This equipment can be installed with a Ground-Fault
Circuit Interrupter (GFCI). Although this is a recog-
nized measure for additional protection, with the
grounding system in North America, a dedicated GFCI
is not necessary.
•
When installing or relocating the system, keep the
refrigerant circuit free from substances other than the
specified refrigerant (R410A) such as air. Any pres
-
ence of air or other foreign substance in the refriger-
ant circuit can cause an abnormal pressure rise or
rupture, resulting in injury.
•
Do not change the setting of the protection devices. If
the pressure switch, thermal switch, or other protec-
tion device is shorted and operated forcibly, or parts
other than those specified by Daikin are used, fire or
explosion may occur.
CAUTION
• Do not touch the switch with wet fingers. Touching a
switch with wet fingers can cause electric shock.
•
Do not allow children to play on or around the unit to
prevent injury.
•
Do not touch the refrigerant pipes during and imme-
diately after operation as the refrigerant pipes may be
hot or cold, depending on the condition of the refriger-
ant flowing through the refrigerant piping, compres
-
sor, and other refrigerant cycle parts. Your hands may
suffer burns or frostbite if you touch the refrigerant
pipes. To avoid injury, give the pipes time to return
to normal temperature or, if you must touch them, be
sure to wear proper gloves.
• Heat exchanger fins are sharp enough to cut. To avoid
injury, wear glove or cover the fins when working
around them.
•
Install drain piping to proper drainage. Improper drain
piping may result in water leakage and property dam-
age.
•
Insulate piping to prevent condensation.
•
Be careful when transporting the product.
•
Do not turn off the power supply immediately after
stopping operation. Always wait for at least 5 minutes
before turning off the power supply. Otherwise, water
leakage may occur.
•
Do not use a charging cylinder. Using a charging cylin-
der may cause the refrigerant to deteriorate.
• Refrigerant R410A in the system must be kept clean,
dry, and tight.
(a) Clean and Dry -- Foreign materials (including min-
eral oils such as SUNISO oil or moisture) should
be prevented from getting into the system.
(b)
Tight -- R410A does not contain any chlorine, does
not destroy the ozone layer, and does not reduce
the earth’s protection again harmful ultraviolet
radiation. R410A can contribute to the greenhouse
effect if it is released. Therefore take proper mea-
sures to check for the tightness of the refrigerant
piping installation. Read the chapter REFRIGER-
ANT PIPING WORK and follow the procedures.
• Since R410A is a blend, the required additional refrig
-
erant must be charged in its liquid state. If the refriger-
ant is charged in a gaseous state, its composition can
change and the system will not work properly.
• The indoor unit is for R410A. See the catalog for in
-
door models that can be connected. Normal operation
is not possible when connected to other units.
•
Handheld remote controller transmitting distance can
be shorter than expected in rooms with electronic
fluorescent lamps (inverter or rapid start types).
Install the indoor unit far away from fluorescent lamps
as much as possible.
•
Indoor units are for indoor installation only. Outdoor
units can be installed either outdoors or indoors.
•
Do not install the air conditioner in the following loca-
tions:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result
in water leakage.
(b) Where corrosive gas, such as sulfurous acid gas,
is produced.
Corroding copper pipes or soldered parts may
result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation
of the control system and cause the unit to mal-
function.
(d)
Where flammable gas may leak, where there is
carbon fiber, or ignitable dust suspension in the
air, or where volatile flammables such as thinner
or gasoline are handled. Operating the unit in
such conditions can cause a fire.
NOTE
•
Install the power supply and control wires for the
indoor and outdoor units at least 3.5 feet (1.0 m) away
from televisions or radios to prevent image interfer-
ence or noise. Depending on the radio waves, a dis-
tance of 3.5 feet (1.0 m) may not be sufficient to elimi
-
nate the noise.
•
Dismantling the unit, treatment of the refrigerant, oil
and additional parts must be done in accordance with
the relevant local, state, and national regulations.
•
Do not use the following tools that are used with con-
ventional refrigerants: gauge manifold, charge hose,
gas leak detector, reverse flow check valve, refriger
-
ant charge base, vacuum gauge, or refrigerant recov-
ery equipment.
•
If the conventional refrigerant and refrigerator oil are
mixed in R410A, the refrigerant may deteriorate.
•
This air conditioner is an appliance that should not be
accessible to the general public.
• As design pressure is 478 psi (3.3 MPa), the wall thick
-
ness of field-installed pipes should be selected in
accordance with the relevant local, state, and national
regulations.