4 Installation
Installation manual
14
RZASG71~Y1
Sky Air Advance-series
4P485928-1 – 2017.04
Item
Tightening torque (N•m)
M4 (earth)
1.2~1.4
M5 (X1M)
2.0~3.0
Item
Tightening torque (N•m)
M5 (earth)
2.4~2.9
If limited space is available at the wire terminal, use bended crimp-
style ring terminals.
4.5.3
Specifications of standard wiring components
Component
V1
Y1
71
100
125
140
100
125+140
Power supply cable
MCA
(a)
19.4 A
24.3 A
31.3 A
30.5 A
15.9 A
16.9 A
Voltage range
220~240 V
380~415 V
Phase
1~
3N~
Frequency
50 Hz
Wire sizes
Must comply with applicable legislation
Interconnection cables
Minimum cable section of 2.5 mm² and applicable for 230 V
Recommended field fuse
20 A
25 A
32 A
16 A
20 A
Earth leakage circuit breaker
Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).
4.5.4
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover.
2
Connect the interconnection cables and power supply as
follows:
c
a
d
e
1~50 Hz
220-240 V
3N~50 Hz
380-415 V
V1
Y1
L1 L2 L3
L1 L2 L3
N
b
b
a
a
a
I, II, III, IV
Pair, twin, triple, double twin
M, S
Master, slave
a
Interconnection cables
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e
User interface
a
71
d
c
e
d
c
e
f
100~140
d
f
d
c
c
b
a
Switch box
b
Stop valve attachment plate
c
Earth
d
Cable tie
e
Interconnection cable
f
Power supply cable
3
Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration above.
4
Route the wiring through the frame and connect the wiring to
the frame at the knockout hole.
Routing through
the frame
Choose one of the 3 possibilities:
a
b
a
b
a
b
2
3
1
a
Power supply cable
b
Interconnection cable
Содержание RZASG71M2V1B