Si281314E
Procedure to Remove Thermistor
Removal Procedure
9
8. Procedure to Remove Thermistor
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
Remove the front panel 2,
the right side panel, and
the piping cover, following
the procedure indicated at
"Removal of Outside
Panels and Related
Parts".
The discharge pipe thermistor, the suction pipe
thermistor, the heat exchange distributor
thermistor, and the thermistor for the midpoint of
the heat exchange are connected to the 1
common connector. When replacing, you have to
replace all 4 thermistors at once.
1
Remove the outdoor air
thermistor, pulling
forward and then sliding
it to the right.
2
Pull out the discharge
pipe thermistor (
∗
1) by
picking and pulling out
the mounting spring.
3
Pull out the suction pipe
thermistor by pushing
the fixing part.
4
Since the thermistor of
the heat exchange
distribution pipe is fixed
with the clamp plate,
pull the clamp plate
forward in order to
remove the thermistor.
5
Remove the thermistor
at the midpoint of heat
exchange by pushing
the fixing part.
6
Pull out the liquid pipe
thermistor by pushing
the fixing part.
Thermistor
Thermistor
Discharge pipe thermistor
(R2T)
Suction pipe thermistor
(R3T)
Liquid pipe thermistor
(R6T)
Thermistor for the
midpoint of heat exchange
(R5T)
Outdoor air thermistor
(R1T)
Heat exchange thermistor
(R4T)