7
|
Installation
Installer reference guide
53
RZAG71~Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
Size-up liquid pipe size
L1 (m)
L1:
15~20
20~25
25~30
30~35
R:
0.35
0.7
1.05
(a)
1.4
(a)
(a)
Only for RZAG100~140.
To determine the additional refrigerant amount (R in kg) (in case of twin, triple
and double twin)
1
Determine G1 and G2.
G1 (m)
Total length of <x> liquid piping
x=
Ø9.5 mm
(standard)
x=
Ø12.7 mm
(size‑up)
G2 (m)
Total length of
Ø6.4
mm liquid piping
2
Determine R1 and R2.
If
Then
G1>40 m
(a)
Use the table below to determine R1
(length=
G1−40 m
)
(a)
and R2 (length=
G2
).
G1≤40 m
(a)
(and G1+G2>40 m)
(a)
R1=0.0 kg.
Use the table below to determine R2
(length=
G1+G2−40 m
)
(a)
.
(a)
In case of size‑up: Replace 40 m by 15 m.
Standard liquid pipe size
Length (m)
0~10
10~15
15~20
20~30
30~40
40~45
R1:
0.35
0.7
(a)
0.55
(b)
0.7
(a)
1.05
(a)
1.4
(a)
1.55
(a)
R2:
0.2
0.4
0.4
0.6
0.8
(a)
1.0
(a)
(a)
Only for RZAG100~140.
(b)
Only for RZAG71.
Size‑up liquid pipe size
Length (m)
0~5
5~10
10~15
15~20
20~30
30~40
40~45
R1:
0.35
0.7
1.05
(a)
1.4
(a)
—
—
—
R2:
0.35
0.7
(a)
1.05
(a)
1.4
(a)
—
(a)
Only for RZAG100~140.
3
Determine the additional refrigerant amount: R=R1+R2.