3
2
• VRV Systems • SB.RKXYQ-T
3
• Outdoor Unit • SB.RKXYQ-T
2
Specifications
2-1 Technical Specifications
SB.RKXYQ5T
SB.RKXYQ8T
System
Heat exchanger unit
RDXYQ5T
RDXYQ8T
Compressor unit
RKXYQ5T
RKXYQ8T
Capacity range
HP
5
8
Cooling capacity
Nom.
35°CDB
kW
14.0 (1)
21.4 (1)
Heating capacity
Nom.
6°CWB
kW
14.0 (2)
21.4 (2)
Max.
6°CWB
kW
16.0 (2)
25.0 (2)
Power input - 50Hz
Cooling
Nom.
35°CD
B
kW
4.38 (1)
7.64 (1)
Heating
Nom.
6°CWB kW
3.68 (2)
5.94 (2)
Max.
6°CWB kW
4.71 (2)
7.60 (2)
Capacity control
Method
Inverter controlled
EER at nom. capacity 35°CDB
kW/kW
3.20 (1)
2.80 (1)
COP at nom. capacity 6°CWB
kW/kW
3.80 (2)
3.60 (2)
COP at max. capacity 6°CWB
kW/kW
3.40 (2)
3.29 (2)
Maximum number of connectable indoor units
10 (3)
17 (3)
Indoor index
connection
Min.
63
100
Nom.
125
200
Max.
163
260
Fan
External static
pressure
Max.
Pa
150
Nom.
Pa
60
Piping connections
Between
Compressor module
(CM) and heat
exchanger module
(HM)
Liquid
Type
Braze connection
OD
mm
12.7
Gas
Type
Braze connection
OD
mm
19.1
22.2
Piping
length
Max.
m
30.0
Level
differen
ce
CM
below
HM
m
10.0
CM
above
HM
m
10.0
Between
Compressor module
(CM) and indoor
units (IU)
Liquid
Type
Braze connection
OD
mm
9.52
Gas
Type
Braze connection
OD
mm
15.9
19.1
Level
differen
ce
CM
below
IU
m
30.0
CM
above
IU
m
30.0
Liquid
OD
mm
-
Total piping length
System Actual
m
140 (4)
300 (4)
Level difference
IU - IU
Max.
m
15
Defrost method
Reversed cycle
2-2 Electrical Specifications
SB.RKXYQ5T
SB.RKXYQ8T
Current - 50Hz
Zmax
List
No requirements
Minimum Ssc value
kVa
-
3,329 (5)
Wiring connections -
50Hz
For connection with indoor
Quantity
2
-
Remark
F1,F2
-