<Failure example> 

If there is an obstacle in the airflow path or proper installation 

space is not provided, the indoor unit will cause air volume 

reduction and take in air blown out of the indoor unit, 

thus resulting in performance degradation or turning the 

thermostat OFF frequently. 

-:&CAUTION 

• Install the indoor and outdoor units, power supply wiring,

remote controller wiring and transmission wiring at least 

1 meter away from televisions or radios to prevent image 

interference or noise. 

(Depending on the radio waves, a distance of 1 meter may

not be sufficient to eliminate the noise.) 

• Install the indoor unit as far as possible from fluorescent

lamps. 

If a wireless remote controller kit is installed, the transmis­

sion distance may be shorter in a room where an electronic 

lighting type (inverter or rapid start type) fluorescent lamp is 

installed. 

(2) Use hanging bolts for installation.

Investigate if the installation place can withstand the mass 

of the indoor unit and, if necessary, hang the indoor unit 

with bolts after it is reinforced by beams etc. 

4. PREPARATION BEFORE INSTALLATION

(1) Check the relation of location between the ceiling

opening and the indoor unit hanging bolts.

• Provide one of the following service spaces for the

maintenance and inspection of the control box and 

drain pump or for other services. 

1. Inspection hatch 1 and 2 ( 450 x 450) for the el.

compo box and a minimum space of 300 mm at the

bottom of the product. (Refer Fig. 2-2) 

2. Inspection hatch 1 (450 x 450) on the control box side

and inspection hatch 2 on the bottom of the 

product.(Fig. 2-3, arrow A-1) 

3. Inspection hatch 3 on the bottom of the product and on

the bottom side of the control box, see direction view 

A-2 (Refer Fig. 2-3)

Case 1 

fZll/11111'' 

Inspection hatch/ 

Fig.2-1 

El. compo. box 

(') 

II 

(') 

� 

C\I 

C: 

• 

50 

-

140 type 

700 

631 

(Hanging bolt pitch) 

r·-·-·-

i'v/! 

i  /', 

+----++-_:,,,-' _ _'_� 

Inspection hatch 

(450x450)
Hanging bolt  (x 4) 

El. compo. box 

(For disassembly such as motors and drain pan) 

• When work is possible in space of the unit

lower part, inspection hatch 2 is unnecessary.

Fig.2-2 

Case 2,  3 

Inspection hatch 

(Ceiling opening) 

El. compo. box 

1

u

�v]j 

Inspection hatch/ 

A

� 

Inspection hatch 1 

(450x450) 

Inspection hatch 3 
(Same as the indoor 

unit size +300 or more) 

l':

l

:;i 

'"/ 

C\I 

:  /'•'- I 

l-----�---+ 

ri '•'-.,  _;· 

j: 

:!  / ·'-, 

lj/  ·"-.U

I.

700  • 

I

Arrow A-1 

Model 

50.71 

90.100.125.140 

El. compo.  box 

!\  /:  g 

1----'----i,z:_.'. __ ,.J 

• 

--�7  ID

El. com po.  box  n 

,X. 

! i 

ti 

!i  /  \  !i 

C: 

Inspection 

11

:

\,U 

hatch 2 

-

-

(Same as the 

I ,  700  , I 

indoor unit 

Arrow A-2 

size or more) 

Fig.2-3 

1000 

1038 

1400 

1438 

1300 

1700 

{All dimensions are in mm) 

(2) Mount canvas ducts to the air outlet and inlet so that

the vibration of the indoor unit will not be transmitted

to the ducts or ceiling. Furthermore, attach sound

absorbing material (thermal insulation material) to the

duct inner walls and anti-vibration rubber to the hanging 

bolts (refer to 8. DUCT WORK).

(3) The indoor unit is set to standard external static

pressure.

• If external static pressure is higher or lower than the

standard set value, the remote controller may be used to

make on-site setting change in the external static pressure. 

Refer to 

10. FIELD SETTING.

 

3

8

Содержание RZVF50

Страница 1: ...1...

Страница 2: ...2...

Страница 3: ...3...

Страница 4: ...4...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...7...

Страница 8: ...8...

Страница 9: ...9...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...255...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...28...

Страница 29: ...299...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32...

Страница 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...

Страница 34: ...Operation Manual Ask the user to keep this manual in a handy place for future reference WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the ma...

Страница 35: ...itioner in places such as the following 1 Where there is mist of oil oil spray or vapour for example a kitchen Resin parts may deteriorate and fall out or water may leak 2 Where corrosive gas such as...

Страница 36: ...quired for multi slave units in simultaneous multi operation There are 2 kinds of remote controller wired type and wireless type Install the remote controller to the place where the customer has given...

Страница 37: ...mer read through the troubleshooting items while explaining the above items 3 SELECTION OF INSTALLATION LOCATION Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacke...

Страница 38: ...uct Refer Fig 2 2 2 Inspection hatch 1 450 x 450 on the control box side and inspection hatch 2 on the bottom of the product Fig 2 3 arrow A 1 3 Inspection hatch 3 on the bottom of the product and on...

Страница 39: ...al components before installing the indoor unit 5 INSTALLATION OF INDOOR UNIT Depending on the optional parts it may be easier to attach them beforeinstalling the indoor unit Refer to also the install...

Страница 40: ...40...

Страница 41: ...ing NOTE 2 After all the brazing works are finished carry out flare connection with the indoor unit Refer to Fig 8 Pressure reducing valve Refrigerant piping Fig 9 NOTE a Taping Nitrogen 1 The proper...

Страница 42: ...maged with the clamp end or bend the tip of the metal clamp 1 inward as shown Refer to Fig 12 In case of sticking vinyl tape Vinyl tape Stick vinyl tape without tearing the sealing l material r _ 5 _...

Страница 43: ...ing must be carried out by a qualified electrician If a qualified person is not present after the electric wir ing work is finished check the drainage according to the method specified in When the ele...

Страница 44: ...circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker Failure to do so may c...

Страница 45: ...ctric shocks or a fire 1 Remove the control box lid Fig 20 2 Connect the wiring into the control box through the wiring intake beside the control box Low voltage wiring inlet Remote controller wiring...

Страница 46: ...r and indoor units must be matched 2 1 Connect the remote controller only to the master unit 2 2 The remote controller needs to be wired only to the master unit it does not need to be connected to the...

Страница 47: ...factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of ModeNo is carried out as a group if you intend to ca...

Страница 48: ...ring to the table below according to the external static pressure of the duct to be connected Table External static Mode No FIRST SECOND pressure CODE No CODE No 50Pa 05 60Pa 06 70Pa 07 80Pa 08 90Pa 0...

Страница 49: ...the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode 3 7 Earth leakage circuit breaker Eart...

Страница 50: ...e the malfunction code NOTE _ DI 1 When the ON OFF button is kept pressed for 5 seconds or longer during the inspection mode the above trouble his tory indication disappears In this case after the mal...

Страница 51: ...ct the adapter or Outdoor air thermistor Abnormal stop is applied the capacity is not set to the system malfunction depending on the model or data retention IC Outdoor unit condition The refrigerant m...

Страница 52: ...he customer 12 DECLARED RATINGS Rated Values Please do not refer the Capacity Input Power Current Electricity Consumption mentioned on Outdoor unit rating label when this Outdoor is connected with Inv...

Страница 53: ...caution to be given when connecting pipes IFi I I ur t e srace wit rutty or t ermal insulation field surrlY w ere t e rires t roug as s own elow If small animals li e insects enter into He outdoor un...

Страница 54: ...tch to protectthe compressor I Caution I Never short circuit the high pressure switch duringpump down operation It is not allowed to let the refrigerant out into the air The refrigerant should be reco...

Страница 55: ...itioner air conditioner Rework the flare For R32 see table on next page Use the supplied flare nut I Existing pi ping wort tor new air conditioner PRECAUTIONS ON REFRIGERANT PIPING Clean pipe if exist...

Страница 56: ...LARE PROCESSING I Fi 9 I n oor t U ni t 7l Liq atop valve I I Fi 9 2 n oor i1 n 7 aa s pipe Liq stop valve I I Fi 9 3 n oor u ni Liq stop valve I I Ref recovery port Flare connection area of existed p...

Страница 57: ...MEMO 57...

Страница 58: ...DAIKIN SPLIT SYSTEM MODELS Ceiling mounted Duct type FDMF50BRV16 FDMF71BRV16 FDMF90BRV16 FDMF100BRV16 FDMF125BRV16 FDMF140BRV16 OPERATION MANUAL Air Conditioner 58...

Страница 59: ...nd user maintenance shall only be done by persons described in manual The appliance is not intended for use by unattended young children or persons who are incompetent to operate air conditioners It m...

Страница 60: ...oil vapor Oil vapor may cause crack damage to the air conditioner electric shocks or a fire Do not use flammable materials e g hairspray or insecticide near the air conditioner Do not clean the air c...

Страница 61: ...result in electric shocks or fire Do not place water containers flower vases etc on the indoor unit as this may result in electric shocks or a fire Do not put flammable containers such as spray cans...

Страница 62: ...r and call your local dealer for assistance After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall and cause injury Do not sit or place obj...

Страница 63: ...ess remote controller kit If your installation has a customized control system ask your local dealer for the operation that corresponds to your system Names and functions of parts 2 7 3 D 6 d2b 13 10...

Страница 64: ...and increased running noises If abnormal noises occur in use stop the operation of the air conditioner consult your local dealer Regarding drainage of drain piping Is the drain piping carried out prop...

Страница 65: ...let of the air conditioner It may decrease the effect or stop the operation Set the airflow of the air discharge grille horizontally not to obstruct the wind Otherwise the wind will not come out and a...

Страница 66: ...an air filter as a standard accessory Do not attach objects other than the genuine air filter e g kitchen paper to the air inlet Otherwise the performance of the air conditioner will be degraded and...

Страница 67: ...inside of the air conditioner may become contaminated after several seasons of use potentially causing performance degradation and water leakage Ask your local dealer for details on cleaning the insi...

Страница 68: ...operation from long resting time Dust absorbed by the unit blows out 7 THE INDOOR UNITS GIVE OFF ODORS During operation The unit absorbs the smell of rooms furniture cigarettes etc and then emits the...

Страница 69: ...cooling Check if the heat source of the room is exces sive when cooling 4 Operation was performed or stopped al though the ON OFF button was not pressed Are you sure that the ON OFF timer operation is...

Страница 70: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P725250 2 70...

Отзывы: