2
|
Components
Service manual
94
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
10
With the DC fan motor connector S71 disconnected from the main PCB,
measure the voltage on the connector pins 10-11 (= fan motor control) on the
inverter PCB.
Result:
The voltage MUST be 15±10% V DC.
Is the measured voltage correct?
Action
Yes
Continue with the next step.
No
Perform a check of the main PCB, see
74].
11
Connect the DC fan motor connector to the PCB. Remove the plastic insert
from the connector for easier measurement.
CAUTION
Ensure that the system CANNOT start the fan. Disable all modes (heating, cooling, …)
on the unit. The outdoor unit MUST be kept powered.
12
Manually (slowly) rotate the fan blade propeller 1 turn and measure the
voltage on the DC fan motor connector pins 10-12.
Result:
4 pulses MUST be measured.
13
Repeat the previous step and measure the voltage on the DC fan motor
connector pins 10-13.
Result:
4 pulses MUST be measured.
Pulses are measured during fan blade
propeller rotation?
Action
Yes
Perform a check of the main PCB, see
74].
No
Replace the DC fan motor, see
94].
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
101].
2
Remove the nut that fixes the propeller fan blade assembly.
Содержание Sensira Series
Страница 169: ......
Страница 170: ......
Страница 171: ......
Страница 172: ...ESIE18 12E 2021 02 Copyright 2018 Daikin Verantwortung f r Energie und Umwelt...