Installation and operation manual

5

RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482256-1 – 2017.03

Table of Contents

1 About the documentation

6

1.1

About this document..................................................................

6

For the installer

6

2 About the box

6

2.1

Outdoor unit...............................................................................

6

2.1.1

To remove the accessories from the outdoor unit.......

6

3 About the units and options

6

3.1

About the outdoor unit ...............................................................

6

3.2

System layout ............................................................................

7

4 Preparation

7

4.1

Preparing installation site ..........................................................

7

4.1.1

Installation site requirements of the outdoor unit ........

7

4.1.2

Additional installation site requirements of the
outdoor unit in cold climates .......................................

7

4.2

Preparing refrigerant piping .......................................................

7

4.2.1

Refrigerant piping requirements..................................

7

4.2.2

Refrigerant piping material..........................................

7

4.2.3

To select the piping size .............................................

8

4.2.4

To select refrigerant branch kits..................................

9

4.3

Preparing electrical wiring .........................................................

9

4.3.1

Safety device requirements ........................................

9

5 Installation

9

5.1

Opening the units ......................................................................

9

5.1.1

To open the outdoor unit.............................................

9

5.2

Mounting the outdoor unit..........................................................

9

5.2.1

To provide the installation structure ............................

9

5.2.2

To install the outdoor unit............................................ 10

5.2.3

To provide drainage .................................................... 10

5.2.4

To prevent the outdoor unit from falling over .............. 10

5.3

Connecting the refrigerant piping ..............................................

10

5.3.1

Using the stop valve and service port ......................... 10

5.3.2

To remove the pinched pipes...................................... 11

5.3.3

To connect the refrigerant piping to the outdoor unit .. 12

5.4

Checking the refrigerant piping .................................................

13

5.4.1

About checking the refrigerant piping ......................... 13

5.4.2

Checking refrigerant piping: General guidelines ......... 13

5.4.3

Checking refrigerant piping: Setup.............................. 13

5.4.4

To perform a leak test ................................................. 14

5.4.5

To perform vacuum drying .......................................... 14

5.5

To insulate the refrigerant piping...............................................

14

5.6

Charging refrigerant ..................................................................

14

5.6.1

Precautions when charging refrigerant ....................... 14

5.6.2

To determine the additional refrigerant amount .......... 15

5.6.3

To charge refrigerant .................................................. 15

5.6.4

Error codes when charging refrigerant........................ 16

5.6.5

To fix the fluorinated greenhouse gases label ............ 16

5.7

Connecting the electrical wiring.................................................

16

5.7.1

Field wiring: Overview................................................. 16

5.7.2

Guidelines when knocking out knockout holes ........... 16

5.7.3

Guidelines when connecting the electrical wiring ....... 17

5.7.4

To connect the electrical wiring on the outdoor unit.... 17

5.8

Finishing the outdoor unit installation ........................................

18

5.8.1

To finish the transmission wiring................................. 18

6 Configuration

18

6.1

Making field settings ..................................................................

18

6.1.1

About making field settings ......................................... 18

6.1.2

To access the field setting components...................... 18

6.1.3

Field setting components ............................................ 18

6.1.4

To access mode 1 or 2 ............................................... 19

6.1.5

To use mode 1 ............................................................. 19

6.1.6

To use mode 2 ............................................................. 19

6.1.7

Mode 1 (and default situation): Monitoring settings ..... 20

6.1.8

Mode 2: Field settings.................................................. 20

7 Commissioning

22

7.1

Precautions when commissioning .............................................. 23

7.2

Checklist before commissioning ................................................. 23

7.3

Checklist during commissioning ................................................. 23

7.3.1

About test run............................................................... 23

7.3.2

To perform a test run (7-LEDs display)........................ 23

7.3.3

Correcting after abnormal completion of the test run... 24

7.3.4

Operating the unit ........................................................ 24

8 Troubleshooting

24

8.1

Solving problems based on error codes ..................................... 24

8.1.1

Error codes: Overview ................................................. 24

9 Technical data

25

9.1

Service space: Outdoor unit ....................................................... 25

9.2

Piping diagram: Outdoor unit...................................................... 26

9.3

Wiring diagram: Outdoor unit ..................................................... 27

For the user

28

10 About the system

28

10.1

System layout ............................................................................. 28

11 User interface

28

12 Operation

28

12.1

Operation range ......................................................................... 28

12.2

Operating the system ................................................................. 28

12.2.1

About operating the system ......................................... 28

12.2.2

About cooling, heating, fan only, and automatic
operation ...................................................................... 28

12.2.3

About the heating operation......................................... 28

12.2.4

To operate the system ................................................. 29

12.3

Using the dry program ................................................................ 29

12.3.1

About the dry program ................................................. 29

12.3.2

To use the dry program................................................ 29

12.4

Adjusting the air flow direction.................................................... 29

12.4.1

About the air flow flap .................................................. 29

12.5

Setting the master user interface ............................................... 29

12.5.1

About setting the master user interface ....................... 29

12.5.2

To designate the master user interface (VRV DX)....... 30

12.5.3

To designate the master user interface (RA DX) ......... 30

13 Maintenance and service

30

13.1

About the refrigerant................................................................... 30

13.2

After-sales service and warranty ................................................ 30

13.2.1

Warranty period ........................................................... 30

13.2.2

Recommended maintenance and inspection............... 30

14 Troubleshooting

31

14.1

Error codes: Overview ................................................................ 31

14.2

Symptoms that are NOT system malfunctions ........................... 32

14.2.1

Symptom: The system does not operate ..................... 32

14.2.2

Symptom: Fan operation is possible, but cooling and
heating do not work...................................................... 32

14.2.3

Symptom: The fan strength does not correspond to
the setting .................................................................... 32

14.2.4

Symptom: The fan direction does not correspond to
the setting .................................................................... 32

14.2.5

Symptom: White mist comes out of a unit (Indoor
unit) .............................................................................. 32

14.2.6

Symptom: White mist comes out of a unit (Indoor
unit, outdoor unit) ......................................................... 32

14.2.7

Symptom: The user interface display reads "U4" or
"U5" and stops, but then restarts after a few minutes .. 33

14.2.8

Symptom: Noise of air conditioners (Indoor unit)......... 33

Содержание RXYSQ4TAY1B

Страница 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ4TAY1B RXYSQ5TAY1B RXYSQ6TAY1B...

Страница 2: ...0 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB...

Страница 3: ...3 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platnom znen De i tir...

Страница 4: ...la M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln teplota...

Страница 5: ...8 6 Configuration 18 6 1 Making field settings 18 6 1 1 About making field settings 18 6 1 2 To access the field setting components 18 6 1 3 Field setting components 18 6 1 4 To access mode 1 or 2 19...

Страница 6: ...nstructions Format Paper in the box of the outdoor unit Installer and user reference guide Preparation of the installation reference data Detailed step by step instructions and background information...

Страница 7: ...io interference in which case the user may be required to take adequate measures 4 1 2 Additional installation site requirements of the outdoor unit in cold climates NOTICE When operating the unit in...

Страница 8: ...e pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6...

Страница 9: ...header Indoor unit capacity index Refrigerant branch kit 182 KHRQ22M29H INFORMATION Maximum 8 branches can be connected to a header 4 3 Preparing electrical wiring 4 3 1 Safety device requirements Th...

Страница 10: ...he invasion of water in the unit and to avoid the drain water dripping see the following illustration NOTICE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise...

Страница 11: ...aks after tightening the service port cover Tightening torques Stop valve size mm Tightening torque N m turn clockwise to close Shaft Valve body Hexagonal wrench Cap valve lid Service port 9 5 5 4 6 6...

Страница 12: ...with screw b a b 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout hole b Cut out the slits c with a metal saw c c b a 4 6 m...

Страница 13: ...the outdoor unit are powered on NOTICE Wait until the outdoor unit has finished the initialisation to apply setting 2 21 Leak test and vacuum drying Checking the refrigerant piping involves Checking f...

Страница 14: ...il all moisture has been removed 4 Depending on whether you want to immediately charge refrigerant through the refrigerant charge port or first pre charge a portion of refrigerant through the liquid l...

Страница 15: ...valve b Nitrogen c Weighing scales d Refrigerant R410A tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves C and B 3 Pre charge...

Страница 16: ...Contains fluorinated greenhouse gases 2 1 1 1 2 2 kg tCO2 eq GWP kg 1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories...

Страница 17: ...ard field supply 3 Connect the power supply as follows 3N 50 Hz 380 415 V L1 L2 L3 L1 L2 L3 N X1M a b c a Earth leakage circuit breaker b Fuse c Power supply cable 4 Fix the cables power supply and tr...

Страница 18: ...ervention after changing field settings Some field settings are used for special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is re...

Страница 19: ...S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1 Press BS1 BS1 5 s Press BS1 for at least 5 s INFORMATION If you get confused in the middle of the process p...

Страница 20: ...power consumption limitation Power consumption limitation reduces the power consumption of the unit compared to nominal operating conditions Power consumption limitation can be set in mode 2 There are...

Страница 21: ...ut automatic refrigerant charging functionality following setting should be applied binary 1 default Deactivated binary 2 Activated To stop the manual additional refrigerant charge operation when the...

Страница 22: ...daptor DTA104A61 62 If the system needs to be running under power consumption limitation conditions when an external signal is sent to the unit this setting defines the level power consumption limitat...

Страница 23: ...e unit on loose connections or damaged electrical components Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properly executed Stop valves B...

Страница 24: ...malfunction code perform correcting actions as explained in the malfunction code table Carry out the test operation again and confirm that the abnormality is properly corrected INFORMATION If a malfun...

Страница 25: ...s within range Reversed power supply phase malfunction Correct phase order Insufficient supply voltage Check if the supply voltage is supplied properly Malfunction code System test run not yet execute...

Страница 26: ...reezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bo...

Страница 27: ...an 1 A5P Printed circuit board fan 2 BS1 BS5 Push button switch C32 C67 Capacitor DS1 DIP switch E1HC Crankcase heater F1U F2U Fuse T 3 15 A 250 V A1P F101U Fuse 5 A DC650 V A4P A5P F400U Fuse T 6 3 A...

Страница 28: ...manual of the indoor unit Refer to the operation manual of the installed user interface 12 Operation 12 1 Operation range Use the system in the following temperature and humidity ranges for safe and e...

Страница 29: ...12 4 Adjusting the air flow direction on page 29 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTIC...

Страница 30: ...njury CAUTION After a long use check the unit stand and fitting for damage If damaged the unit may fall and result in injury NOTICE Do not wipe the controller operation panel with benzine thinner chem...

Страница 31: ...s Remove any obstacle and make it well ventilated Check if the user interface display shows time to clean the air filter Refer to 13 Maintenance and service on page 30 and Maintenance in the indoor un...

Страница 32: ...nt overloading of the compressor motor the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before The same starting delay occurs after the operation mode se...

Страница 33: ...nt caused by flow stop or flow change 14 2 10 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency 14 2 11 Symptom Du...

Страница 34: ......

Страница 35: ......

Страница 36: ...4P482256 1 0000000P 4P482256 1 2017 03 Copyright 2017 Daikin...

Отзывы: