• Outdoor Unit • Optimized for seasonal efficiency • RZQG-L7V1
1
2
• Split - Sky Air
®
• Outdoor Unit
8
2
Specifications
Notes
(1) Cooling: return air temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent refrigerant piping length 5m (horizontal)
(2) Heating rated condition (Return air temperature: 20ºCDB, outdoor temperature: 7ºCDB, 6ºCWB, Equivalent ref.piping:5.0m\<horizontal\>, Front 1m, Height 1.5m)
(3) Minimum piping length: no limit
(4) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
(5) Equipment complying with EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current \> 16A and
≤
75A per phase
(6) Short-circuit power
(7) See separate drawing for electrical data
(8) 3 with re-charging
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5 (5)
Max.
m
50
75
System Equival
ent
m
70
90
Chargel
ess
m
30
Additional refrigerant charge
kg/m
see installation manual 4P302555-1
Level difference
IU - OU Max.
m
30.0
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Defrost method
Pressure equalising
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan motor thermal protection
03
Fuse
2-3 Electrical Specifications
RZQG71L7V1
RZQG100L7V1
RZQG125L7V1
RZQG140L7V1
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
10
Max.
%
10
Current
Zmax
List
Complies to EN61000-3-11
Recommended fuses
A
25
40
Wiring connections
For power supply
Remark
see installation manual 4P302555-1
For connection with
indoor
Remark
see installation manual 4P302555-1
Power supply intake
Outdoor unit only
2-2 Technical Specifications
RZQG71L7V1
RZQG100L7V1
RZQG125L7V1
RZQG140L7V1