![Daikin RZQSG-LV1 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/daikin/rzqsg-lv1/rzqsg-lv1_technical-data-manual_2460038008.webp)
3
1
2
• Split - Sky Air
®
• Outdoor Unit
7
• Outdoor Unit • Optimized for seasonal efficiency • RZQSG-LV1
2
Specifications
Fan motor
Quantity
1
2
Model
KFD-325-70-8A
Brushless DC motor
Output
W
70
200
94
Drive
Direct drive
Speed
Steps
8
Cooling Nom.
rpm
800
850
855
700
Super
low
rpm
-
Heating Nom.
rpm
745
920
540
Super
low
rpm
-
Sound power level
Cooling
Nom.
dBA
65
69
70
69
Sound pressure level
Cooling
Nom.
dBA
49
53
54
53
Silent operation
dBA
47
49
Heating
Nom.
dBA
51
57
58
54
Compressor
Quantity
1
Model
2YC63DXD
2YC63SXD
2YC90AXD
Type
Hermetically sealed swing compressor
Output
W
1,700
2,080
2,620
3,620
Starting method
Inverter driven
Operation range
Cooling
Ambien
t
Min.
ºCDB
-5.0
Max.
ºCDB
46
Heating
Ambien
t
Min.
ºCWB
-15
Max.
ºCWB
15.5
Refrigerant
Type
R-410A
Charge
kg
2.75
2.9
4.0
Control
Expansion valve (electronic type)
Circuits
Quantity
1
Refrigerant oil
Type
FVC50K
Charged volume
l
0.75
0.9
1.35
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
3
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5
Max.
m
30
50
System Equival
ent
m
40
70
Chargel
ess
m
30
Additional refrigerant charge
kg/m
see installation manual
4PW72942-1
see installation manual 4P302555-1
Level difference
IU - OU Max.
m
15
30.0
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Defrost method
Pressure equalising
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan motor thermal protection
03
Fuse
2-2 Technical Specifications
RZQSG71LV1
RZQSG100LV1
RZQSG125LV1
RZQSG140LV1