4 Installation

Installation manual

12

250D7Y1B

Sky Air Advance-series

4P573384-1 – 2019.04

To activate/deactivate the vacuum mode field
setting

Description

To  perform  vacuum  drying  or  a  complete  recharge  of  the  outdoor
unit’s  internal  refrigerant  piping  it  is  necessary  to  activate  the
vacuum  mode  which  will  open  required  valves  in  the  refrigerant
circuit  so  the  vacuuming  process  or  recharge  of  refrigerant  can  be
done properly.

To activate vacuum mode:

Activating  the  vacuum  mode  is  done  by  operating  the  push  buttons
BS* on the PCB (A1P) and reading the feedback from the 7‑segment
displays.

Operate the switches and push buttons with an insulated stick (such
as a closed ball-point pen) to avoid touching of live parts.

1

When  the  unit  is  powered  on  and  not  running,  hold  down  the
BS1 pushbutton for 5 seconds.

Result: 

You will reach the setting mode, the 7 segment display

will show '2 0 0'.

2

Press the BS2 button until you reach page 

2–17

.

3

When 

2–17

 is reached, press the BS3 button once.

4

Change the setting to '

2

' by pressing the BS2 button once .

5

Push the BS3 button once.

6

When the display is not blinking anymore, press the BS3 button
again to activate vacuum mode.

To deactivate vacuum mode:

After charging or vacuuming the unit, please deactivate the vacuum
mode:

7

Press the BS2 button until you reach page 

2–17

.

8

When 

2–17

 is reached, press the BS3 button once.

9

Change the setting to '

1

' by pressing the BS2 button once.

10

Push the BS3 button once.

11

When the display is not blinking anymore, press the BS3 button
again to deactivate vacuum mode.

12

Press the BS1 button to leave the setting mode.

Make  sure  to  reattach  the  electronic  component  box  cover  and  to
install the front cover after the job is finished.

NOTICE

Make  sure  that  all  outside  panels,  except  for  the  service
cover  on  the  electrical  component  box,  are  closed  while
working.

Close the lid of the electrical component box firmly before
turning on the power.

Charging refrigerant: Setup

See 

"4.3.1 Checking refrigerant piping: Setup" 

[

4

 9].

To completely recharge refrigerant

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

Prerequisite: 

Before  completely  recharging  refrigerant,  make  sure

the  system  is  pumped  down,  the  outdoor  unit's 

external

  refrigerant

piping  is  checked  (leak  test,  vacuum  drying)  and  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping is performed.

1

If not already done (for vacuum drying of the unit), activate the
vacuum  mode  (see 

"To  activate/deactivate  the  vacuum  mode

field setting" 

[

4

 12])

2

Connect the refrigerant cylinder to the service port of the liquid
stop valve.

3

Open the liquid stop valve.

4

Charge the complete refrigerant amount.

5

Deactivate  the  vacuum  mode  (see 

"To  activate/deactivate  the

vacuum mode field setting" 

[

4

 12]).

6

Open the gas stop valve.

4.4.7

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Quantity of fluorinated greenhouse gases

 of the total

refrigerant charge expressed as tonnes CO

2

 equivalent.

f

GWP = Global warming potential

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Use  the  GWP  value  mentioned  on  the  refrigerant  charge
label.  That  GWP  is  based  on  the  current  legislation  on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

Содержание Sky Air Advance RZA200D7Y1B

Страница 1: ...Installation manual Sky Air Advance series English Installation manual Sky Air Advance series RZA200D7Y1B RZA250D7Y1B ...

Страница 2: ... HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HD HU 250 1500 1000 500 HU HD HU 300 1500 1000 500 HD HU HB HD HU mm HU a b c d e eB eD A B C D E HB HD 100 1 100 1 1 b mm 1000 200 2000 100 3000 1500 b 100 1 HB HU 100 1 100 1 HB HU b 250 HU...

Страница 3: ...1 12 13 14 15 16 17 Direktiver med senere ændringer Direktiv med företagna ändringar Direktiver med foretatte endringer Direktiivejä sellaisina kuin ne ovat muutettuina v platném znění Smjernice kako je izmijenjeno irányelv ek és módosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muud...

Страница 4: ...rin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpoví...

Страница 5: ...ssioning 14 5 2 To perform a test run 15 5 3 Error codes when performing a test run 16 6 Disposal 16 7 Technical data 17 7 1 Service space Outdoor unit 17 7 2 Piping diagram Outdoor unit 17 7 3 Wiring diagram Outdoor unit 18 1 About the documentation 1 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops i...

Страница 6: ...iance or an operating electric heater 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter and the figures on the inside of the front cover INFORMATION The sound pressure level is less than 70 dBA CAUTION Appliance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and out...

Страница 7: ...eze between the heat exchanger and the casing of the unit This might decrease the operating efficiency INFORMATION We suggest to install the optional bottom plate heater EKBPH250D7 when the unit is installed in cold climates 4 1 4 To prevent the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as in...

Страница 8: ...ntation of the bends NOTICE Always protect the surrounding surfaces e g wiring insulation foam from heat when brazing 6 Do the following Insulate the liquid piping a and the gas piping b Wind heat insulation around the curves and then cover it with vinyl tape c Make sure the field piping does not touch any compressor components Seal the insulation ends sealant etc d Wrap the field piping with viny...

Страница 9: ... copper flare 4 3 3 To perform vacuum drying To remove all moisture from the system proceed as follows 1 Check that with the vacuum pump turned off the target vacuum is maintained for at least 1 hour 4 4 Charging refrigerant 4 4 1 About charging refrigerant The outdoor unit is factory charged with refrigerant but in some cases the following might be necessary What When Charging additional refriger...

Страница 10: ... the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an opera...

Страница 11: ...70 R1 0 45 0 9 1 35 1 8 2 25 2 7 3 15 Standard liquid pipe size Length m 0 10 10 20 20 30 30 40 40 50 50 60 60 70 R2 0 2 0 4 0 6 0 8 1 1 2 1 4 Size up liquid pipe size Length m 0 5 5 10 10 15 15 20 20 25 25 30 R1 0 35 0 7 1 05 1 1 1 75 2 1 R2 0 18 0 35 0 53 0 7 0 88 1 05 3 Determine the additional refrigerant amount R R1 R2 Examples Layout Additional refrigerant amount R L2 7 m Ø9 5 mm L3 5 m Ø9 5...

Страница 12: ...e refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before completely recharging refrigerant make sure the system is pumped down th...

Страница 13: ... 18 6 A 19 9 A Voltage range 380 415 V Phase 3N Frequency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cables H05VV U4G2 5 Recommended field fuse 20 A Earth leakage circuit breaker Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 4 5 3 To connect ...

Страница 14: ...ck the insulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 MΩ then the unit will not break down Use a 500 V mega tester when measuring insulation Do not use a mega tester for low voltage circuits 1 Measure the insulation resistance over the poles If Then 1 MΩ Insulat...

Страница 15: ...be lit For any other action it needs to be lit first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve and gas stop valve by removing the cap and turning counterclockwise with a hex wrench until it stops 2 Close the service cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to pr...

Страница 16: ...case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air inlet or air outlet is blocked U0 The stop valves are closed U2 There is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring a...

Страница 17: ...m distance between the unit and the edge of obstacle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed See figure 2 on the inside of the front cover 1 For better serviceabil...

Страница 18: ...nd Legend Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter A3P Printed circuit board inverter A4P Printed circuit board fan A5P Printed circuit board demand C503 C506 C507 A3P Capacitor DS1 DS2 A1P DIP switch E1H Bottom plate heater E1HC Crankcase heater F1U A1P Fuse T 3 15 A 250 V F8U F9U Fuse F F101U A4P Fuse F101U F102...

Страница 19: ......

Страница 20: ...4P573384 1 2019 04 Copyright 2019 Daikin 4P573384 1 0000000S ...

Отзывы: