVE...
Страница 48: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 37 FAY71 FAY100FAVE...
Страница 49: ...Settings Concerning Maintenance Si 71A 38 Explanation of Field Set FVY L...
Страница 50: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 39 FUY71 FUY125FJ...
Страница 52: ...Si 71A Settings Concerning Maintenance Explanation of Field Set 41 RY140K...
Страница 106: ...Si 71A Procedure of Self Diagnosis by Remote Controller Troubleshooting 95...
Страница 135: ...Troubleshooting by Remote Controller Display LED Display Si 71A 124 Troubleshooting...
Страница 201: ...For R Y 71K Si 71A 190 Removal Procedure...
Страница 205: ...Piping Diagrams Si 71A 194 Appendix FUY100FJ R100K FUY125FJ R125K R71K R100K R125K Twin System DU428 6141A 3D018539...
Страница 206: ...Si 71A Piping Diagrams Appendix 195 R140KY1 Twin System R140KTAL Twin System 3D000191 3D000222...
Страница 207: ...Piping Diagrams Si 71A 196 Appendix R140KY1 Triple System R140KTAL Triple System 3D000192 3D000224...
Страница 208: ...Si 71A Piping Diagrams Appendix 197 FHYC35K FHYK35FJ FHYB35F FHY35F RY35FV1A FHYC50K FHYK45FJ FHYB45F FHY45F RY50GV1A...
Страница 211: ...Piping Diagrams Si 71A 200 Appendix FUY100FJ RY100K FUY125FJ RY125K RY71K RY100K RY125K Twin System DU428 6140 3D018540...
Страница 212: ...Si 71A Piping Diagrams Appendix 201 RY140KY1 Twin System RY140KTAL Twin System 3D000187 3D000216...
Страница 213: ...Piping Diagrams Si 71A 202 Appendix RY140KY1 Triple System RY140KTAL Triple System 3D000188 3D000217...
Страница 214: ...Si 71A Wiring Diagram Appendix 203 2 Wiring Diagram 2 1 Indoor Unit FHC35KVE FHC50KVE FHC60KVE...
Страница 215: ...Wiring Diagram Si 71A 204 Appendix FHK35FV1 FHK71FV1 DU427 5405...
Страница 216: ...Si 71A Wiring Diagram Appendix 205 FHB35FV1 FHB60FV1 DU423 5175A...
Страница 217: ...Wiring Diagram Si 71A 206 Appendix FH35FVE FH125FVE DU423 5172B...
Страница 219: ...Wiring Diagram Si 71A 208 Appendix FHYK35FJV1 FHYK70FJV1 DU423 5174...
Страница 220: ...Si 71A Wiring Diagram Appendix 209 FHYB35FV1 FHYB71FV1 DU423 5173A...
Страница 221: ...Wiring Diagram Si 71A 210 Appendix FHYB100FV1 FHYB125FV1 DU428 5353A...
Страница 222: ...Si 71A Wiring Diagram Appendix 211 FHY35FVE FHY125FVE DU423 5172B...
Страница 223: ...Wiring Diagram Si 71A 212 Appendix FAY71F A VE FAY100F A VE DU427 5410D...
Страница 224: ...Si 71A Wiring Diagram Appendix 213 FVY71FV1 FVY125FV1 DU427 5403...
Страница 225: ...Wiring Diagram Si 71A 214 Appendix FUY71FJV1 FUY100FJV1 FUY125FJV1 3D013404A...
Страница 226: ...Si 71A Wiring Diagram Appendix 215 FVY71LVE FVY100LVE FVY125LVE 3D013540A...
Страница 227: ...Wiring Diagram Si 71A 216 Appendix 2 2 Outdoor Units 50Hz R35GV1 R50GV1 DW523 555 1A...
Страница 228: ...Si 71A Wiring Diagram Appendix 217 R60GV1 R71KV1 DU427 5399C...
Страница 229: ...Wiring Diagram Si 71A 218 Appendix R100KV1 R71KY1 DU428 5349E DU427 5401B...
Страница 230: ...Si 71A Wiring Diagram Appendix 219 R100KY1 R125KY1 R140KY1 DU428 5351D...
Страница 231: ...Wiring Diagram Si 71A 220 Appendix 2 3 Outdoor Units 60Hz R50GVAL R60GVAL 3D005750...
Страница 232: ...Si 71A Wiring Diagram Appendix 221 R71KVAL R100KVAL 3D014723A 3D014724A...
Страница 234: ...Si 71A Wiring Diagram Appendix 223 2 4 Outdoor Unit HeaT Pump RY35FV1A RY50GV1A 3D001431A 3D000794...
Страница 235: ...Wiring Diagram Si 71A 224 Appendix RY60GV1A RY71KV1...
Страница 236: ...Si 71A Wiring Diagram Appendix 225 RY71KY1 RY100KY1 RY125KY1 DU427 5397B DU428 5347D...
Страница 237: ...Wiring Diagram Si 71A 226 Appendix RY140KY1 RY140KTAL 3D000102A 3D000104A...
Страница 241: ...Si 71A iv Index...