ELECTRICAL WIRING CONNECTION

IMPORTANT :

 

*  The figures shown in the table are for information purpose only. They should be checked and selected 

to comply with the local/national codes of regulations. This is also subject to the type of installation and 
conductors used.

 

**  The appropriate voltage range should be checked with label data on the unit.

N

OF

4WV

N1

L

COMP

N

OF

4WV

COMP

Heat Pump Unit (Single Phase)

Model

Indoor (ATYN)

20J 25J 35J 50J 60J

Outdoor (ARYN)

20C 25C 35C 50C 60C

Voltage range**

220-240V/~/50Hz + 

!

 

Power supply cable size* mm

2

Number of conductors

1.5

3

2.5

3

Interconnection cable size* mm

2

Number of conductors

1.5

5

2.5

5

Recommended fuse/circuit breaker rating 

A

15

20

Outdoor Unit 

Terminal Block

Indoor Unit 

Terminal Block

Interconnection cable

There must be an all pole disconnection 
in the supply mains with a contact 
separation of at least 3mm.

!

Outdoor coil sensor connection wire 
(8m long) attached in the indoor unit

N / L2
L / L1

Power 
Supply

Main 

Switch

Fuse / Circuit 

Breaker

Power Supply Cable

Attach insulation sleeve

Round crimp-style terminal

Electric wire

All wires must be 

fi

 rmly connected.

All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly 

fi

 xed to avoid any gap.

Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching 
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).







Connect wires of the 
same gauge to both side.

Do not connect wires of the 
same gauge to one side.

Do not connect wires 
of different gauges.

Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.




1 IM-5WMJR-0515(0)-DAIKIN SIESTA11   11

1 IM-5WMJR-0515(0)-DAIKIN SIESTA11   11

6/1/15   3:20:43 PM

6/1/15   3:20:43 PM

Интернет

-

магазин

 «

Мистер

 

Климат

» 

Тел

.: 8-800-5555-710

www.mrklimat.ru

Содержание Siesta ARYN20LV1

Страница 1: ...V1 ARYN60LV1 WALL MOUNTED R410A SPLIT TYPE AIR CONDITIONER IM 5WMJR 0515 0 DAIKIN SIESTA Part No R08019043338 Installation Manual R410A Split Type Air Conditioner R410A English CVR IM 5WMJR 0515 0 DAI...

Страница 2: ...CVR IM 5WMJR 0515 0 DAIKIN SIES2 2 CVR IM 5WMJR 0515 0 DAIKIN SIES2 2 6 1 15 3 20 21 PM 6 1 15 3 20 21 PM 8 800 5555 710 www mrklimat ru...

Страница 3: ...RATURE THERMISTOR INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL F E J G G L D B K M A Gas pipe end INSTALLATION PLATE 20 25 35J Liquid pipe end Through the wall hole 65mm All dimensions are in...

Страница 4: ...plate retention spots 7 spots in all Dimension Model A B C D E F G H I J K L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 207 52 Recommended mounting plate retention spots 5 spots in all Throug...

Страница 5: ...3 19 65 80 30 T All dimensions are in mm B A Q P R S D O K L L M N F E C G H I J N Dimension Model A B C D E F G H I J K L 50C 855 628 328 520 179 46 93 149 101 113 603 126 60C 855 730 328 520 179 46...

Страница 6: ...on the type and source of the electrical waves static may be heard even when more than 1m away Please take note of the following important points when installing Do not install the unit where leakage...

Страница 7: ...the arrow 3 Pull down INSTALLATION DIAGRAM Indoor unit Service lid Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s...

Страница 8: ...g cord PUSH PULL UP BASE A DRAIN ELBOW DRAIN ELBOW PLUG INSTALLATION OF THE OUTDOOR UNIT The outdoor unit must be installed in such a way so as to prevent short circuit of the hot discharged air or ob...

Страница 9: ...are in mm Right bottom piping Right side piping Remove pipe port cover here for right side piping Left back piping Left side piping Left bottom piping Left Side Left Back or Left Bottom Piping INSTALL...

Страница 10: ...to release the claws Mounting plate Interconnecting wires Hang indoor unit s hook here Wire guide When stripping the ends of interconnecting wires in advance bind right ends of wires with insulating...

Страница 11: ...ize mm in 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 Liquid Pipe Size mm in 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 Heat Pump Model If the pipe is too long both the capacity and reliability...

Страница 12: ...k and the flaring punch then tighten the flaring punch fully Piping Connection To The Units Align the center of the piping and tighten the flare nut sufficiently with fingers See Figure IV Finally tig...

Страница 13: ...tric wire All wires must be firmly connected All wires must not touch the refrigerant piping compressor or any moving parts of the fan motor The connecting wires between the indoor unit and the outdoo...

Страница 14: ...e center of the charging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacuum pump Evacuate for approximately 30 minutes The evacuation time vari...

Страница 15: ...re by switching automatically to either cool or heat mode according to the temperature set by the user ON OFF Cool Heat Timer Sleep ON OFF switch The refrigerant is pre charged in the outdoor unit If...

Страница 16: ...3 times Outdoor coil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compressor overload Indoor coil sensor short outdoor coil sensor short Call...

Страница 17: ...ase the internal and or the external temperature is too high or that the filter is dirty and clogged up the refrigerant may be overheated The compressor will cut out when the condensing temperature re...

Страница 18: ...ull it to the front side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with the grooves and push them all the way in Gently close the front panel Pu...

Страница 19: ...ay be caused by cigarettes smoke particles perfume etc which might have adhered onto the coil Condensation on the front air grille of the indoor unit 5 This is caused by air humidity after an extended...

Страница 20: ...MEMO 1 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 1 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 6 1 15 3 20 44 PM 6 1 15 3 20 44 PM 8 800 5555 710 www mrklimat ru...

Страница 21: ...20 25 35J 800 288 206 166 184 42 46 55 56 154 182 263 52 K ATYN A B C H I B F E J G G L D B K M A 20 25 35J 65 F 5 2 IM 5WMJR 0515 0 DAIKIN SIESTA1 1 2 IM 5WMJR 0515 0 DAIKIN SIESTA1 1 6 10 15 9 16 1...

Страница 22: ...E F G H I J K L M 50 60J 1065 310 224 190 173 61 40 45 48 91 219 580 45 D B G H J L M A K F I G F E 50 60J 7 5 65 E F G I K M L J H G F B D A 20 25 35J 65 2 IM 5WMJR 0515 0 DAIKIN SIESTA2 2 2 IM 5WMJ...

Страница 23: ...65 80 30 25 35C 18 3 19 65 80 30 T B A Q P R S D O K L L M N F E C G H I J N A B C D E F G H I J K L 50C 855 628 328 520 179 46 93 149 101 113 603 126 60C 855 730 328 520 179 46 93 149 101 113 603 12...

Страница 24: ...2 4 H MAH E CTOPO HO 1 1 OFF 2 IM 5WMJR 0515 0 DAIKIN SIESTA4 4 2 IM 5WMJR 0515 0 DAIKIN SIESTA4 4 6 10 15 9 16 16 AM 6 10 15 9 16 16 AM 8 800 5555 710 www mrklimat ru...

Страница 25: ...2 5 M4 x 12L e 75 50 1 2 3 500 2 IM 5WMJR 0515 0 DAIKIN SIESTA5 5 2 IM 5WMJR 0515 0 DAIKIN SIESTA5 5 6 10 15 9 16 16 AM 6 10 15 9 16 16 AM 8 800 5555 710 www mrklimat ru...

Страница 26: ...2 A A H A B C D acc o e 300 1000 300 500 A B H 2 H pe c C D pe c 2 IM 5WMJR 0515 0 DAIKIN SIESTA6 6 2 IM 5WMJR 0515 0 DAIKIN SIESTA6 6 6 10 15 9 16 16 AM 6 10 15 9 16 16 AM 8 800 5555 710 www mrklimat...

Страница 27: ...50 75 c y ox K K 50 60J 20 25 35J K 20 25 35J 20 25 35J 50 60J 65 2 IM 5WMJR 0515 0 DAIKIN SIESTA7 7 2 IM 5WMJR 0515 0 DAIKIN SIESTA7 7 6 10 15 9 16 17 AM 6 10 15 9 16 17 AM 8 800 5555 710 www mrklim...

Страница 28: ...5 153 8 263 51 9 800 45 9 42 2 288 42 2 45 9 poc ep e ec ep o 50 60J 20 25 35J 5 65 7 65 5 104 141 30 46 56 181 800 55 207 52 153 46 30 288 20 25 35J K 65 2 IM 5WMJR 0515 0 DAIKIN SIESTA8 8 2 IM 5WMJR...

Страница 29: ...L 12 12 12 20 20 E 5 5 5 15 15 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 L E 2 IM 5WMJR 0515 0 DAIKIN SIESTA9 9 2 IM 5WMJR 0515 0 DAIKIN SIESTA9 9 6...

Страница 30: ...A 1 4 6 35 1 3 0 7 3 8 9 52 1 6 1 0 1 2 12 70 1 9 1 3 5 8 15 88 2 2 1 7 3 4 19 05 2 5 2 0 II III IV L 3 8 OD9 52 0 18 1 3 1 2 OD12 7 0 20 1 5 5 8 OD15 9 0 25 2 3 4 OD19 1 0 35 2 4 7 8 OD22 2 0 40 3 1...

Страница 31: ...35J 50J 60J ARYN 20C 25C 35C 50C 60C 220 240V 50 2 1 5 3 2 5 3 2 1 5 5 2 5 5 A 15 20 8 N L2 L L1 3 H07RN F 2 IM 5WMJR 0515 0 DAIKIN SIESTA11 11 2 IM 5WMJR 0515 0 DAIKIN SIESTA11 11 6 10 15 9 16 18 AM...

Страница 32: ...PVE R410A R22 R410A POE PVE R22 R410A R410A R410A R22 C 3 30 760 760 3 2 4 o 3 760 760 3 3 2 IM 5WMJR 0515 0 DAIKIN SIESTA12 12 2 IM 5WMJR 0515 0 DAIKIN SIESTA12 12 6 10 15 9 16 18 AM 6 10 15 9 16 18...

Страница 33: ...YN35J ARYN35C 12 4 5 4 5 x 9 40 5 1 R410A ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C 20 16 16 19 16 2 IM 5WMJR 0515 0 DAIKIN SIESTA13 13 2 IM 5WMJR 0515 0 DAIKIN SIESTA13 13 6 10 15 9 16 18 AM...

Страница 34: ...2 14 1 E1 3 E3 2 E2 1 E4 3 E5 6 E8 4 E9 2 IM 5WMJR 0515 0 DAIKIN SIESTA14 14 2 IM 5WMJR 0515 0 DAIKIN SIESTA14 14 6 10 15 9 16 19 AM 6 10 15 9 16 19 AM 8 800 5555 710 www mrklimat ru...

Страница 35: ...1 C 33 8 F HIGH HOT KEEP OFF INTERVAL ON X DB WB WB C DB C 46 43 19 14 19 23 DB C 15 20 27 WB C 18 10 9 2 IM 5WMJR 0515 0 DAIKIN SIESTA15 15 2 IM 5WMJR 0515 0 DAIKIN SIESTA15 15 6 10 15 9 16 19 AM 6...

Страница 36: ...T 2 1 3 4 2 2 1 2 c 3 CTOPO HO 40 104 F 1 2 3 1 2 40 104 F 1 2 1 2 2 IM 5WMJR 0515 0 DAIKIN SIESTA16 16 2 IM 5WMJR 0515 0 DAIKIN SIESTA16 16 6 10 15 9 16 19 AM 6 10 15 9 16 19 AM 8 800 5555 710 www mr...

Страница 37: ...2 17 CTOPO HO 40 C 3 1 3 4 2 3 4 5 6 2 30 C 86 F 2 IM 5WMJR 0515 0 DAIKIN SIESTA17 17 2 IM 5WMJR 0515 0 DAIKIN SIESTA17 17 6 10 15 9 16 20 AM 6 10 15 9 16 20 AM 8 800 5555 710 www mrklimat ru...

Страница 38: ...2 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 2 IM 5WMJR 0515 0 DAIKIN SIESTA18 18 6 10 15 9 16 20 AM 6 10 15 9 16 20 AM 8 800 5555 710 www mrklimat ru...

Страница 39: ...CVR IM 5WMJR 0515 0 DAIKIN SIES3 3 CVR IM 5WMJR 0515 0 DAIKIN SIES3 3 6 1 15 3 20 21 PM 6 1 15 3 20 21 PM 8 800 5555 710 www mrklimat ru...

Страница 40: ...alleries 4 11th Floor Downtown Jebel Ali Dubai UAE Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kay sdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE...

Отзывы: