background image

COMMISSIONING

1. CHECKLIST BEFORE COMMISSIONING

Do NOT operate the system before the following checks are OK:

The

indoor unit

is properly mounted.

The

outdoor unit

is properly mounted.

The system is properly

earthed

and the earth terminals are tightened.

ENGLISH

The 

fuses 

or locally installed protection devices are installed according to this document, and have NOT been

bypassed.
The

power supply voltage

matches the voltage on the identification label of the unit.

There are NO 

loose connections 

or damaged electrical components in the switch box.

There are NO 

damaged components 

or 

squeezed pipes 

on the inside of the indoor and outdoor units.

There are NO

refrigerant leaks

The

refrigerant pipes

(gas and liquid) are thermally insulated.

The correct pipe size is installed and the

pipes

are properly insulated.

The

stop valves

(gas and liquid) on the outdoor unit are fully open.

The following

field wiring

has been carried out according to this document and the applicable legislation

between the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence

: Condensate water might drip.

The indoor unit receives the signals of the

user interface

The specified wires are used for the

interconnection cable

.

2. CHECKLIST DURING COMMISSIONING

To perform an

air purge

To perform a

test run

.

INDICATION LIGHTS

IR Signal Receiver

When an infrared remote control operating signal has
been transmitted, the signal receiver on the indoor unit
will respond as below to confirm acceptance of the signal
transmission.

ON to OFF

OFF to ON

Pump down/Cool force on

Others

1 Long Beep

2 Short Beep

LED INDICATOR LIGHTS

1 Short Beep

Heatpump Unit

The table shows the LED indicator lights for the air
conditioner unit under normal operation and fault
conditions. The LED indicator lights are located at the
side of the air conditioner unit.

The heat pump units are equipped with an “auto”
mode sensor whereby it will provide reasonable room
temperature by switching automatically to either “cool” or
“heat” mode according to the temperature set by the user.

LED Indicator Lights for Heatpump Unit

IR RECEIVER
ON/OFF DISPLAY
TIMER
ON/OFF SWITCH

15

Содержание Siesta ATXC20DV1B

Страница 1: ...NDITIONER INSTALLATION MANUAL MODELS Installation Manual R32 Split Series ATXC20DV1B ARXC20DV1B ATXC25DV1B ARXC25DV1B ATXC35DV1B ARXC35DV1B ATXC50DV1B ARXC50DV1B ATXC60DV1B ARXC60DV1B ATXC71DV1B ARXC7...

Страница 2: ...dz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR ZTSR TM RZRZTO u d d d d k x x d d v w x d dd d d J 8B GI...

Страница 3: ...d d fv vd u vd vd f v v d v d vd d d d d d h i hk f d d d zdz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR...

Страница 4: ...e wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or...

Страница 5: ...ainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torqu...

Страница 6: ...if any and find the site where remote controller signals are properly received by the indoor unit within 7 metres Outdoor Unit The outdoor unit should be sited in a place where The restrictions on ins...

Страница 7: ...of work space below the ceiling surface Stop valve cover How to remove the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve co...

Страница 8: ...INDOOR UNIT ATXC60 71 y Recommended mounting plate retention spots 7 spots in all Place a leveler on these tabs Use a tape measure as shown Position the end of the tape measure at Z 117 126 5 65 65 49...

Страница 9: ...guide How to replace the drain plug and drain hose Removal method Drain hose attachment position 1 Rotate to detach wire clip from hook on the right and remove The drain hose is on the back of the un...

Страница 10: ...the marked area Front grille Bottom frame Mark rear side maintenance All dimensions are in mm at the lower part of the front grille to release the claws DRAIN PIPING Connect the drain hose as describ...

Страница 11: ...pressure is applied to the terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal b...

Страница 12: ...s so that the evacuated condensate CANNOT freeze FLARING THE PIPE END 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe...

Страница 13: ...bend radius Piping thickness Thermal insulation size Thermal insulation thickness Gas pipe Inter unit wire 6 4 1 4 30mm or more 9 5 3 8 30mm or more 12 7 1 2 40mm or more 15 9 5 8 50mm or more 19 1 3...

Страница 14: ...rating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If...

Страница 15: ...that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block Firmly fix the wires with the terminal screws Inter unit wire 4 core 60245 IEC 57 H07RN F 1 1 2...

Страница 16: ...checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking there shall be no live electrical components and wiring are exposed while char...

Страница 17: ...f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No...

Страница 18: ...ation between the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interfac...

Страница 19: ...peration Unit error Blinking OPERATING RANGE Heat Pump Model Model ATXC20 25 35 ARXC20 25 35 COOLING 50 46 43 40 30 HEATING 20 18 10 20 0 10 0 14 15 19 20 23 25 INDOOR TEMP CWB 10 15 20 10 15 20 25 27...

Страница 20: ...ance devices of the unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in...

Отзывы: