SiUS28-902_a
Troubleshooting by Indication on the Unified ON/OFF Controller
Troubleshooting
158
Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
Check for Power Transistor
Judgment is made through cable check with an analog tester.
(1) Do not touch the energized part (high voltage part) for at least 10 minutes after the power is
turned OFF.
(2) Be sure to touch the ground terminal with a hand to release static electricity from the body
(to prevent the PC board from being damaged).
(3) Also with a tester, take measurements at the following spots and confirm that residual
electric charge of the power transistor is DC 50V or less.
(4) After checking the residual electric charge, remove the connector of the outdoor unit fan
motor. When the outdoor unit fan is rotated by strong headwind, remove the connector of
the outdoor unit fan motor after confirming that the outdoor unit fan has stopped because
electrical energy is stored in the capacitor and there may be a risk of electric shock.
(5) Remove the wire connecting the power transistor and the compressor. Remove it from the
compressor terminal side. During this work, be careful not to deform the Faston terminal at
the end of the connecting wire.
(6) Using an analog tester, measure resistance and fill in the blanks in the following table.
In case of unbalanced resistance for one of the three phases in each table (when the
resistance value is equal to five times or more than the other resistance values), the power
transistor is broken.
In normal cases, each phase shows a similar resistance value.
CHECK 3
Measurement point
Judgement
1 - 4
1M
Ω
or more
2 - 4
100k
Ω
or more
3 - 4
100
Ω
or more
4 - 7
100k
Ω
or more
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
GND
CHECK 4
Tester
Resistance
Tester
Resistance
(+)
(-)
Ω
(+)
(-)
Ω
C+
U
C-
U
∞
C+
V
C-
V
∞
C+
W
C-
W
∞
U
C+
∞
U
C-
V
C+
∞
V
C-
W
C+
∞
W
C-
Electrical
e
qu
ipment
b
ox
O
u
tdoor
u
nit
fan connector
Front face
Gro
u
nd terminal
Resid
u
al
v
oltage
meas
u
rement spot
U
Red White Blue
V
W
U
V
W
Comp.
M1C
Outdoor Unit
PC board
C+
C-
Содержание SkyAir FCQ18PVJU
Страница 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Страница 11: ...SiUS28 902_a Specifications 4 Part 2 Specifications 1 Specifications 5 1 1 FCQ 5 1 2 FHQ 6 1 3 FAQ 7...
Страница 20: ...Refrigerant Circuit SiUS28 902_a 13 Refrigerant Circuit C 3D062238B E T S J G O D N A P M S1NPL S1NPH S1PH...
Страница 44: ...Other Control SiUS28 902_a 37 Function...
Страница 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Страница 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...