background image

5

Operation range

RYS20,25,35B

3D039535

Outdoor

temp.

(°CDB)

Pull-down

period

Indoor temp. (°CWB)

Notes:

The graphs are based on the following conditions:

+

Equivalent piping length

7.5 m

+

Level difference

0 m

+

Air flow rate

high

Cooling

Heating

Indoor temp. (°CDB)

Outdoor

temp.

(°CWB)

RYS50,60B

3D028318C

Outdoor

temp.

(°CDB)

Pull-down

period

Indoor temp. (°CWB)

Notes:

The graphs are based on the following conditions:

+

Equivalent piping length

7.5 m

+

Level difference

0 m

+

Air flow rate

high

Cooling

Heating

Indoor temp. (°CDB)

Outdoor

temp.

(°CWB)

Pair Application

R-410A

RYS20,25,35,50,60BVMB

1

5

10

Split - Sky Air

Outdoor Units

Содержание RYS20BVMB

Страница 1: ...RYS B Pair Application technical data Split Sky Air air conditioning systems ...

Страница 2: ...s products and services and to assist in maintaining and improving the quality of the environment Daikin Europe N V is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard ISO9001 pertains to quality assurance regarding design development manufacturing as well as to services related to the product Daikin units comply with the European regulations that guarante...

Страница 3: ...ta 3 Capacity tables 6 4 Dimensional drawings 9 5 Operation range 10 6 Piping diagrams 11 7 Wiring diagrams 13 8 Sound level 14 Sound level data Sound pressure spectrum 9 Accessories 16 Standard accessories Optional accessories 10 Installation 17 Pair Application R 410A RYS20 25 35 50 60BVMB 1 Split Sky Air Outdoor Units ...

Страница 4: ...door units for pair application Daikin outdoor units can be mounted easily on a roof or terrace or simply placed against an outside wall Pair Application R 410A RYS20 25 35 50 60BVMB 1 1 2 Split Sky Air Outdoor Units ...

Страница 5: ...HEAT EXCHANGER Type WL fin J8 Hi XA tube Rows x stages x fin pitch mm 1 x 24 x 1 5 2 x 24 x 1 5 1 x 32 x 1 6 2 x 32 x 1 8 REFRIGERANT CIRCUIT Refrigerant type R 410A Refrigerant charge kg 0 79 0 96 1 20 1 70 Maximum allowable distance between indoor and outdoor m 15 30 Maximum allowable level difference m 15 20 Refrigerant control Motor operated expansion valve COMPRESSOR Type Hermetically sealed ...

Страница 6: ...YS60BVMB POWER SUPPLY VM VM VM VM VM NOMINAL DISTRIBUTION SYSTEM VOLTAGE Phase 1 1 1 1 1 Frequency Hz 50 50 50 50 50 Voltage V 230 230 230 230 230 NOTES 1 The sound pressure level is measured in an anechoic room at 1m distance from the unit It is a relative value depending on the distance and acoustic environment For measuring conditions please refer to item 8 of this chapter 2 The sound power lev...

Страница 7: ...ly Compressor OFM IFM Hz Volts Voltage range MCA MFA RHz RLA W FLA W FLA FTYS50BVMB RYS50BVMB 50 230 MAX 50Hz 253V MIN 50Hz 207V 18 20 72 6 92 53 0 18 40 0 16 3D040875 RYS FTYS60B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz Volts Voltage range MCA MFA RHz RLA W FLA W FLA FTYS60BVMB RYS60BVMB 50 230 MAX 50Hz 253V MIN 50Hz 207V 18 20 72 8 86 53 0 24 43 0 16 3D040875 SYMBOLS MCA Min C...

Страница 8: ...83 2 31 1 53 0 85 2 25 1 49 0 87 2 16 1 43 0 91 18 0 25 2 70 1 79 0 69 2 61 1 73 0 77 2 52 1 67 0 85 2 48 1 65 0 86 2 42 1 60 0 88 2 32 1 54 0 95 19 0 27 2 80 1 85 0 70 2 70 1 79 0 78 2 61 1 73 0 86 2 57 1 70 0 87 2 50 1 66 0 89 2 40 1 59 0 96 22 0 30 3 09 2 05 0 72 2 99 1 98 0 80 2 88 1 91 0 88 2 84 1 88 0 90 2 76 1 83 0 92 2 65 1 76 0 99 24 0 32 3 28 2 18 0 73 3 18 2 11 0 81 3 07 2 04 0 90 3 02 ...

Страница 9: ...25 5 37 3 34 1 36 5 22 3 27 1 46 5 07 3 20 1 55 5 01 3 18 1 59 4 92 3 13 1 65 4 77 3 06 1 74 19 0 27 5 45 3 36 1 38 5 30 3 29 1 47 5 15 3 22 1 57 5 09 3 19 1 60 5 00 3 15 1 66 4 85 3 08 1 76 22 0 30 5 68 3 41 1 41 5 53 3 34 1 51 5 38 3 27 1 60 5 32 3 24 1 64 5 23 3 20 1 70 5 08 3 13 1 79 24 0 32 5 84 3 45 1 44 5 69 3 38 1 54 5 54 3 31 1 63 5 48 3 28 1 67 5 39 3 24 1 73 5 24 3 17 1 82 Heating capac...

Страница 10: ... 78 6 02 1 89 7 04 2 01 7 71 2 10 20 0 3 44 1 65 4 29 1 76 5 14 1 86 5 98 1 96 7 00 2 09 7 68 2 17 21 0 3 43 1 69 4 27 1 79 5 12 1 90 5 97 2 00 6 98 2 13 7 66 2 21 22 0 3 41 1 73 4 25 1 83 5 10 1 94 5 95 2 04 6 97 2 17 7 64 2 25 24 0 3 37 1 80 4 22 1 91 5 07 2 01 5 91 2 12 6 93 2 24 7 61 2 32 3D040898 SYMBOLS AFR Air flow rate m3 min BF Bypass factor EWB Entering wet bulb temp CWB EDB Entering dry...

Страница 11: ... label In case of removing stop valve cover RYS50 60B unit mm 3D034257B Minimum space for air passage Wall height on air outlet side less than 1200 Drain outlet I D J 15 9 hose for connection 4 x holes for anchor bolts M8 or M10 Name plate Terminal strip with earth terminal Wiring inlet Gas stop valve J B CuT Liquid stop valve J A CuT Service port Outdoor air thermistor Brand name label In case of...

Страница 12: ... m Air flow rate high Cooling Heating Indoor temp CDB Outdoor temp CWB RYS50 60B 3D028318C Outdoor temp CDB Pull down period Indoor temp CWB Notes The graphs are based on the following conditions Equivalent piping length 7 5 m Level difference 0 m Air flow rate high Cooling Heating Indoor temp CDB Outdoor temp CWB Pair Application R 410A RYS20 25 35 50 60BVMB 1 5 10 Split Sky Air Outdoor Units ...

Страница 13: ...ilter Outdoor unit Gas stop valve Liquid receiver with filter Muffler with filter Filter 3D039302 RYS35 Outdoor temperature thermistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Accumulator Compressor Muffler Refrigerant flow Cooling Heating Discharge pipe thermistor Heat exchanger thermistor Muffler Motor operated valve Four way valve on cooling Muffler with filter O...

Страница 14: ...oor unit Four way valve on heating Muffler 3D034263C RYS60 Outdoor temperature thermistor Heat exchanger Propeller fan Capillary tube 1 Liquid stop valve Field piping Field piping Gas stop valve with service port Accumulator Compressor Capillary tube 3 Refrigerant flow Cooling Heating Discharge pipe thermistor Heat exchanger thermistor Capillary tube 2 Capillary tube 4 Muffler with filter Motor op...

Страница 15: ... Condenser discharge 3D037854D RYS50 60 R Protective earth Z1C Z2C Ferrite core X1M Terminal strip Y2E Electronic expansion valve coil V2 V5 Varistor F1U F2U FU201 Fuse HE1 HE2 HAC1 E AC1 AC2 H1 H2 HL L1 L2 X11A Connector MRM10 MRM20 MRC W Magnetic relay R1T R3T Thermistor S2 S102 Connector LEDA Pilot lamp PCB1 PCB2 Printed circuit board L Live N Neutral S1W Forced operation on off switch S4W Loca...

Страница 16: ...of publication Octave band center frequency Hz Octave band center frequency Hz RYS20 25 35B Cooling RYS20 25 35B Heating 3D013516E 3D013516E Legend 50 60Hz 220 240 220 230V 8 2 Sound pressure spectrum approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise NOTES 1 Operation sound is measured in an anechoic chamber 2 Operation sound level differs with o...

Страница 17: ...band sound pressure level Octave band sound pressure level approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 3D035059A 3D035059A Octave band center frequency Hz Octave band center frequency Hz NOTES 1 Operation sound is measured in an anechoic chamber 2 Operation sound level differs with operation and ambient conditions 3 Reference acoustic press...

Страница 18: ...ptional accessories RYS B RYS20BVMB RYS25BVMB RYS35BVMB RYS50BVMB RYS60BVMB Air direction adjustment grille KPW937A4 KPW945A4 A Installation manual B Drain plug Heat pump models There is on the bottom packing case Pair Application R 410A RYS20 25 35 50 60BVMB 1 9 9 1 16 Split Sky Air Outdoor Units ...

Страница 19: ...inage use block bases for outdoor unit Adjust foot height until the unit is leveled Otherwise water leakage or pooling of water may occur Where there is a danger of the unit falling use foot bolts or wires Allow space for piping and electrical servicing Service lid How to remove the service lid This service lid is an open close type Slide the lid downward to remove it How to attach the service lid...

Страница 20: ...efrigerant Failure to do so may result in reduced performance In sites with poor drainage use block bases for outdoor unit Adjust foot height until the unit is leveled Otherwise water leakage or pooling of water may occur Where there is a danger of the unit falling use foot bolts or wires Allow space for piping and electrical servicing Service lid Foot bolt hole centres Foot bolt hole centres From...

Отзывы: