ESIE16-03B
|
Part 5. Appendix
5.1. Field setting
SA R32 Sky-Air RZAG-L
22/08/16
|
Version 1.1
Page 105
5.1.2.2. Sky-Air R32 outdoor field settings through outdoor
The figures in the columns under “No.” represent the number of times to push the
SET (BS2)
button.
h
: OFF
k
: ON
No.
Display of setting items
Display of setting conditions
Setting items
LED display
Setting condition
LED Display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H1P
H2P
H3P
H4P
H5P
H6P
H7P
3
Demand 2 operation
bck
h
h
h
h
bck
bck
30% Demand
k
h
h
h
k
h
h
40% Demand (factory set)
k
h
h
h
h
k
h
50% Demand
k
h
h
h
h
h
k
11
TeS Lower limit value
bck
h
h
bck
h
bck
bck
0°C
k
h
h
h
h
h
k
2°C (factory set)
k
h
h
h
h
k
h
4°C
k
h
h
h
h
k
k
6°C
k
h
h
h
k
h
h
28
Refrigerant recovery mode
k
h
k
k
k
h
h
OFF (factory setting)
k
h
h
h
h
h
k
ON
k
h
h
h
h
k
h
33
TeS Lower limit value
k
k
h
h
h
h
k
0°C (factory set)
k
h
h
h
h
h
k
6°C
k
h
h
h
h
k
h
9°C
k
h
h
h
h
k
k
11°C
k
h
h
h
k
h
h
13°C
k
h
h
h
k
h
k
15°C
k
h
h
h
k
k
h
17°C
k
h
h
h
k
k
k
Weather depending con-
trol in cooling
k
h
h
k
h
h
h
34
TcS Upper limit value
k
k
h
h
h
k
h
60°C
k
h
h
h
h
h
k
50°C
k
h
h
h
h
k
h
47°C
k
h
h
h
h
k
k
45°C
k
h
h
h
k
h
h
43°C
k
h
h
h
k
h
k
Weather depending con-
trol in heating
k
h
h
h
k
k
h
54
Weather depending control TeS
Lower limit value A
k
k
k
h
k
k
h
9°C (factory set)
k
h
h
h
h
h
k
11°C
k
h
h
h
h
k
h
13°C
k
h
h
h
h
k
k
15°C
k
h
h
h
k
h
h
57
Weather depending control TeS
Lower limit value B
k
k
k
k
h
h
k
2°C (factory set)
k
h
h
h
h
h
k
4°C
k
h
h
h
h
k
h
6°C
k
h
h
h
h
k
k
8°C
k
h
h
h
k
h
h
58
Weather depending control TeS
Lower limit value C
k
k
k
k
h
k
h
14°C (factory set)
k
h
h
h
h
h
k
17°C
k
h
h
h
h
k
h
20°C
k
h
h
h
h
k
k
23°C
k
h
h
h
k
h
h
59
Weather depending control TeS
Lower limit value D
k
k
k
k
h
k
k
23°C (factory set)
k
h
h
h
h
h
k
27°C
k
h
h
h
h
k
h
31°C
k
h
h
h
h
k
k
35°C
k
h
h
h
k
h
h
60
Weather depending control TcS
Upper limit value E
k
k
k
k
k
h
h
47°C (factory set)
k
h
h
h
h
h
k
48°C
k
h
h
h
h
k
h
49°C
k
h
h
h
h
k
k
50°C
k
h
h
h
k
h
h
61
Weather depending control TcS
Upper limit value F
k
k
k
k
k
h
k
43°C (factory set)
k
h
h
h
h
h
k
44°C
k
h
h
h
h
k
h
45°C
k
h
h
h
h
k
k
46°C
k
h
h
h
k
h
h
62
Weather depending control TcS
Upper limit value G
k
k
k
k
k
k
h
2°C (factory set)
k
h
h
h
h
h
k
5°C
k
h
h
h
h
k
h
8°C
k
h
h
h
h
k
k
11°C
k
h
h
h
k
h
h
63
Weather depending control TcS
Upper limit value H
k
k
k
k
k
k
k
15°C (factory set)
k
h
h
h
h
h
k
18°C
k
h
h
h
h
k
h
21°C
k
h
h
h
h
k
k
24°C
k
h
h
h
k
h
h
Содержание SA R32 Sky-Air RZAG-L
Страница 14: ...ESIE16 03B Part 1 Introduction 1 4 How to use Page 14 22 08 16 Version 1 1 SA R32 Sky Air RZAG L...
Страница 60: ...ESIE16 03B Part 2 Troubleshooting 2 5 Other capacity range Page 60 22 08 16 Version 1 1 SA R32 Sky Air RZAG L...
Страница 94: ...ESIE16 03B Part 3 Repair 3 3 Unit specific repair procedures Page 94 22 08 16 Version 1 1 SA R32 Sky Air RZAG L...
Страница 98: ...ESIE16 03B Part 5 Appendix Page 98 22 08 16 Version 1 1 SA R32 Sky Air RZAG L...