background image

7

English

(E) When outdoor units are installed in rows (on the rooftop, etc.)

(1)When one outdoor unit is installed in each row

(2)When two or more outdoor units are installed side by side

The dimensional relationship between H, L and A is as shown in the
table below.

5.

CAUTIONS ON INSTALLATION

• Before installation, confirm the strength and levelness of the founda-

tion so that vibrations and noise are not generated.

• Fix the outdoor unit securely on a rigid base with foundation bolts as 

shown in the foundation drawing below.
(Prepare 4 sets of commercially available M12-type or equivalent 
foundation bolts, nuts and washers.)

• Use resin washers to prevent the paint from being scratched off and 

rusting.

• The foundation bolts should be protruded by 15/16 in.

(Refer to figure)

〈〈

Drain treatment

〉〉

• In a location where drain from the outdoor unit may cause troubles 

(for example, where drainage may splash on general passersby), 
perform the drain piping work using the drain plug (optional).

• For drain treatment, space of at least 4 in. is required under the bot-

tom frame of the outdoor unit.

• In the drain piping work, make sure that drainage is discharged 

securely.
(When routing the piping downward, check for water leakage.)

• A transportation metal in yellow and a washer are provided on the 

leg of the compressor for protecting the unit during transport. 
Remove them as described below.

(1) Open the sound-proof cover as shown in the above figure.

At this time, do not pull the sound-proof cover, and do not remove it 
from the compressor.

(2) Remove the fixing nut.
(3) Remove the transportation metal and the washer as shown in the 

above figure.

(4) Return and tighten the fixing nut again.
(5) Return the sound-proof cover to achieve the former status.

CAUTION

• If the unit is operated with the transportation metal attached, abnor-

mal vibration or sound may be generated.

6.

REFRIGERANT PIPING WORK

CAUTION

<To piping technician>

Make sure to open the stop valves after finishing the piping 
work. (Refer to the table shown in “ 6-7 Additional refrigerant 
charge”.) 
(Operating the air conditioner with the stop valve shut may 
damage the compressor.)

• Use R410A to add refrigerant. (The R410A refrigerant cylinder has a 

pink stripe painted around it.)
All field piping must be installed by a licensed refrigeration technician 
and must comply with relevant local and national regulations.

BRAZING REFRIGERANT PIPING

Do not use flux when brazing copper-to copper refrigerant piping. 
(Particularly for the HFC refrigerant piping) Therefore, use the phosphor 
copper brazing filler metal (BCuP) which does not require flux.
(Flux has an extremely negative effect on refrigerant piping systems. 
For instance, if chlorine based flux is used, it will cause pipe corro-
sion. Flux containing fluorine will damage refrigerant oil.)

L

A

 H

0  

≤ 

1/2H

10

1/2H  

 H

12

H  

L

Installation is not allowed.

4 or more

8 or more

80 or more

40 or more

A

L

60 or more

24 or more

120 or more

H

15/16

Resin
washer

Transportation metal removal procedure

5 1/2

1 3/4

5 1/2

24 3/8

Air outlet side

(13 5/8-14)

13 3/4

11 3/8

8 5/8

4 5/8

Bottom view 
(unit: inch)

 Drain hole

16 5/8

24 1/8

Compressor

Fixing nut

Washer

Transportation 
metal

Sound-proof cover

Turn in the arrow direction 
and remove it.

01_EN_3PN07193-9P.fm  Page 7  Tuesday, June 6, 2017  3:56 PM

Содержание RZR36PVJU8

Страница 1: ...avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde...

Страница 2: ...ult in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant l...

Страница 3: ...as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animal...

Страница 4: ...whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following eff...

Страница 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pr...

Страница 6: ...utdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 W...

Страница 7: ...2 Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 i...

Страница 8: ...ng nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If th...

Страница 9: ...than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimens...

Страница 10: ...nditioner at 14 6 psi or less for 1 hour or more and confirm that the vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture o...

Страница 11: ...counterclockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is open How to close the stop valve 1 Insert a hexagon wrench into the valve stem and turn the valve stem c...

Страница 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmiss...

Страница 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU7 1 60Hz 208 230V 30A 27A RZQ36PVJU8 RZR36PVJU8 RZQ4...

Страница 14: ...ORK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas...

Страница 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis playe...

Страница 16: ...in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the pipi...

Страница 17: ...ions in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximu...

Страница 18: ...1707 HT 3PN07193 9P EM17A016 00_CV_3PN07193 9P fm Page 2 Tuesday June 6 2017 3 52 PM...

Отзывы: