12 Technical data
Installer and user reference guide
60
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1B – 2016.02
12.9
Capacity table: Indoor unit
Total capacity of indoor units needs to be within the specified range.
The connection ratio (CR): 50%≤CR≤130%.
HP class of
outdoor unit
50%
minimum CR
100%
nominal CR
130%
maximum CR
8
100
200
260
10
125
250
325
12
150
300
390
14
175
350
455
16
200
400
520
18
225
450
585
20
250
500
650
22
275
550
715
24
300
600
780
26
325
650
845
28
350
700
910
30
375
750
975
32
400
800
1040
34
425
850
1105
36
450
900
1170
38
475
950
1235
40
500
1000
1300
42
525
1050
1365
44
550
1100
1430
46
575
1150
1495
48
600
1200
1560
NOTICE
When selecting the total capacity higher than mentioned in
above table, cooling and heating capacity will drop. For
additional information see technical engineering data.