18 Troubleshooting

Installer and user reference guide

29

FCAHG71~140GVEB
Split system air conditioners
4P482875-1 – 2017.03

▪ Normal  use  without  frequent  starting  and  stopping  of  the  unit.

Depending  on  the  model,  we  recommend  not  starting  and
stopping the machine more than 6 times/hour.

▪ Operation  of  the  unit  is  assumed  to  be  10  hours/day  and

2,500 hours/year.

NOTICE

▪ The  table  indicates  main  components.  Refer  to  your

maintenance and inspection contract for more details.

▪ The  table  indicates  recommended  intervals  of

maintenance cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be  required  sooner.  Recommended  intervals  can  be
used  for  appropriate  maintenance  design  in  terms  of
budgeting 

maintenance 

and 

inspection 

fees.

Depending  on  the  content  of  the  maintenance  and
inspection contract, inspection and maintenance cycles
may in reality be shorter than listed.

17.5.4

Shortened maintenance and replacement
cycles

Shortening of "maintenance cycle" and "replacement cycle" needs to
be considered in following situations:

The unit is used in locations where:

▪ Heat and humidity fluctuate out of the ordinary.

▪ Power fluctuation is high (voltage, frequency, wave distortion, etc.)

(the  unit  cannot  be  used  if  power  fluctuation  is  outside  the
allowable range).

▪ Bumps and vibrations are frequent.

▪ Dust,  salt,  harmful  gas  or  oil  mist  such  as  sulphurous  acid  and

hydrogen sulfide may be present in the air.

▪ The machine is started and stopped frequently or operation time is

long (sites with 24 hour air-conditioning).

Recommended replacement cycle of wear parts

Component

Inspection

cycle

Maintenance cycle

(replacements and/or

repairs)

Air filter

1 year

5 years

High efficiency filter

1 year

Fuse

10 years

Pressure containing parts

In case of corrosion,

contact your local dealer.

NOTICE

▪ The  table  indicates  main  components.  Refer  to  your

maintenance and inspection contract for more details.

▪ The  table  indicates  recommended  intervals  of

replacement cycles. However, in order to keep the unit
operational as long as possible, maintenance work may
be  required  sooner.  Recommended  intervals  can  be
used  for  appropriate  maintenance  design  in  terms  of
budgeting  maintenance  and  inspection  fees.  Contact
your dealer for details.

INFORMATION

Damage due to taking apart or cleaning interiors of units by
anyone  other  than  our  authorised  dealers  may  not  be
included in the warranty.

18

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.

Turn off the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work
well.

Turn off the power.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  not  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check  if  the  air  filter  is  not  clogged  (see

"17.1.1  To  clean  the  air  filter"  on
page 27

).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

Содержание SkyAir FCAHG71GVEB

Страница 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71GVEB FCAHG100GVEB FCAHG125GVEB FCAHG140GVEB...

Страница 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Страница 3: ...wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 20 8 1 Overview Commissioning 20 8 2 Precautions when commis...

Страница 4: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Страница 5: ...s weight and vibration Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive...

Страница 6: ...7 3 6 4 351 3 0 5 74 6 6 27 8 3 0 77 2 6 6 374 3 2 6 54 6 8 29 5 3 2 87 9 6 8 397 3 4 7 38 7 0 31 3 3 4 99 2 7 0 420 3 6 8 27 7 2 33 1 3 6 111 7 2 445 3 8 9 22 7 4 34 9 3 8 124 7 4 470 4 0 10 2 7 6 36...

Страница 7: ...wn Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing cl...

Страница 8: ...e all covers are closed before starting up the unit NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of revers...

Страница 9: ...e Large gas pipe 4 About the units and options 4 1 Overview About the units and options This chapter contains information about Combining outdoor and indoor units Combining the indoor unit with option...

Страница 10: ...ral installation site requirements See the General safety precautions chapter Refrigerant piping requirements length height difference See further in this Preparation chapter INFORMATION The sound pre...

Страница 11: ...orners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Minimum and maximum distance to the floor Minimum 2 5 m to avoid accidental touching...

Страница 12: ...ion This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the in...

Страница 13: ...een the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position A B C a b...

Страница 14: ...tion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks on page 14 4 Install the insulation piece drain pip...

Страница 15: ...to account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 or R410A1 when adding refrigerant Only use installation tools e g manifold gauge s...

Страница 16: ...and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducing valve a b c d e...

Страница 17: ...Terminal b Screw c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of...

Страница 18: ...ollers control 1 indoor unit 1 50 Hz 220 240 V b a e2 e1 c d a Interconnection cable b Power supply cable c Earth leakage circuit breaker d Fuse e1 Main user interface e2 Optional user interface Force...

Страница 19: ...en4 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perf...

Страница 20: ...kers 8 3 Checklist before commissioning Do NOT operate the system before the following checks are OK You read the complete installation instructions as described in the installer reference guide The i...

Страница 21: ...er supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The...

Страница 22: ...l data Installer and user reference guide 22 FCAHG71 140GVEB Split system air conditioners 4P482875 1 2017 03 11 1 Piping diagram Indoor unit b a c a Liquid pipe connection b Gas pipe connection c Hea...

Страница 23: ...L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH F...

Страница 24: ...ech Republic A B C D E FCAHG125 7 83 4 27 13 50 0 25 61 FCAHG140 8 68 4 72 15 50 0 25 61 13 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some p...

Страница 25: ...erant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the display Hot start In order to prevent...

Страница 26: ...keep the temperature setting at a moderate level Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Turn off the main...

Страница 27: ...loration and deformation 1 Open the suction grille 1 2 Remove the suction grille 45 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral det...

Страница 28: ...es service and warranty 17 5 1 Warranty period This product includes a warranty card that was filled in by the dealer at the time of installation The completed card has to be checked by the customer a...

Страница 29: ...to taking apart or cleaning interiors of units by anyone other than our authorised dealers may not be included in the warranty 18 Troubleshooting If one of the following malfunctions occur take the me...

Страница 30: ...eration Moisture generated by defrost becomes steam and is exhausted 18 1 6 Symptom The user interface display reads U4 or U5 and stops but then restarts after a few minutes This is because the user i...

Страница 31: ...can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it...

Страница 32: ...4P482875 1 2017 03 Copyright 2017 Daikin...

Отзывы: